Regl. 5293, art. 310-11-333 dup2
ARMORED CABLE
Cite as Reglamento Núm. 5293, Art. 310-11-333 dup2
70-225
B. Installation
333-7. Support. Type AC cable shall be secured by approved staples,
straps, hangers, or similar fittings so designed and installed as not to damage
the cable at intervals not exceeding 4½ feet (1.37 m) and within 12 inches
(305 mm) of every outlet box, junction box, cabinet or fitting.
Exception No. 1: Where cable is fished.
Exception No. 2: Lengths of not more than 2 feet (610 mm) at terminals
where flexibility is necessary.
Exception No. 3: Lengths of not more than 6 feet (1.83 m) from an outlet for connections within an accessible ceiling to lighting fixtures or equipment.
Exception No. 4: Where installed in cable trays, Type AC cable shall
comply with Section 318-8(b).
333-8. Bending Radius. All bends shall be made so that the cable will not
be damaged, and the radius of the curve of the inner edge of any bend shall
not be less than five times the diameter of the Type AC cable.
333-9. Boxes and Fittings. At all points where the armor of AC cable
terminates, a fitting shall be provided to protect wires from abrasion,
unless the design of the outlet boxes or fittings is such as to afford equivalent protection, and, in addition, an approved insulating bushing or its
equivalent approved protection shall be provided between the conductors
and the armor. The connector or clamp by which the Type AC cable is
fastened to boxes or cabinets shall be of such design that the insulating
bushing or its equivalent will be visible for inspection. This bushing shall
not be required with lead-covered cables where so installed that the lead
sheath will be visible for inspection. Where change is made from Type AC
cable to other cable or raceway wiring methods, a box, fitting, or conduit
body shall be installed at junction points as required in Section 300-15.
333-10. Through or Parallel to Framing Members. Type AC cable shall
comply with Section 300-4 where installed through or parallel to studs,
joists, rafters, or similar wood or metal members.
333-11. Exposed Work. Exposed runs of cable shall closely follow the
surface of the building finish or of running boards.
Exception No. 1: Lengths of not more than 24 inches (610 mm) at terminals where flexibility is necessary.
Exception No. 2: On the underside of floor joists in basements where
supported at each joist and so located as not to be subject to physical
damage.
Exception No. 3: Lengths of not more than 6 feet (1.83 m) from an outlet for connection within an accessible ceiling to lighting fixtures or other
equipment.
70-226
NATIONAL ELECTRICAL CODE
333-12. In Accessible Attics. Type AC cables in accessible attics or roof
spaces shall be installed as specified in (a) and (b) below.
(a) Where Run Across the Top of Floor Joists. Where run across the
top of floor joists, or within 7 feet (2.13 m) of floor or floor joists across the
face of rafters or studding, in attics and roof spaces that are accessible, the
cable shall be protected by substantial guard strips that are at least as high
as the cable. Where this space is not accessible by permanent stairs or ladders, protection shall only be required within 6 feet (1.83 m) of the nearest
edge of the scuttle hole or attic entrance.
(b) Cable Installed Parallel to Framing Members. Where the cable is
installed parallel to the sides of rafters, studs, or floor joists, neither guard
strips nor running boards shall be required, and the installation shall also
comply with Section 300-4(d).
C. Construction Specifications
333-19. Construction. Type AC cable shall have an armor of flexible
metal tape. The insulated conductors shall be in accordance with Section
333-20. Cables of the AC type shall have an internal bonding strip of copper or aluminum in intimate contact with the armor for its entire length.
333-20. Conductors. Insulated conductors shall be of a type listed in
Table 310-13 or those identified for use in this cable. In addition, the conductors shall have an overall moisture-resistant and fire retardant fibrous
covering. For Type ACT, a moisture-resistant fibrous covering shall be
required only on the individual conductors. The ampacity shall be determined by Section 310-15.
Exception: Armored cable installed in thermal insulation shall have
conductors rated at 90°C (194°F). The ampacity of cable installed in these
applications shall be that of 60°C (140°F) conductors.
333-21. Grounding. Type AC cable shall provide an adequate path for
equipment grounding as required by Section 250-51.
333-22. Marking. The provisions of Section 310-11 shall apply, except
that Type AC cable shall have ready identification of the manufacturer by
distinctive external markings on the cable sheath throughout its entire
length. Cables that are flame-retardant and have limited-smoke characteristics shall be permitted to be identified with the suffix LS.