Regl. 5293, art. 310-15(d)
Resolución 2535: adopta el Código Eléctrico Nacional, versión 1993. (Sustituye el Anejo A del Reglamento 4435)
Cite as Reglamento Núm. 5293, Art. 310-15(d)
B-310-15(b)(5). Tables B-310-6 and B-310-7.
(1) To obtain the ampacity of cables installed in two electrical ducts in
one horizontal row with 7.5-inch (191-mm) center-to-center spacing
between electrical ducts, similar to Detail 1, Figure B-310-2, multiply the
ampacity shown for one duct in Tables B-310-6 and B-310-7 by 0.88.
(2) To obtain the ampacity of cables installed in four electrical ducts in
one horizontal row with 7.5-inch (191-mm) center-to-center spacing between
electrical ducts, similar to Detail 2, Figure B-310-2, multiply the ampacity
shown for three electrical ducts in Tables B-310-6 and B-310-7 by 0.94.
B-310-15(b)(6). Electrical Ducts Utilized in Figure B-310-2. If spacing
between electrical ducts, as shown in Figure B-310-2, is less than specified
in Figure B-310-2, where electrical ducts enter equipment enclosures from
underground, the ampacity of conductors contained within such electrical
ducts need not be reduced.
B-310-15(b)(7). Examples Showing Use of Figure B-310-1 for Electrical
Duct Bank Ampacity Modifications. Figure B-310-1 is used for interpolation or extrapolation for values of Rho and load factor for cables installed in
electrical ducts. The upper family of curves shows the variation in ampacity
and Rho at unity load factor in terms of I₁, the ampacity for Rho = 60, and
50 percent load factor. Each curve is designated for a particular ratio I₂/I₁,
where I₂ is the ampacity at Rho = 120 and 100 percent load factor.
The lower family of curves shows the relationship between Rho and load
factor that will give substantially the same ampacity as the indicated value of
Rho at 100 percent load factor.
As an example, to find the ampacity of a 500 kcmil copper cable circuit for six
electrical ducts as shown in Table B-310-5: At the Rho = 60, LF = 50,
I₁ = 583; for Rho = 120 and LF = 100, I₂ = 400. The ratio I₂/I₁ = 0.686. Locate
Rho = 90 at bottom of chart and follow the 90 Rho line to the intersection with
100 percent load factor where the equivalent Rho = 90. Then follow the 90 Rho
line to I₂/I₁ ratio of 0.686 where F = 0.74. The desired ampacity = 0.74 X 583 =
431, which agrees with the table for Rho = 90, LF = 100.
To determine the ampacity for the same circuit where Rho = 80 and LF =
75, using Figure B-310-1, the equivalent Rho = 43, F = 0.855, and the desired
ampacity = 0.855 X 583 = 498 amperes. Values for using Figure B-310-1 are
found in the electrical duct bank ampacity tables of this appendix.
Where the load factor is less than 100 percent and can be verified by
measurement or calculation, the ampacity of electrical duct bank installations can be modified as shown. Different values of Rho can be accommodated in the same manner.
APPENDIX B
70-857
Table B-310-1. Ampacities of Two or Three Insulated Conductors,
Rated 0 through 2000 Volts, within an Overall Covering
(Multiconductor Cable), in Raceway in Free Air
Based on Ambient Air Temperature of 30°C (86°F)
Size
Temperature Rating of Conductor. See Table 310-13.
Size
60°C
75°C
90°C
60°C
75°C
90°C
(140°F)
(167°F)
(194°F)
(140°F)
(167°F)
(194°F)
TYPES
TYPES
TYPES
TYPE
TYPES
TYPES
AWG
TW, UF
RH, RHW,
THHN,
TW
RH, RHW,
THHN,
AWG
THHW, THW,
THHW,
THHW, THW,
THHW,
kcmil
THWN,
THW-2,
THWN,
THW-2,
kcmil
XHHW,
THWN-2,
XHHW
THWN-2,
ZW
RHH,
RHH,
RWH-2,
RWH-2,
USE-2,
USE-2,
XHHW
XHHW,
XHHW-2,
XHHW-2,
ZW-2
ZW-2
COPPER
ALUMINUM OR COPPER-CLAD
ALUMINUM
14
16+
18+
21+
14
12
20+
24+
27+
16+
18+
21+
12
10
27+
33+
36+
21+
25+
28+
10
8
36
43
48
28
33
37
8
6
48
58
65
38
45
51
6
4
66
79
89
51
61
69
4
3
76
90
102
59
70
79
3
2
88
105
119
69
83
93
2
1
102
121
137
80
95
106
1
1/0
121
145
163
94
113
127
1/0
2/0
138
166
186
108
129
146
2/0
3/0
158
189
214
124
147
167
3/0
4/0
187
223
253
147
176
197
4/0
250
205
245
276
160
192
217
250
300
234
281
317
185
221
250
300
350
255
305
345
202
242
273
350
400
274
328
371
218
261
295
400
500
315
378
427
254
303
342
500
600
343
413
468
279
335
378
600
700
376
452
514
310
371
420
700
750
387
466
529
321
384
435
750
800
397
479
543
331
397
450
800
900
415
500
570
350
421
477
900
1000
448
542
617
382
460
521
1000
Amblent
For ambient temperatures other than 30°C (86°F), multiply the ampacities shown above by
Ambient
Temp. °C
the appropriate factor shown below.
Temp. °F
21-25
1.08
1.05
1.04
1.08
1.05
1.04
70-77
26-30
1.00
1.00
1.00
1.00
1.00
1.00
79-86
31-35
.91
.94
.96
.91
.94
.96
88-95
36-40
.82
.88
.91
.82
.88
.91
97-104
41-45
.71
.82
.87
.71
.82
.87
106-113
46-50
.58
.75
.82
.58
.75
.82
115-122
51-55
.41
.67
.76
.41
.67
.76
124-131
56-60
.58
.71
.58
.71
133-140
61-70
.33
.58
.33
.58
142-158
71-80
.41
.41
160-176
t Unless otherwise specifically permitted elsewhere in this Code, the overcurrent protection for conductor types marked with an obelsik (f) shall not exceed 15 amperes for No. 14,
20 amperes for No. 12, and 30 amperes for No. 10 copper; or 15 amperes for No. 12 and 25
amperes for No. 10 aluminum and copper-clad aluminum.
70-858
NATIONAL ELECTRICAL CODE
Table B-310-2. Ampacities of Two or Three Single Insulated Conductors,
Rated 0 through 2000 Volts, Supported on a Messenger,
Based on Ambient Air Temperature of 40°C (104°F)
Size
Temperature Rating of Conductor. See Table 310-13.
Size
75°C (167°F)
90°C (194°F)
75°C (167°F)
90°C (194°F)
TYPES
TYPES
TYPES
TYPES
AWG
RH, RHW,
THHN, THHW,
RH, RHW,
THHN, THHW,
AWG
THHW, THW,
THW-2, THWN-2,
THW, THWN,
RHH, XHHW,
kcmil
THWN,
RHH, RWH-2,
THHW, XHHW
RHW-2, XHHW-2,
kcmil
XHHW, zw
USE-2, XHHW,
THW-2, THWN-2,
XHHW-2, ZW-2
USE-2, ZW-2
COPPER
ALUMINUM OR COPPER-CLAD ALUMINUM
8
57
66
44
51
8
6
76
89
59
69
6
4
101
117
78
91
4
3
118
138
92
107
3
2
135
158
106
123
2
1
158
185
123
144
1
1/0
183
214
143
167
1/0
2/0
212
247
165
193
2/0
3/0
245
287
192
224
3/0
4/0
287
335
224
262
4/0
250
320
374
251
292
250
300
359
419
282
328
300
350
397
464
312
364
350
400
430
503
339
395
400
500
496
580
392
458
500
600
553
647
440
514
600
700
610
714
488
570
700
750
638
747
512
598
750
800
660
773
532
622
800
900
704
826
572
669
900
1000
748
879
612
716
1000
Ambient
For ambient temperatures other than 40°C (104°F), multiply the ampacities
Ambient
Temp. °C
shown above by the appropriate factor shown below.
