Regl. 5293, art. 310-11-328
FLAT CONDUCTOR CABLE
Cite as Reglamento Núm. 5293, Art. 310-11-328
Type FCC
A. General
328-1. Scope. This article covers a field-installed wiring system for
branch circuits incorporating Type FCC cable and associated accessories
as defined by the article. The wiring system is designed for installation
under carpet squares.
328-2. Definitions.
Type FCC Cable: Type FCC cable consists of three or more flat copper conductors placed edge-to-edge and separated and enclosed within an
insulating assembly.
FCC System: A complete wiring system for branch circuits that is
designed for installation under carpet squares. The FCC system includes
Type FCC cable and associated shielding, connectors, terminators, adapters, boxes, and receptacles.
Cable Connector: A connector designed to join Type FCC cables without using a junction box.
Insulating End: An insulator designed to electrically insulate the end of
a Type FCC cable.
Top Shield: A grounded metal shield covering undercarpet components of the FCC system for the purposes of providing protection against
physical damage.
Bottom Shield: A protective layer that is installed between the floor
and Type FCC flat conductor cable to protect the cable from physical
damage and may or may not be incorporated as an integral part of the
cable.
Transition Assembly: An assembly to facilitate connection of the FCC
system to other approved wiring systems, incorporating (1) a means of
electrical interconnection, and (2) a suitable box or covering for providing
electrical safety and protection against physical damage.
Metal Shield Connections: Means of connection designed to electrically and mechanically connect a metal shield to another metal shield, to a
receptacle housing or self-contained device, or to a transition assembly.
328-3. Other Articles. The FCC systems shall conform with applicable
provisions of Articles 210, 220, 240, 250, and 300.
328-4. Uses Permitted.
(a) Branch Circuits. Use of FCC systems shall be permitted both for
general-purpose and appliance branch circuits and for individual branch
circuits.
ARTICLE 328 - FLAT CONDUCTOR CABLE
70-217
(b) Floors. Use of FCC systems shall be permitted on hard, sound,
smooth, continuous floor surfaces made of concrete, ceramic, or composition flooring, wood, and similar materials.
(c) Walls. Use of FCC systems shall be permitted on wall surfaces in
surface metal raceways.
(d) Damp Locations. Use of FCC systems in damp locations shall be
permitted.
(e) Heated Floors. Materials used for floors heated in excess of 30°C
(86°F) shall be identified as suitable for use at these temperatures.
328-5. Uses Not Permitted. FCC systems shall not be used (1) outdoors or
in wet locations; (2) where subject to corrosive vapors; (3) in any hazardous
(classified) location; or (4) in residential, school, and hospital buildings.
328-6. Branch-Circuit Ratings.
(a) Voltage. Voltage between ungrounded conductors shall not exceed
300 volts. Voltage between ungrounded conductors and the grounded con-
I
ductor shall not exceed 150 volts.
(b) Current. General-purpose and appliance branch circuits shall have
ratings not exceeding 20 amperes. Individual branch circuits shall have ratings not exceeding 30 amperes.
B. Installation
328-10. Coverings. Floor-mounted Type FCC cable, cable connectors,
and insulating ends shall be covered with carpet squares no larger than 36
inches (914 mm) square. Those carpet squares that are adhered to the floor
shall be attached with release-type adhesives.
328-11. Cable. Connections and Insulating Ends. All Type FCC cable
connections shall use connectors identified for their use, installed such that
electrical continuity, insulation, and sealing against dampness and liquid
spillage are provided. All bare cable ends shall be insulated and sealed
against dampness and liquid spillage using listed insulating ends.
328-12. Shields.
(a) Top Shield. A metal top shield shall be installed over all floormounted Type FCC cable, connectors, and insulating ends. The top shield
shall completely cover all cable runs, corners, connectors, and ends.
(b) Bottom Shield. A bottom shield shall be installed beneath all Type
FCC cable, connectors, and insulating ends.
328-13. Enclosure and Shield Connections. All metal shields, boxes,
receptacle housings, and self-contained devices shall be electrically-continuous to the equipment grounding conductor of the supplying branch circuit. All
such electrical connections shall be made with connectors identified for this
use. The electrical resistivity of such shield system shall not be more than
that of one conductor of the Type FCC cable used in the installation.
