Regl. 5293, art. 310-11-339
UNDERGROUND FEEDER
Cite as Reglamento Núm. 5293, Art. 310-11-339
AND BRANCH-CIRCUIT CABLE
Type UF
339-1. Description and Marking.
(a) Description. Underground feeder and branch-circuit cable shall be
an approved Type UF cable in sizes No. 14 copper or No. 12 aluminum or
copper-clad aluminum through No. 4/0. The conductors of Type UF shall
be one of the moisture-resistant types listed in Table 310-13 that is suitable
for branch-circuit wiring or one that is identified for such use. In addition
to the insulated conductors, the cable shall be permitted to have an
approved size of insulated or bare conductor for equipment grounding purposes only. The overall covering shall be flame-retardant, moisture-,
fungus-, and corrosion-resistant, and suitable for direct burial in the earth.
(b) Marking. In addition to the provisions of Section 310-11, the cable
shall have a distinctive marking on the exterior for its entire length specifying the cable type.
339-2. Other Articles. In addition to the provisions of this article, installations of underground feeder and branch-circuit cable (Type UF) shall
comply with other applicable provisions of this Code, especially Article
300 and Section 310-13.
339-3. Use.
(a) Uses Permitted.
(1) Type UF cable shall be permitted for use underground, including
direct burial in the earth, as feeder or branch-circuit cable where provided
with overcurrent protection of the rated ampacity as required in Section
339-4.
(2) Where single-conductor cables are installed, all cables of the feeder
circuit, subfeeder circuit, or branch circuit, including the neutral and
equipment grounding conductor, if any, shall be run together in the same
trench or raceway.
Exception: For solar photovoltaic systems in accordance with Section
690-31.
(3) For underground requirements, see Section 300-5.
(4) Type UF cable shall be permitted for interior wiring in wet, dry, or
corrosive locations under the recognized wiring methods of this Code, and,
where installed as nonmetallic-sheathed cable, the installation and conductor requirements shall comply with the provisions of Article 336 and shall
be of the multiconductor type.
Exception: Single-conductor cables shall be permitted as the nonheating leads for heating cables as provided in Section 424-43 and in solar
photovoltaic systems in accordance with Section 690-31.
Type UF cable supported by cable trays shall be of the multiconductor
type.
(FPN): See Section 310-10 for temperature limitation of conductors.
70-236
NATIONAL ELECTRICAL CODE
(b) Uses Not Permitted. Type UF cable shall not be used (1) as serviceentrance cables; (2) in commercial garages; (3) in theaters; (4) in motion
picture studios; (5) in storage battery rooms; (6) in hoistways; (7) in any
hazardous (classified) location; (8) embedded in poured cement, concrete,
or aggregate, except where embedded in plaster as nonheating leads as
provided in Article 424; (9) where exposed to direct rays of the sun, unless
identified as sunlight-resistant.
Exception: See Section 501-4(b), Exception.
339-4. Overcurrent Protection. Overcurrent protection shall be provided
in accordance with provisions of Section 240-3.
339-5. Ampacity. The ampacity of Type UF cable shall be that of 60°C
(140°F) conductors in accordance with Section 310-15.