Temp. °F
21-25
1.20
1.14
1.20
1.14
70-77
26-30
1.13
1.10
1.13
1.10
79-86
31-35
1.07
1.05
1.07
1.05
88-95
36-40
1.00
1.00
1.00
1.00
97-104
41-45
.93
.95
.93
.95
106-113
46-50
.85
.89
.85
.89
115-122
51-55
.76
.84
.76
.84
124-131
56-60
.65
.77
.65
.77
133-140
61-70
.38
.63
.38
.63
142-158
71-80
.45
.45
160-176
APPENDIX B
70-859
Table B-310-3. Ampacities of Multiconductor Cables with not
more than Three Insulated Conductors, Rated 0 through 2000 Volts,
in Free Air. Based on Ambient Air Temperature of 40°C (104°F)
(For TC, MC, MI, UF, USE, and SNM cables)
Size
Temperature Rating of Conductor. See Table 310-13.
Size
60°C
75°C
85°C
90°C
60°C
75°C
85°C
90°C
AWG
(140°F)
(167°F)
(185°F)
(194°F)
(140°F)
(167°F)
(185°F)
(194°F)
AWG
kcmil
COPPER
ALUMINUM OR COPPER-CLAD ALUMINUM
kcmil
18
11+
18
16
16+
16
14
18+
21+
24+
25+
14
12
21+
28+
30+
32+
18+
21+
24+
25+
12
10
28+
36+
41+
43+
21+
28+
30+
32+
10
8
39
50
56
59
30
39
44
46
8
6
52
68
75
79
41
53
59
61
6
4
69
89
100
104
54
70
78
81
4
3
81
104
116
121
63
81
91
95
3
2
92
118
132
138
72
92
103
108
2
1
107
138
154
161
84
108
120
126
1
1/0
124
160
178
186
97
125
139
145
1/0
2/0
143
184
206
215
111
144
160
168
2/0
3/0
165
213
238
249
129
166
185
194
3/0
4/0
190
245
274
287
149
192
214
224
4/0
250
212
274
305
320
166
214
239
250
250
300
237
306
341
357
186
240
268
280
300
350
261
337
377
394
205
265
296
309
350
400
281
363
406
425
222
287
317
334
400
500
321
416
465
487
255
330
368
385
500
600
354
459
513
538
284
368
410
429
600
700
387
502
562
589
306
405
462
473
700
750
404
523
586
615
328
424
473
495
750
800
415
539
604
633
339
439
490
513
800
900
438
570
639
670
362
469
514
548
900
1000
461
601
674
707
385
499
558
584
1000
Ambient
For ambient temperatures other than 30°C (86°F), multiply the ampacities shown above by
Ambient
Temp. °C
the appropriate factor shown below.
Temp. °F
21-25
1.32
1.20
1.15
1.14
1.32
1.20
1.15
1.14
70-77
26-30
1.22
1.13
1.11
1.10
1.22
1.13
1.11
1.10
79-86
31-35
1.12
1.07
1.05
1.05
1.12
1.07
1.05
1.05
88-95
36-40
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
97-104
41-45
.87
.93
.94
.95
.87
.93
.94
.95
106-113
46-50
.71
.85
.88
.89
.71
.85
.88
.89
115-122
51-55
.50
.76
.82
.84
.50
.76
.82
.84
124-131
56-60
.65
.75
.77
.65
.75
.77
133-140
61-70
.38
.58
.63
.38
.58
.63
142-158
71-80
.33
.44
.33
.44
160-176
t Unless otherwise specifically permitted elsewhere in this Code, the overcurrent protection for conductor types marked with an obelisk (t) shall not exceed 15 amperes for No. 14,
20 amperes for No. 12, and 30 amperes for No. 10 copper; or 15 amperes for No. 12 and 25
amperes for No. 10 aluminum and copper-clad aluminum.
70-860
NATIONAL ELECTRICAL CODE
Table B-310-4. Ampacities for Bare or Covered Conductors
Based on 40°C (104°F) Ambient, 80°C (176°F)
Total Conductor Temperature,
2 Feet (610 mm) per Second Wind Velocity
Bare Copper Conductors
Covered Copper Conductors
AWG
AWG
kcmil
AMPS
kcmil
AMPS
8
98
8
103
6
124
6
130
4
155
4
163
2
209
2
219
1/0
282
1/0
297
2/0
329
2/0
344
3/0
382
3/0
401
4/0
444
4/0
466
250
494
250
519
300
556
300
584
500
773
500
812
750
1000
750
1050
1000
1193
1000
1253
Covered AAC
Bare AAC Aluminum Conductors
Aluminum Conductors
AWG
AWG
kcmil
AMPS
kcmil
AMP
8
76
8
80
6
96
6
101
4
121
4
127
2
163
2
171
1/0
220
1/0
231
2/0
255
2/0
268
3/0
297
3/0
312
4/0
346
4/0
364
266.8
403
266.8
423
336.4
468
336.4
492
397.5
522
397.5
548
477.0
588
477.0
617
556.5
650
556.5
682
636.0
709
636.0
744
795.0
819
795.0
860
954.0
920
1033.5
968
1033.5
1017
1272
1103
1272
1201
1590
1267
1590
1381
2000
1454
2000
1527
Table B-310-5. Ampacities of Single Insulated Conductors, Rated 0 through 2000 Volts, in Nonmagnetic Underground
Electrical Ducts (One Conductor per Electrical Duct) Based on Ambient Earth Temperature of 20°C (68°F), Electrical Duct
Arrangement per Figure B-310-2, Conductor Temperature 75°C (167°F)
Size
Size
3 Electrical Ducts
6 Electrical Ducts
9 Electrical Ducts
3 Electrical Ducts
6 Electrical Ducts
9 Electrical Ducts
(Fig. B-310-2 Detail 2)
(Fig. B-310-2 Detail 3)
(Fig. B-310-2 Detail 4)
(Fig. B-310-2 Detail 2)
(Fig. B-310-2 Detail 3)
(Fig. B-310-2 Detail 4)
kcmil
kcmil
TYPES
TYPES
TYPES
TYPES
TYPES
TYPES
RHW, THHW, THW,
RHW, THHW, THW,
RHW, THHW, THW,
RHW, THHW, THW,
RHW, THHW, THW,
RHW, THHW, THW,
THWN, XHHW, USE
THWN, XHHW, USE
THWN, XHHW, USE
THWN, XHHW, USE
THWN, XHHW, USE
THWN, XHHW, USE
COPPER
ALUMINUM OR COPPER-CLAD ALUMINUM
RHO
RHO
RHO
RHO
RHO
RHO
RHO
RHO
RHO
RHO
RHO
RHO
RHO
RHO
RHO
RHO
RHO
RHO
60
90
120
60
90
120
60
90
120
60
90
120
60
90
120
60
90
120
LF
LF
LF
LF
LF
LF
LF
LF
LF
LF
LF
LF
LF
LF
LF
LF
LF
LF
50
100
100
50
100
100
50
100
100
50
100
100
50
100
100
50
100
100
250
410
344
327
386
295
275
369
270
252
320
269
256
302
230
214
288
211
197
250
350
503
418
396
472
355
330
446
322
299
393
327
310
369
277
258
350
252
235
250
500
624
511
484
583
431
400
545
387
360
489
401
379
457
337
313
430
305
284
500
APPENDIX B
750
794
640
603
736
534
494
674
469
434
626
505
475
581
421
389
538
375
347
750
1000
936
745
700
864
617
570
776
533
493
744
593
557
687
491
453
629
432
399
1000
1250
1055
832
781
970
686
632
854
581
536
848
668
627
779
551
508
703
478
441
1250
1500
1160
907
849
1063
744
685
918
619
571
941
736
689
863
604
556
767
517
477
1500
1750
1250
970
907
1142
793
729
975
651
599
1026
796
745
937
651
598
823
550
507
1750
2000
1332
1027
959
1213
836
768
1030
683
628
1103
850
794
1005
693
636
877
581
535
2000
Ambient
Ambient
Temp. °C
For ambient temperatures other than 20°C (68°F), multiply the ampacitles shown above by the appropriate factor shown below.
