Regl. 5293, art. 310-10-430 dup2
MOTOR CIRCUITS, CONTROLLERS
Cite as Reglamento Núm. 5293, Art. 310-10-430 dup2
70-387
Part A. General, Sections 430-1 through 430-18
Part B. Motor Circuit Conductors, Sections 430-21 through 430-29.
Part C. Motor and Branch-Circuit Overload Protection, Sections
430-31 through 430-44.
Part D. Motor Branch-Circuit Short-Circuit and Ground-Fault
Protection, Sections 430-51 through 430-58
Part E. Motor Feeder Short-Circuit and Ground-Fault Protection,
Sections 430-61 through 430-63
Part F. Motor Control Circuits, Sections 430-71 through 430-74.
Part G. Motor Controllers, Sections 430-81 through 430-91.
Part H. Motor Control Centers, Sections 430-92 Through 430-98.
Part 1. Disconnecting Means, Sections 430-101 through 430-113.
Part J. Over 600 Volts, Nominal, Sections 430-121 through 430-127.
Part K. Protection of Live Parts-All Voltages, Sections 430-131
through 430-133.
Part L. Grounding-All Voltages, Sections 430-141 through 430-145.
Part M. Tables, Tables 430-147 through 430-152.
To supply
Part B
Motor feeder
Sec. 430-24
430-25 and 430-26
Motor feeder
short-circuit and
ground-fault protection
Part E
Motor disconnecting
means
Part 1
Motor branch-circuit
short-circuit and
ground-fault protection
Part D
Motor circuit conductor
Part B
Motor controller
Part G
Motor control circuits
Part F
Motor overload
Part C
protection
Motor
Part A
Thermal protection
0
b
Part C
Secondary controller
Part B
Secondary conductors
Sec. 430-23
Secondary resistor
Part B
Sec. 430-23 and Art.
470
(FPN) Diagram 430-1.
70-388
NATIONAL ELECTRICAL CODE
The disconnecting means shall be permitted to be in the incoming line to
the conversion equipment and shall have a rating not less than 115 percent
of the rated input current of the conversion unit.
430-3. Part-Winding Motors. A part-winding-start induction or synchronous motor is one arranged for starting by first energizing part of its primary (armature) winding and, subsequently, energizing the remainder of
this winding in one or more steps. The purpose is to reduce the initial values of the starting current drawn or the starting torque developed by the
motor. A standard part-winding-start induction motor is arranged so that
one-half of its primary winding can be energized initially, and, subsequently, the remaining half can be energized, both halves then carrying
equal current. A hermetic refrigerant compressor motor shall not be considered a standard part-winding-start induction motor.
Where separate overload devices are used with a standard part-windingstart induction motor, each half of the motor winding shall be individually
protected in accordance with Sections 430-32 and 430-37 with a trip current
one-half that specified.
Each motor-winding connection shall have branch-circuit short-circuit
and ground-fault protection rated at not more than one-half that specified
by Section 430-52.
Exception: A single device having this half rating shall be permitted for
both windings if it will allow the motor to start. Where a time-delay (dualelement) fuse is used as a single device for both windings, it shall be permitted to have a rating not exceeding 150 percent of motor full-load
current.
430-5. Other Articles. Motors and controllers shall also comply with the
applicable provisions of the following:
Air-Conditioning and Refrigerating Equipment