70-218
NATIONAL ELECTRICAL CODE
328-14. Receptacles. All receptacles, receptacle housings, and selfcontained devices used with the FCC system shall be identified for this use
and shall be connected to the Type FCC cable and metal shields. Connection from any grounding conductor of the Type FCC cable shall be made
to the shield system at each receptacle.
328-15. Connection to Other Systems. Power feed, grounding connection, and shield system connection between the FCC system and other
wiring systems shall be accomplished in a transition assembly identified for
this use.
328-16. Anchoring. All FCC system components shall be firmly
anchored to the floor or wall using an adhesive or mechanical anchoring
system identified for this use. Floors shall be prepared to assure adherence
of the FCC system to the floor until the carpet squares are placed.
328-17. Crossings. Crossings of more than two Type FCC cable runs
shall not be permitted at any one point. Crossings of a Type FCC cable
over or under a flat communications or signal cable shall be permitted. In
each case, a grounded layer of metal shielding shall separate the two
cables, and crossings of more than two flat cables shall not be permitted at
any one point.
328-18. System Height. Any portion of an FCC system with a height
above floor level exceeding 0.090 inches (2.29 mm) shall be tapered or
feathered at the edges to floor level.
328-19. FCC Systems Alterations. Alterations to FCC systems shall be
permitted. New cable connectors shall be used at new connection points to
make alterations. It shall be permitted to leave unused cable runs and
associated cable connectors in place and energized. All cable ends shall be
covered with insulating ends.
328-20. Polarization of Connections. All receptacles and connections
shall be constructed and installed so as to maintain proper polarization of
the system.
C. Construction
328-30. Type FCC Cable. Type FCC cable shall be approved for use with
the FCC system and shall consist of three, four, or five flat copper conductors, one of which shall be an equipment grounding conductor. The insulating material of the cable shall be moisture-resistant and flame-retardant.
328-31. Markings. Type FCC cable shall be clearly and durably marked
on both sides at intervals of not more than 24 inches (610 mm) with the
ARTICLE 328 - FLAT CONDUCTOR CABLE
70-219
information required by Section 310-11(a) and with the following additional information: (1) material of conductors; (2) maximum temperature
rating; and (3) ampacity.
328-32. Conductor Identification.
(a) Colors. Conductors shall be clearly and durably marked on both
sides throughout their length as specified in Section 310-12.
(b) Order. For a 2-wire FCC system with grounding, the grounding conductor shall be central.
328-33. Corrosion Resistance. Metal components of the system shall be
either (1) corrosion-resistant; (2) coated with corrosion-resistant materials;
or (3) insulated from contact with corrosive substances.
328-34. Insulation. All insulating materials in the FCC systems shall be
identified for their use.
328-35. Shields.
(a) Materials and Dimensions. All top and bottom shields shall be of
designs and materials identified for their use. Top shields shall be metal.
Both metallic and nonmetallic materials shall be permitted for bottom
shields.
(b) Resistivity. Metal shields shall have cross-sectional areas that pro-
I
vide for electrical resistivity of not more than that of one conductor of the
Type FCC cable used in the installation.
(c) Metal-Shield Connectors. Metal shields shall be connected to each
other and to boxes, receptacle housings, self-contained devices, and transition assemblies using metal-shield connectors.
328-36. Receptacles and Housings. Receptacle housings and selfcontained devices designed either for floor mounting or for in- or on-wall
mounting shall be permitted for use with the FCC system. Receptacle
housings and self-contained devices shall incorporate means for facilitating
entry and termination of Type FCC cable and for electrically connecting
the housing or device with the metal shield. Receptacles and self-contained
devices shall comply with Section 210-7. Power and communications outlets installed together in common housing shall be permitted in accordance
with Section 800-52(c)(2), Exception No. 2.
328-37. Transition Assemblies. All transition assemblies shall be identified for their use. Each assembly shall incorporate means for facilitating entry of the Type FCC cable into the assembly, for connecting the
Type FCC cable to grounded conductors, and for electrically connecting the assembly to the metal cable shields and to equipment grounding
conductors.
70-220
NATIONAL ELECTRICAL CODE