Temp. °F
6-10
1.09
1.09
1.09
1.09
1.09
1.09
43-50
11-15
1.04
1.04
1.04
1.04
1.04
1.04
52-59
16-20
1.00
1.00
1.00
1.00
1.00
1.00
61-68
21-25
.95
.95
.95
.95
.95
.95
70-77
70-861
26-30
.90
.90
.90
.90
.90
.90
79-86
Table B-310-6. Ampacities of Three Insulated Conductors, Rated 0 through 2000 Volts, within an Overall Covering
(Three-Conductor Cable) in Underground Electrical Ducts (One Cable per Electrical Duct)
Based on Ambient Earth Temperature of 20°C (68°F), Electrical Duct
70-862
Arrangement per Figure B-310-2, Conductor Temperature 75°C (167°F)
Size
Size
1 Electrical Duct
3 Electrical Ducts
6 Electrical Ducts
1 Electrical Duct
3 Electrical Ducts
6 Electrical Ducts
AWG
(Fig. B-310-2 Detail 1)
(Fig. B-310-2 Detail 2)
(Fig. B-310-2 Detail 3)
(Fig. B-310-2 Detail 1)
(Fig. B-310-2 Detail 2)
(Fig. B-310-2 Detail 3)
AWG
TYPES
TYPES
TYPES
TYPES
TYPES
TYPES
kcmil
RHW, THHW, THW,
RHW, THHW, THW,
RHW, THHW, THW,
RHW, THHW, THW,
RHW, THHW, THW,
RHW, THHW, THW,
kcmil
THWN, XHHW, USE
THWN, XHHW, USE
THWN, XHHW, USE
THWN, XHHW, USE
THWN, XHHW, USE
THWN, XHHW, USE
COPPER
ALUMINUM OR COPPER-CLAD ALUMINUM
RHO
RHO
RHO
RHO
RHO
RHO
RHO
RHO
RHO
RHO
RHO
RHO
RHO
RHO
RHO
RHO
RHO
RHO
60
90
120
60
90
120
60
90
120
60
90
120
60
90
120
60
90
120
LF
LF
LF
LF
LF
LF
LF
LF
LF
LF
LF
LF
LF
LF
LF
LF
LF
LF
50
100
100
50
100
100
50
100
100
50
100
100
50
100
100
50
100
100
8
58
54
53
56
48
46
53
42
39
45
42
41
43
37
36
41
32
30
8
6
77
71
69
74
63
60
70
54
51
60
55
54
57
49
47
54
42
39
6
4
101
93
91
96
81
77
91
69
65
78
72
71
75
63
60
71
54
51
4
2
132
121
118
126
105
100
119
89
83
103
94
92
98
82
78
92
70
65
2
1
154
140
136
146
121
114
137
102
95
120
109
106
114
94
89
107
79
74
1
1/0
177
160
156
168
137
130
157
116
107
138
125
122
131
107
101
122
90
84
1/0
2/0
203
183
178
092
156
147
179
131
121
158
143
139
150
122
115
140
102
95
2/0
3/0
233
210
204
221
178
158
205
148
137
182
164
159
172
139
131
160
116
107
3/0
NATIONAL ELECTRICAL CODE
4/0
268
240
232
253
202
190
234
168
155
209
187
182
198
158
149
183
131
121
4/0
250
297
265
256
280
222
209
258
184
169
233
207
201
219
174
163
505
144
132
250
350
363
321
310
340
267
250
312
219
202
285
252
244
267
209
196
245
172
158
350
500
444
389
375
414
320
299
377
261
240
352
308
297
328
254
237
299
207
190
500
750
552
478
459
511
388
362
462
314
288
446
386
372
413
314
293
374
254
233
750
1000
628
539
518
579
435
405
522
351
321
521
447
430
480
361
336
433
291
266
1000
Ambient
Ambient
Temp. °C
For ambient temperatures other than 20°C (68°F), multiply the ampacities shown above by the appropriate factor shown below.
Temp. °F
6-10
1.09
1.09
1.09
1.09
1.09
1.09
43-50
11-15
1.04
1.04
1.04
1.04
1.04
1.04
52-59
16-20
1.00
1.00
1.00
1.00
1.00
1.00
61-68
21-25
.95
.95
.95
.95
.95
.95
70-77
26-30
.90
.90
.90
.90
.90
.90
79-86
Table B-310-7. Ampacities of Three Single Insulated Conductors, Rated 0 through 2000 Volts, in Underground Electrical
Ducts (Three Conductors per Electrical Duct) Based on Ambient Earth Temperature of 20°C (68°F), Electrical Duct
Arrangement per Figure B-310-2, Conductor Temperature 75°C (167°F)
Size
Size
1 Electrical Duct
3 Electrical Ducts
6 Electrical Ducts
1 Electrical Duct
3 Electrical Ducts
6 Electrical Ducts
(Fig. B-310-2 Detail 1)
(Fig. B-310-2 Detail 2)
(Fig. B-310-2 Detail 3)
(Fig. B-310-2 Detail 1)
(Fig. B-310-2 Detail 2)
(Fig. B-310-2 Detail 3)
AWG
TYPES
TYPES
TYPES
TYPES
TYPES
TYPES
AWG
RHW, THHW, THW,
RHW, THHW, THW,
RHW, THHW, THW,
RHW, THHW, THW,
RHW, THHW, THW,
RHW, THHW, THW,
THWN, XHHW, USE
THWN, XHHW, USE
THWN, XHHW, USE
THWN, XHHW, USE
THWN, XHHW, USE
kcmil
kcmil
THWN, XHHW, USE
COPPER
ALUMINUM OR COPPER-CLAD ALUMINUM
RHO
RHO
RHO
RHO
RHO
RHO
RHO
RHO
RHO
RHO
RHO
RHO
RHO
RHO
RHO
RHO
RHO
RHO
60
90
120
60
90
120
60
90
120
60
90
120
60
90
120
60
90
120
LF
LF
LF
LF
LF
LF
LF
LF
LF
LF
LF
LF
LF
LF
LF
LF
LF
LF
50
100
100
50
100
100
50
100
100
50
100
100
50
100
100
50
100
100
8
63
58
57
61
51
49
57
44
41
49
45
44
47
40
38
45
34
32
8
67
63
75
56
53
66
60
58
63
52
49
59
44
41
6
6
84
77
75
80
4
111
100
98
105
86
81
98
73
67
86
78
76
79
67
63
77
57
52
4
3
129
116
113
122
99
94
113
83
77
101
91
89
83
77
73
84
65
60
3
2
147
132
128
139
112
106
129
93
86
115
103
100
108
87
82
101
73
67
2
115
126
100
94
116
83
77
1
1
171
153
148
161
128
121
149
106
98
133
119
1/0
197
175
169
185
146
137
170
121
111
153
136
132
144
114
107
133
94
87
1/0
121
151
106
98
2/0
2/0
226
200
193
212
166
156
194
136
126
176
156
151
165
130
3/0
260
228
220
243
189
177
222
154
142
203
178
172
189
147
138
173
121
111
3/0
APPENDIX B
126
4/0
4/0
301
263
253
280
215
201
255
175
161
235
205
198
219
168
157
199
137
334
290
279
310
236
220
281
192
176
261
227
218
242
185
172
220
150
137
250
250
300
373
321
308
344
260
242
310
210
192
293
252
242
272
204
190
245
165
151
300
377
283
264
340
228
209
321
276
265
296
222
207
266
179
164
350
350
409
351
337
400
442
376
361
394
302
280
368
243
223
349
297
284
321
238
220
288
191
174
400
500
503
427
409
460
341
316
412
273
249
397
338
323
364
270
250
326
216
197
500
600
552
468
447
511
371
343
457
296
270
446
373
356
408
296
274
365
236
215
600
700
602
509
486
553
402
371
492
319
291
488
408
389
443
321
297
394
255
232
700
750
632
529
505
574
417
385
509
330
301
508
425
405
461
334
309
409
265
241
750
800
654
544
520
597
428
395
527
338
308
530
439
418
481
344
318
427
273
247
800
900
692
575
549
628
450
415
554
355
323
563
466
444
510
365
337
450
288
261
900
475
304
276
1000
1000
730
605
576
659
472
435
581
372
338
597
494
471
538
385
355
Ambient
Ambient
Temp. °C
For ambient temperatures other than 20°C (68°F), multiply the ampacities shown above by the appropriate factor shown below.
