Regl. 5293, art. 310-11-342
NONMETALLIC EXTENSIONS
Cite as Reglamento Núm. 5293, Art. 310-11-342
70-237
318, 501, 502, and 504 in industrial establishments where the conditions of
maintenance and supervision assure that only qualified persons will service
the installation; (4) for Class 1 circuits as permitted in Article 725; (5) for
nonpower-limited fire protective signaling circuits if conductors comply
with the requirements of Section 760-16.
(FPN): See Section 310-10 for temperature limitation of conductors.
340-5. Uses Not Permitted. Type TC tray cable shall not be (1) installed
where they will be exposed to physical damage; (2) installed as open cable
on brackets or cleats; (3) used where exposed to direct rays of the sun,
unless identified as sunlight-resistant; (4) direct buried, unless identified for
such use.
340-6. Marking. The cable shall be marked in accordance with Section
310-11. Cables that are flame-retardant and have limited-smoke characteristics shall be permitted to be identified with the suffix LS.
340-7. Ampacity. The ampacities of the conductors of Type TC tray
cable shall be determined from Section 402-5 for conductors smaller than
No. 14 and from Section 318-11.
340-8. Bends. Bends in Type TC cable shall be made so as not to damage the cable.