Temp. °F
6-10
1.09
1.09
1.09
1.09
1.09
1.09
43-50
11-15
1.04
1.04
1.04
1.04
1.04
1.04
52-59
16-20
1.00
1.00
1.00
1.00
1.00
1.00
61-68
70-863
21-25
.95
.95
.95
.95
.95
.95
70-77
26-30
.90
.90
.90
.90
.90
.90
79-86
70-864
NATIONAL ELECTRICAL CODE
Table B-310-8. Ampacities of Two or Three Insulated Conductors,
Rated 0 through 2000 Volts, Cabled within an Overall
(Two-or-Three Conductor) Covering, Directly Buried in Earth
Based on Ambient Earth Temperature of 20°C (68°F),
Arrangement per Figure B-310-2, 100 Percent Load Factor,
Thermal Resistance (RHO) of 90
Size
Size
1 Cable
2 Cables
1 Cable
2 Cables
(Fig. B-310-2
(Fig. B-310-2
(Fig. B-310-2
(Fig. B-310-2
Detail 5)
Detail 6)
Detail 5)
Detail 6)
60°C
75°C
60°C
75°C
60°C
75°C
60°C
75°C
(140°F)
(167°F)
(140°F)
(167°F)
(140°F)
(167°F)
(140°F)
(167°F)
TYPES
TYPES
TYPES
TYPES
RHW,
RHW,
RHW,
RHW,
THHW,
THHW,
THHW,
THHW,
THW,
THW,
THW,
THW,
AWG
UF
THWN,
UF
THWN,
UF
THWN,
UF
THWN,
AWG
XHHW,
XHHW,
XHHW,
XHHW,
kcmll
USE
USE
USE
USE
kcmil
ALUMINUM OR COPPER-CLAD
COPPER
ALUMINUM
8
64
75
60
70
51
59
47
55
8
6
85
100
81
95
68
75
60
70
6
4
107
125
100
117
83
97
78
91
4
2
137
161
128
150
107
126
110
117
2
1
155
182
145
170
121
142
113
132
1
1/0
177
208
165
193
138
162
129
151
1/0
2/0
201
236
188
220
157
184
146
171
2/0
3/0
229
269
213
250
179
210
166
195
3/0
4/0
259
304
241
282
203
238
188
220
4/0
250
333
308
261
241
250
350
401
370
315
290
350
500
481
442
381
350
500
750
585
535
473
433
750
1000
657
600
545
497
1000
Ambient
For ambient temperatures other than 20°C (68°F), multiply the ampacities shown above by
Ambient
Temp. °C
the appropriate factor shown below.
Temp. °F
6-10
1.12
1.09
1.12
1.09
1.12
1.09
1.12
1.09
43-50
11-15
1.06
1.04
1.06
1.04
1.06
1.04
1.06
1.04
52-59
16-20
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
61-68
21-25
.94
.95
.94
.95
.94
.95
.94
.95
70-77
26-30
.87
.90
.87
.90
.87
.90
.87
.90
79-86
For ampacities of UF cable in underground electrical ducts, multiply the ampacities
shown in the table by 0.74.
APPENDIX B
70-865
Table B-310-9. Ampacities of Three Triplexed Single Insulated
Conductors, Rated 0 through 2000 Volts, Directly Buried in Earth
Based on Ambient Earth Temperature of 20°C (68°F),
Arrangement per Figure B-310-2, 100 Percent Load Factor,
Thermal Resistance (RHO) of 90
Size
Size
See
See
See
See
Fig. B-310-2
Fig. B-310-2
Fig. B-310-2
Fig. B-310-2
Detail 7
Detail 8
Detail 7
Detail 8
60°C
75°C
60°C
75°C
60°C
75°C
60°C
75°C
(140°F)
(167°F)
(140°F)
(167°F)
(140°F)
(167°F)
(140°F)
(167°F)
AWG
TYPES
TYPES
TYPES
TYPES
AWG
kcmil
UF
USE
UF
USE
UF
USE
UF
USE
kcmil
ALUMINUM OR COPPER-CLAD
COPPER
ALUMINUM
8
72
84
66
77
55
65
51
60
8
6
91
107
84
99
72
84
66
77
6
4
119
139
109
128
92
108
85
100
4
2
153
179
140
164
119
139
109
128
2
1
173
203
159
186
135
158
124
145
1
1/0
197
231
181
212
154
180
141
165
1/0
2/0
223
262
205
240
175
205
159
187
2/0
3/0
254
298
232
272
199
233
181
212
3/0
4/0
289
339
263
308
226
265
206
241
4/0
250
370
336
289
263
250
350
445
403
349
316
350
500
536
483
424
382
500
750
654
587
525
471
750
1000
744
665
608
544
1000
Ambient
For ambient temperatures other than 20°C (68°F), multiply the ampacities shown above by
Ambient
Temp. °C
the appropriate factor shown below.
Temp. °F
6-10
1.12
1.09
1.12
1.09
1.12
1.09
1.12
1.09
43-50
11-15
1.06
1.04
1.06
1.04
1.06
1.04
1.06
1.04
52-59
16-20
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
61-68
21-25
.94
.95
.94
.95
.94
.95
.94
.95
70-77
26-30
.87
.90
.87
.90
.87
.90
.87
.90
79-86
70-866
NATIONAL ELECTRICAL CODE
Table B-310-10. Ampacities of Three Single Insulated Conductors,
Rated 0 through 2000 Volts, Directly Buried in Earth
Based on Ambient Earth Temperature of 20°C (68°F),
Arrangement per Figure B-310-2, 100 Percent Load Factor,
Thermal Resistance (RHO) of 90
Size
Size
See
See
See
See
Fig. B-310-2
Fig. B-310-2
Fig. B-310-2
Fig. B-310-2
Detail 9
Detail 10
Detail 9
Detail 10
60°C
75°C
60°C
75°C
60°C
75°C
60°C
75°C
(140°F)
(167°F)
(140°F)
(167°F)
(140°F)
(167°F)
(140°F)
(167°F)
AWG
TYPES
TYPES
TYPES
TYPES
AWG
kcmil
UF
USE
UF
USE
UF
USE
UF
USE
kcmil
ALUMINUM OR COPPER-CLAD ALU-
COPPER
MINUM
8
84
98
78
92
66
77
61
72
8
6
107
126
101
118
84
98
78
92
6
4
139
163
130
152
108
127
101
118
4
2
178
209
165
194
139
163
129
151
2
1
201
236
187
219
157
184
146
171
1
1/0
230
270
212
249
179
210
165
194
1/0
2/0
261
306
241
283
204
239
188
220
2/0
3/0
297
348
274
321
232
272
213
250
3/0
4/0
336
394
309
362
262
307
241
283
4/0
250
429
394
335
308
250
350
516
474
403
370
350
500
626
572
490
448
500
750
767
700
605
552
750
1000
887
808
706
642
1000
1250
979
891
787
716
1250
1500
1063
965
862
783
1500
1750
1133
1027
930
843
1750
2000
1195
1082
990
897
2000
Ambient
For ambient temperatures other than 20°C (68°F), multiply the ampacities shown above by
Ambient
Temp. °C
the appropriate factor shown below.
Temp. °F
6-10
1.12
1.09
1.12
1.09
1.12
1.09
1.12
1.09
43-50
11-15
1.06
1.04
1.06
1.04
1.06
1.04
1.06
1.04
52-59
16-20
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
61-68
21-25
.94
.95
.94
.95
.94
.95
.94
.95
70-77
26-30
.87
.90
.87
.90
.87
.90
.87
.90
79-86
APPENDIX B
70-867
1.15
1.10
1.05
1.00
1,00
.95
0.95
0.95
.90
0.90
.85
0.90
0.85
.80
-F-
0.80
0.85
I
.75
0.75
0.80
Ratio 12/1
.70
0.70
.65
0.75
0.65
.60
0.70
0.60
:55
0.65
0.55
.50
0.60
0.50
.45
0.55
40
0.50
10
20
30
40
50
60
70
80
90
100
110
120
130
140
150
160
170
180
190
200
100
95
90
85
80
75
70
Load Factor
65
60
55
50
45
40
35
30
0
10
20
30
40
50
60
70
80
90
100
110
120
130
140
150
160
170
180
190
200
RHO
Figure B-310-1. Interpolation Chart for Cables in a
Duct Bank I₁ = Ampacity for Rho - 60, 50 LF;
I₂ = Ampacity for Rho-120, 100 LF;
Desired Ampacity = F X I₁
70-868
NATIONAL ELECTRICAL CODE
a
7.51
Detail 1
A
7.5" 7.5",7.5"
7.5" 7.5",7.5"
D
A
11.5"x11.5"
0
Electrical duct bank
7.5"
One electrical duct
Detail 2
D
19"x19"
7.5
7.5'
7.5
Electrical duct bank
Detail 3
Detail 4
Three electrical ducts
19"x27"
27"x27"
Electrical duct bank
Electrical duct bank
Or
Six electrical ducts
Nine electrical ducts
Or
0
D
:
7.5'
7.5
7.5
5
0
27"x11.5"
A
Electrical duct bank
Three electrical ducts
7.5
7.5
27"x19"
Electrical duct bank
Six electrical ducts
24"
24"
Detail 5
Detail 6
Detail 7
Detail 8
Buried 3
Buried 3
Buried triplexed
conductor
Buried triplexed cables
conductor
cables (1 circuit)
(2 circuits)
cable
cables
7.5'
7.5'
7.5"
7.5"
24"
7.5"
7.5'
Detail 9
Detail 10
Buried single conductor
Buried single conductor
cables (1 circuit)
cables (2 circuits)
Notes for all details:
1. Minimum burial depths to top electrical ducts or
Legend
cables shall be in accordance with Section 300-5.
Backfill
Maximum depth to the top of electrical duct banks shall
(earth or concrete)
be 30 inches and maximum depth to the top of direct
buried cables shall be 36 inches.
Electrical duct
2. For two and four electrical duct installations with
electrical ducts installed in a single row, see Section
Cable or cables
B-310-15(b)( (5).
3. For SI units: one inch = 25.4 millimeters; one foot = 305 millimeters.
Figure B-310-2. Cable Installation Dimensions for Use With Tables B-5 through B-10
APPENDIX B
70-869
Figure B-310-3. Ampacities of Single Insulated Conductors
Rated 0 through 5000 Volts in Underground Electrical
Ducts (Three Conductors per Electrical Duct)
Nine Single-Conductor Cables per Phase
Based on Ambient Earth Temperature of 20°C (68°F),
Conductor Temperature 75°C (167°F)
Surface
Design Criteria
6"
N&
24"
Neutral and Electrical Grounding
EGC
6"
Conductor (EGC) Duct = 6 inch
0
Phase Ducts = 3 to 5 inch
Conductor Material = Copper
7.5
D
30"
Number of Cables per Duct =3
Number of Cables per Phase = 9
7.5"
0
1. (Typical
Rho Concrete = Rho Earth - 5
for all)
4
Rho PVC Duct = 650
Rho Cable Insulation = 500
Rho Cable Jacket = 650
7.5"
7.5'
27"
NOTES:
Neutral configuration per Section 300-5(i), Exception No. 2 for isolated phase installations
in nonmagnetic ducts.
Phasing is A, B, C in rows or columns. Where magnetic electrical ducts are used, conductors are installed A, B, C per electrical duct with the neutral and all equipment grounding
conductors in the same electrical duct. In this case, the 6-inch trade size neutral duct is
eliminated.
Maximum harmonic loading on the neutral conductor cannot exceed 50 percent of the
phase current for the ampacities shown in the table.
Metallic shields of Type MV-75 cable shall be grounded at one point only where using A,
B, C phasing in rows or columns.
For SI units: one inch = 25.4 millimeters.
Size
Types
Size
RHW, THHW, THW, THWN,
XHHW, USE, OR MV-75
kcmil
Total Per Phase Ampere Rating
kcmil
RHO EARTH 60
RHO EARTH 90
RHO EARTH 120
LF 50
LF 100
LF 100
250
2340
1530
1395
250
(260A/Cable)
(170A/Cable)
(155A/Cable)
350
2790
1800
1665
350
(310A/Cable)
(200A/Cable)
(185A/Cable)
500
3375
2160
1980
500
(375A/Cable)
(240A/Cable)
(220A/Cable)
For ambient temperatures other than 20°C (68°F), multiply the ampacities shown
Ambient
Ambient
Temp. °C
above by the appropriate factor shown below.
Temp. °F
6-10
1.09
1.09
1.09
1.09
1.09
43-50
11-15
1.04
1.04
1.04
1.04
1.04
52-59
16-20
1.00
1.00
1.00
1.00
1.00
61-68
21-25
.95
.95
.95
.95
.95
70-77
26-30
.90
.90
.90
.90
.90
79-86
70-870
NATIONAL ELECTRICAL CODE
Figure B-310-4. Ampacities of Single Insulated Conductors
Rated 0 through 5000 Volts in Nonmagnetic Underground
Electrical Ducts (One Conductor per Electrical Duct)
Four Single-Conductor Cables per Phase
Based on Ambient Earth Temperature of 20°C (68°F),
Conductor Temperature 75°C (167°F)
Surface
6"
N &
EGC
6
24"
D
0
AO
0
10
0
38"
BO
Design Criteria
10
D
0
Neutral and Electrical
Grounding Conductor Duct = 6 inch
CO
Phase Ducts = 3 inch (min.)
Conductor Material = Copper
Number of Cables per Duct = 1
Number of Cables per Phase = 4
10
10
10
Rho Concrete = Rho Earth - 5
Rho PVC Duct = 650
44"
Rho Cable Insulation = 500
Rho Cable Jacket = 650
NOTES:
Neutral configuration per Section 300-5(i), Exception No. 2.
Maximum harmonic loading on the neutral conductor cannot exceed 50 percent of the phase current for
the ampacities shown in the table.
Metallic shields of Type MV-75 cable shall be grounded at one point only.
For SI units, one inch = 25.4 millimeters.
Size
Types
Size
RHW, THHW, THW, THWN,
XHHW, USE, OR MV-75
kcmil
Total Per Phase Ampere Rating
kcmil
RHO EARTH 60
RHO EARTH 90
RHO EARTH 120
LF 50
LF 100
LF 100
750
2520
1860
1680
750
(705A/Cable)
(465A/Cable)
(420A/Cable)
1000
3300
2140
1920
1000
(825A/Cable)
(535A/Cable)
(480A/Cable)
1250
3700
2380
2120
1250
(925A/Cable)
(595A/Cable)
(530A/Cable)
1500
4060
2580
2300
1500
(1015A/Cable)
(645A/Cable)
(575A/Cable)
1750
4360
2740
2460
1750
(1090A/Cable)
(685A/Cable)
(615A/Cable)
Ambient
For ambient temperatures other than 20°C (68°F), multiply the ampacities shown
Temp. °C
Ambient
above by the appropriate factor shown below.
Temp. °F
6-10
1.09
1.09
1.09
1.09
1.09
43-50
11-15
1.04
1.04
1.04
1.04
1.04
52-59
16-20
1.00
1.00
1.00
1.00
1.00
61-68
21-25
.95
.95
.95
.95
.95
70-77
26-30
.90
.90
.90
.90
.90
79-86
APPENDIX B
70-871
Figure B-310-5. Ampacities of Single Insulated Conductors
Rated 0 through 5000 Volts in Nonmagnetic Underground
Electrical Ducts (One Conductor per Electrical Duct)
Five Single-Conductor Cables per Phase
Based on Ambient Earth Temperature of 20°C (68°F),
Conductor Temperature 75°C (167°F)
Surface
6"
N &
6"
A
24"
Design Criteria
EGC
Neutral and Electrical Grounding
AO
Conductor (EGC) Duct = 6 inch
10
38"
Phase Ducts = 3 inch (min.)
Conductor Material = Copper
BO
Number of Cables per Duct = 1
10
Number of Cables per Phase = 5
CO
Rho Concrete = Rho Earth - 5
Rho PVC Duct = 650
Rho Cable Insulation = 500
10
10
10
10
Rho Cable Jacket = 650
54"
NOTES:
Neutral configuration per Section 300-5(i), Exception No. 2.
Maximum harmonic loading on the neutral conductor cannot exceed 50 percent of the
phase current for the ampacities shown in the table.
Metallic shields of Type MV-75 cable shall be grounded at one point only.
For SI units: one inch = 25.4 millimeters.
Size
Types
Size
RHW, THHW, THW, THWN,
XHHW, USE, OR MV-75
kcmil
Total Per Phase Ampere Rating
kcmil
RHO EARTH 60
RHO EARTH 90
RHO EARTH 120
LF 50
LF 100
LF 100
2000
5575
3375
3000
2000
(1115A/Cable)
(675A/Cable)
(600A/Cable)
For ambient temperatures other than 20°C (68°F), multiply the
Ambient
Ambient
Temp. °C
ampacities shown above by the appropriate factor shown below.
Temp. °F
6-10
1.09
1.09
1.09
1.09
1.09
43-50
11-15
1.04
1.04
1.04
1.04
1.04
52-59
16-20
1.00
1.00
1.00
1.00
1.00
61-68
21-25
.95
.95
.95
.95
.95
70-77
26-30
.90
.90
.90
.90
.90
79-86
70-872
NATIONAL ELECTRICAL CODE
Table B-310-11. Adjustment Factors for More than Three Current-Carrying
Conductors in a Raceway or Cable with Load Diversity
Percent of Values in
Number of
Tables as Adjusted for
Current-Carrying
Ambient Temperature
Conductors
if Necessary
4 through 6
80
7 through 9
70
10 through 24*
70
25 through 42*
60
43 and above*
50
*These factors include the effects of a load diversity of 50 percent.
(FPN): This table is based on the following formula:
A₂ = V0.5 N X (A₁) where
E
A1 = Table ampacity multiplied by factor from Article 310, Notes to Ampacity Tables of
0 to 2000 Volts, Note 8(a).
N = Total number of conductors used to obtain factor from Article 310, Notes to Ampacity Tables of 0 to 2000 Volts, Note 8(a).
E = Desired number of energized conductors
A₂ = Ampacity limit for energized conductors
70-873
Index
©1992 National Fire Protection Association, All Rights Reserved.
The copyright in this index is separate and distinct from the copyright
in the document that it indexes. The licensing provisions set forth for
the document are not applicable to this index. This index may not be
reproduced in whole or in part by any means without the express written permission of the National Fire Protection Association, Inc.
AC and DC conductors in same enclo-
Aerial cables, Art. 342; see also Nonmesure, 300-3(c)(1), 725-15
tallic extensions
AC armored cable, see Armored cable,
Identification, 200-6(a)
Type AC
Installation, 342-7(b), 820-53(d)
Messenger supported wiring, Art. 321
AC resistance and reactance conversion, Chap. 9, Table 9
Agricultural buildings, Art. 547
Grounding, bonding, and equipotential
AC systems
Conductor to be grounded, 250-25
plane, 547-8
Lighting fixtures, 547-7
Grounding connections, 250-23(a)
Motors, 547-6
Grounding electrode conductor, 250-94
Surface temperatures, 547-3
Grounding of, 250-5, 250-26
Switches, circuit breakers, controllers
In same metallic enclosures, 215-4(b),
and fuses, 547-5
300-20
Wiring methods, 547-4
Access and working space, electric
Air conditioners, room, 440-G
equipment; see also Working
Branch-circuit requirements, 440-62
space
Elevator machine room, 620-72
Definition, 440-60
Not over 600 volts, 110-16
Disconnecting means, 440-63
Over 600 volts, 110-B
Grounding, 440-61
Substations, motion picture and TV
Nameplate marking, 440-4
studio, 530-64
Air conditioning and refrigerating
Switchboards, 384-8
equipment, Art. 440
Transformers, electric signs, 600-32(f)
Branch circuit
Accessible
Conductors, 440-D
Definition, Art. 100-A
Ampacity, determination of, 440-6
Readily
Combination loads for, 440-34
Amplifiers and rectifiers, 640-11(b)
General, 440-31
Conduit bodies, junction, pull, and out-
Multimotor equipment for, 440-35
let boxes, 370-19
Several motor-compressors for,
Definition, Art. 100-A
440-33
Grounding electrode connection,
Single motor-compressor for, 440-32
250-112
Equipment for, 440-22(b)
Sealing fittings, 501-5(c), 502-5; see also
General, 440-21
Hazardous (classified) locations
Individual motor-compressor for,
Splices and taps in auxiliary gutters,
440-22(a)
374-8(a)
Outlets, 210-63
Splices and taps in wireways, 362-7
Ratings, 440-C
Transformers and vaults, 450-13
Selection current
Transformers, signs, outlet lighting,
Definition, 440-4(c) (FPN)
600-32(e)
Marking on nameplate, 440-4(c)
Unfinished attics and roof spaces,
Controllers for, 440-41
knob-and-tube wiring, 324-11(a)
Marking, 440-5
AC-DC general-use snap switches
Definitions, 440-2
Marking, 380-15
Disconnecting means, 440-B
Motors, 430-83 Ex. 1
Cord-connected as, 440-13
Panelboards, use in, 384-16(b)
Ratings and interrupting capacity,
Ratings, type loads, 380-14
440-12
70-874
NATIONAL ELECTRICAL CODE
Hermetic refrigerant motor-compressor,
Antenna discharge units, 810-20
440-2
Nameplate requirements, 440-4
Antenna systems, radio and television,
Overload protection, 440-F
see Community antenna television
Application and selection of, 440-52
and radio distribution systems;
Branch-circuit conductors for, 440-52(b)
Radio and television equipment
General, 440-51
Apparatus
Motor-compressors for, 440-52
Associated, 504-50(a)
On general-purpose circuits, 440-54
Definition, 504-2
Rated-load current
Intrinsically safe, 504-50(a)
Definition, 440-4(a) (FPN)
Definition, 504-2
Marking on nameplate, 440-4(a)
Room air conditioners, see Air
Appliances, Art. 422; see also Motors
conditioners, room
Battery-powered, 517-64(e)
Single machine, when considered, 440-8
Branch circuits, see Branch circuits,
Air plenums, see Plenums
appliances
Branch circuits for (utilization equip-
Aircraft hangars, Art. 513
ment), 210-23
Aircraft batteries, 513-9
Branch-circuit calculations, 220-3
Aircraft electrical systems, 513-8
Control and protection, 422-D
Aircraft energizers, 513-10
Cords, see Cords, flexible
Definition, 513-1
Definition, Art. 100-A
Equipment, 513-3, 513-5, 513-11
Grounding, 513-12
Disconnecting means, 422-D
Locations, classification of, 513-2
Dwelling units, outlets, 210-52(b)
Sealing, 513-7
Feeder calculations for, 220-10
Fixed
Stanchions, rostrums, and docks, 513-6
Wiring, 513-3, 513-4
Definition, 550-2, 551-2
Grounding, 250-E, 550-11, 551-24
Airport runways, underground alarm,
Hazardous (classified) locations, see
signal, conductors, Table 710-3(b)
Ex. 5
Hazardous (classified) locations
Household cooking, demand loads for,
Alarm systems, health care facilities,
Table 220-19
517-32(c), 517-42(c)
Installation, 422-C
Alarms
Load calculations, 220-3, 220-10, Table
Burgler, see Remote-control, signaling,
220-19
and power-limited circuits
Marking, 422-E
Fire, 230-82 Ex. 5, 230-94 Ex. 4; see also
Mobile homes, in, 550-7 (b) and (c),
Fire protective signaling systems
550-9
Alternators, see Generators
Motor-operated, load, 210-22
Overcurrent protection, 422-27
Aluminum conduit
Single, 210-20, 422-27(e)
In concrete and earth, 300-6(b); see also
Portable
Rigid metal conduit
Definition, 550-2, 551-2
Aluminum siding, grounding of,
Recreational vehicles, in, 551-42
250-44(e)(FPN)
Signal transmission between, 517-82
Ambient temperature, 310-10; see also
Stationary
Temperatures, limitations
Definition, 550-2, 551-2
Ampacities
Subject to immersion, 422-24
Conductors, 310-15, Tables 310-16 thru
Terminals, identification, 200-10(e)
310-19, B-310-1 thru 310-10, 310-61
Approval, approved
thru 310-84, 374-6
Definition, Art. 100-A
Crane and hoist conductors,
Equipment and materials, 90-4, 90-6,
Table 610-14(a)
110-2, 500-2, 500-3
Definition, Art. 100-A
Fixture wires, Table 402-3
Arc lamps
Flexible cords and cables, Table 400-5
General, 410-55
Portable
Grounding, 250-95
Tables, 0-2000 volts, 310-16 thru 310-27,
Motion picture studios, 530-17
App. B
Stage equipment, 520-61
Anesthetics, flammable, 517-D; see also
Arc welders, see Electric welders
Hazardous (classified) locations
Arcing parts, 240-41
Definition, 517-3
Enclosure of, 110-18, 430-14(b), 511-7(a),
Anesthetizing locations, 517-D; see also
513-5(a), 514-4, 515-4, 516-7(b) 517-
Health care facilities
61(b)(2)
Definition, 517-3
Arc-welder motors, 630-C
INDEX
70-875
Ampacities of conductors, Table 430-
Auxiliary gutters, Art. 374
22(a) Ex.
Ampacities, bare and insulated conduc-
Nameplate marking, 630-24
tors, 374-6
Arenas, Art. 518, Art. 520
Clearance, bare live parts, 374-7
Emergency lighting system, Art. 700
Conductors, installation, 620-35
Construction, installation, 374-9
Armored cable, Type AC, Art. 333
Covers, 374-4
Accessible attics, 333-12
Extension beyond equipment, 374-2
Bends, 333-8
Number of conductors, 374-5
Boxes and fittings, 333-9
Sound recording, similar equipment,
Conductor type, 333-20
640-4
Construction, 333-C
Splices, taps, 374-8
Definition, 333-1
Supports, 374-3
Exposed work, 333-11
Use, 374-1
Marking, 333-22
Back fed devices, 384-16(f)
Supports, 333-7
Backfill, 300-5(f), 339-3(a)(3), 710-3(b)(3)
Through studs, joists, rafters, or parallel
Ballasts, electric discharge lamps, 410-P
to framing members, 333-10
Protection in fluorescent fixtures,
Use, 333-3, 333-4
410-73(e)
Armories, Art. 518
Protection in recessed HID fixtures;
Emergency lighting system; Art. 700
410-73(f)
Array, solar photovoltaic systems
Bare conductors
Definition, 690-2
Ampacities, Art. 310 Note 5 of Notes to
Arresters, surge, see Lightning (surge)
Ampacity Tables 0-2000 volts
Contact conductors, cranes and hoists,
arresters
610-C
Askarels
Definition, Art. 100-A
Definition, Art. 100-A
Service entrance, Type SE, USE,
Transformers, 450-25
338-1(c)
Assembly, places of, Art. 518
Sizing conduits for, Chap. 9, Note 4 to
Table 1
Classifications, 518-2
Underground conduits, grounded neutral,
Emergency lighting system, Art. 700
230-30 Ex., 230-41 Ex.
Theaters, audience areas, Art. 520
Wiring methods, 518-4
Barriers, 384-3(a)
Atmospheric groups, see Hazardous
Basements (cellars)
(classified) locations
Armored cable, 333-11 Ex. 2
Attachment plugs (caps), see also Haz-
Nonmetallic extensions, 342-4(b)
ardous (classified) locations
Nonmetallic sheathed cable, 336-12
Construction of, 410-56(f)
Receptacles in, 210-8(a)(4), 210-52(g),
410-57
Definition, Art. 100-A
Unfinished, 210-8(4)
Flexible cords on, 400-7(b), 400-24
Grounding type, 410-58
Bathroom
Polarized
Definition, 210-8
Terminal identification, 200-10
Receptacles in, 210-8(a), 210-8(b)
Attics
Bathtubs, hydromassage, 680-G
Armored cable, 333-12
Definition, 680-4
Knob and tube, 324-11
Batteries
Nonmetallic-sheathed cable, 336-13
Aircraft, 513-9
Open wiring, 320-15
Installations, Art. 480, 551-10(d), 690-71
Sign transformers in, 600-32(g)
Nominal voltage
Audio equipment, underwater, 680-41(i)
Definition, 480-2
Sealed
Auditoriums, Art. 518, Art. 520
Definition, 480-2
Emergency lighting system, Art. 700
Storage, see Storage batteries
Authority having jurisdiction, 90-4; see
Battery charging equipment, 511-8
also Approval
Aircraft hangars, 513-9
Automatic
Bell circuits, see Remote-control, signal-
Definition, Art. 100-A
ing, and power-limited circuits
Autotransformers
Bends, 300-34, 334-11; see also wiring system involved
Ballast for lighting units, 410-78
Branch circuits, 210-9
Block (city, town, or village),
Motor starting, 430-82(b)
800-30(a)(FPN No. 1)
70-876
NATIONAL ELECTRICAL CODE
Blocking diode, solar photovoltaic
Vertical raceway runs, 300-19
systems
Wall or ceiling, 370-20
Definition, 690-2
Wet locations, 370-15
Boatyards, see Marinas and boatyards
Branch circuits, Art. 210, Art. 220
Bodies, conduit, see Conduit bodies
Air conditioners, 440-D, 440-G
Boilers
Appliances, 422-B and C
Electrode-type, 424-H
Definition, Art. 100-A
Resistance-type, 424-G
Busways as branch circuits, 364-12 thru
364-14
Bonding, 250-G
Calculation of loads, 220-3, Chap. 9 Part B
Definition, Art. 100-A
Car lighting, 620-22
Grounding-type receptacles, 250-74
Color code, 210-5
Hazardous (classified) locations, see
Conductors, minimum ampacity and size,
Hazardous (classified) locations
210-19
Intrinsically safe systems, 504-60
Critical
Loosely jointed raceways, 250-77
Definition, 517-3
Other enclosures, 250-75
Definition, Art. 100-A
Outside raceway, 250-79(f)
Fixed electric space heating equipment,
Over 250 volts, 250-76
424-3
Piping systems, 250-80
General, 210-A
Receptacles, 250-74
General purpose
Service equipment, 250-71, 250-72
Definition, Art. 100-A
Swimming pools, 680-22
Health care facilities, 517-18(a)
Bonding jumpers, see Jumpers, bonding
Individual
Definition, Art. 100-A
Bored holes through studs, joists,
Overcurrent protection, 210-20
300-4(a)(1), 545-4(b)
Permissible loads, 210-23
Bowling alleys, Art. 518
Required, 520-53(g), 600-6(b), 605-8(b),
Emergency lighting system, Art. 700
620-22, 710-72
Boxes (outlet, device, pull, and junc-
Infrared lamps, 422-15
tion), Art. 370; see also Hazardous
Isolated power systems, 517-160(c)
(classified) locations
Maximum loads, 210-22
Accessibility, 370-29
Mobile homes, 550-7
Concealed work, 370-24
Motor, on individual branch circuit,
Conductors, number in box, 370-16
430-B
Entering boxes, conduit bodies or fit-
Multiwire, 210-4, 501-18, 502-18
tings, 370-17
Definition, Art. 100-A
Construction specifications, 370-C
Outside, Art. 225
Covers, 370-25, 370-28(c), 370-41
Overcurrent protection, 210-20, 240-3
Cutout, see Cabinets and cutout boxes
Patient bed location, 517-19(a)
Damp locations, 370-15
Permissible loads, 210-23
Depth, 370-24
Ratings, 210-B
Exposed surface extensions, 370-22
Recreational vehicles, 551-42
Floor, for receptacles, 370-27(b)
Requirements for, Table 210-24
Grounding, 250-E, 250-114, 300-9
Selection current, 440-4(c)
Definition, 440-2
Insulating, see Boxes, nonmetallic
Junction, pull, see Junction boxes
Small appliance, 220-4(b)
Stage or set, 530-22
Lighting outlets, 370-27(a), 410-C, 410-16
Metal
Taps from, 210-19(c), 210-24, 240-3
Ex. 5, 240-4 Ex. 1 and 2
Construction, 370-40
Through fixtures, 410-11, 410-31
Grounding, 370-14
Two or more outlets on, 210-23
Installation, 370-B
Voltage drop, 210-19(a) FPN
Nonmetallic, 324-13, 336-17, 370-13,
Voltage limitations, 210-6
370-17(c), 370-43
X-ray equipment, 517-E, 660-4, 660-6(b)
Over 600 volts, 370-D
Portable, in theaters, 520-62
Branch-circuit selection current
Remote control, signal circuits,
Definition, 440-2
725-11(b), 725-38(a)(2)
Building component
Repairing plaster around, 370-11
Definition, 545-3
Required location, 300-15
Round, 370-12
Building system
Definition, 545-3
Secured supports, 300-11, 370-23
Snap switches over 300 volts, not
Building wire, see Conductors
ganged, 380-8(b)
Buildings
Unused openings, closed, 110-12(a),
Definition, Art. 100-A
370-18
First floor of, 336-4(a)
INDEX
70-877
Bulk storage plants, Art. 515
Cable suspension, 300-19
Class I locations, 515-2
Cable trays, Art. 318
Definition, 515-1
Ampacity, 318-11, 318-13
Gasoline dispensing, 515-7
Cable fill, 318-9, 318-10, 318-12
Grounding, 515-8
Cable installation, 318-8
Sealing, 515-6
Construction specifications, 318-5
Underground wiring, 515-5
Definition, 318-2
Wiring and equipment, 515-3, 515-4
Grounding, 318-7
Burglar alarm systems, see Remote-
Installation, 318-6
control signaling and power-limited
Separation, 318-6(f) Ex. 1
circuits
Uses not permitted, 318-4
Buried grounding conductor connection,
Uses permitted, 318-3
250-112 Ex.
Cablebus, Art. 365
Busbars, auxiliary gutters, 374-6, 710-3(c)
Conductors, 365-3
Bushings
Overcurrent protection, 365-5
Fiber, see Fiber bushings
Terminations, 365-8
Generators, 445-8
Definition, 365-1
Insulated, 373-6(c)
Fittings, 365-7
Insulating, lampholders attached to
Grounding, 365-9
flexible cord, 410-30
Marking, 365-10
Intermediate metal conduit, 345-15
Support, 365-6
Motors, 430-13
Conductor, 365-3(d)
Outlet boxes, conduit bodies, and outlet
Use, 365-2
fittings, 370-22
Cables
Rigid metal conduit, 346-8
Rigid nonmetallic conduit, 347-12
Aerial entrance, 820-53(d)
Snow-melting and deicing equipment,
Armored, Type AC, see Armored cable
426-22(c)
Border lights, theater, 520-44(b)
Underground installations, 300-5(h)
Continuity, 300-12
Use in lieu of box or terminal fitting,
Definition, 800-2
300-16(b)
Flat cable assemblies, Type FC, see Flat
cable assemblies
Busways, Art. 364
Flat conductor, Type FCC, see Flat con-
Branch circuits, 364-12
ductor cable
Branches from, 364-8
Dead ends closed, 364-7
Heating, see Heating cables
Integrated gas spacer, Type IGS, see
Definition, 364-2
Extension through walls and floors, 364-6
Integrated gas spacer cable
Medium voltage, Type MV, see Medium
Length, as branch circuits, 364-14
Marking, 364-15
voltage cable
Over 600 volts, 364-B
Metal-clad, Type MC, see Metal-clad
cable
Overcurrent protection, 364-9, 364-10,
364-13
Mineral-insulated metal-sheathed, Type
Reduction in size, 364-11
MI, see Mineral-insulated metalsheathed cable
Support, 364-5
Under 600 volts, 364-30
Nonmetallic-sheathed, Types NM and
Use, 364-4
NMC, see Nonmetallic-sheathed
cable
Bypass isolation switch
Nonmetallic extension, see Nonmetallic
Definition, Art. 100-A
extensions
Cabinets, cutout boxes, and meter
Optical fiber, see Optical fiber cables
socket enclosures, Art. 373
Other types of, see names of systems
Construction specifications, 373-B
Point of entrance
Damp or wet locations, 373-2
Definition, 800-2, 820-4
Definitions, Art. 100-A
Power and control tray cable, Type TC,
Deflection of conductors, 373-6
see Power and control tray cable
In walls, 373-3
Power limited tray cable, type PLTC,
Insulation at bushings, 373-6(c)
725-51(e)
Switch enclosures, splices, taps, 373-8
Preassembled in nonmetallic conduit, see
Unused openings, 373-4
Preassembled cable in nonmetallic
Wire bending space, 373-6(b)
conduit
Wiring space, 373-9
Protection against physical damage,
Cable bending, see type of cable
300-4
Cable end fittings, changing from cable
Remote-control signaling and power limto knob-and-tube, 300-16(a)
ited circuits, 725-51
Cable sheath
Secured, 300-11, 370-7(b) and (c)
Definition, 800-2
Service, see Service cable
70-878
NATIONAL ELECTRICAL CODE
Service-entrance, Types SE and USE,
Discontinued outlets, 358-13
see Service-entrance cable
Header ducts, 358-5
Shielded nonmetallic, Type SNM, see
Inserts, 358-9
Shielded nonmetallic cable
Junction boxes, 358-7
Splices in boxes, 300-15
Markers, 358-8
Stage, 530-18(a)
Number of conductors, 358-11
Through studs, joists, rafters, 300-4
Size of conductors, 358-10
Underground, 230-C, 300-5, 310-7,
Uses not permitted, 358-4
710-3(b)
Underground feeder and branch circuit
Cellular metal floor raceways, Art. 356
Type UF, see Underground feeder
Connection to cabinets and extension
and branch circuit cable
from cells, 356-11
Construction, 356-12
Calculations, Chap. 9, Part B; see also
Loads
Definitions, 356-1
Discontinued outlets, 356-7
Camping trailer
Inserts, 356-10
Definition, 551-2
Junction boxes, 356-9
Canopies
Markers, 356-8
Boxes and fittings, 370-15
Number of conductors, 356-5
Lighting fixtures
Size of conductors, 356-4
Conductors, space for, 410-10
Uses not permitted, 356-2
Cover
At boxes, 410-12
Chair lifts, see Elevators, dumbwaiters,
Combustible finishes, covering
escalators, moving walks, wheelrequired between canopy and box,
chair lifts, and stairway chair lifts
410-13
Churches, Art. 518
Live parts exposed, 410-3
Cinder fill
Capacitors, Art. 460; see also Hazardous
Intermediate or rigid metal conduits and
(classified) locations
electrical metallic tubing, in or
Conductors, 460-8
under, 345-3(c), 346-3, 348-1
Connections at services, 230-82
Rigid nonmetallic conduit, 347-2
Discharge of stored energy, 460-6
Draining charge, 460-6
Circuit breakers, Art. 240; see also Haz-
Induction and dielectric heating, 665-24
ardous (classified) locations
Over 600 volts, 460-B
Accessibility and grouping, 380-8
X-ray equipment, 660-36
Circuits over 600 volts, 710-21
Definition, Art. 100-A
Capacity, interrupting, see Interrupting
Disconnection of grounded circuits,
capacity
380-2(b), 514-5
Caps, see Attachment plugs
Enclosures, 380-3
Cartridge fuses, 240-F
General, 110-9, 240-A
Disconnection, 240-40
Overcurrent protection, 230-208, 240-A
CATV systems, see Community antenna
Generators, 445-4
television and radio distribution
Motors, 430-52, 430-58, 430-110
systems
Transformers, 450-3
Ceiling fans, 680-6, 680-41(b)
Panelboards, 384-B
Support of, 370-27(c), 422-18
Rating, motor branch circuits, 430-58
Cell
Rating, nonadjustable trip, 240-3 Ex. 4,
240-83(c)
Cellular concrete floor raceways
Definition, 358-2
Service overcurrent protection, 230-90,
230-91
Electrolytic
Definition, 688-2
Services, disconnecting means, 230-70,
230-208
Sealed, storage batteries
Definition, 480-2
Switches, use as, 240-83(d), 380-11,
Solar
410-81(b)
Definition, 690-2
Wet locations, in, 380-4
Cell line, electrolytic cells
Circuit directory, panelboards, 110-22
Attachments and auxiliary equipment
Circuit-interrupters, ground-fault, see
Definition, 668-2
Ground-fault circuit-interrupters
Definition, 668-2
Circuits
Cellars, see Basements
Anesthetizing locations, 517-63
Cellular concrete floor raceways,
Bonding jumper
Art. 358
Definition, Art. 100-A
Connection to cabinets and other enclo-
Branch, see Branch circuits
sures, 358-6
Burglar alarm, see Remote-control sig-
Definitions, 358-2
naling and power limited circuits
INDEX
70-879
Central station, see Fire protective sig-
Closed-loop and programmed power
naling systems
distribution,A 780
Communication, see Communication
Cables and conductors, 780-6
circuits
Control, 780-3
Electronic computer/data processing
Hybrid cable, 780-6(a)
equipment, 645-5
In same cabinet, panel, or box,
Fire alarm, see Fire protective signaling
780-6(b)
systems
Noninterchangeability, 780-7
Grounding, Art. 250
Power limitation, in signaling circuits,
Impedance, 110-10
780-5
Intrinsically safe, 504-30
Clothes closets
Definition, 504-4
Heating, 424-38(c)
Less than 50 volts, Art. 720
Light fixtures, 410-8
Class 1, 720-B
Overcurrent devices, 240-24(d)
Grounding, 250-5(a)
Clothes dryers
More than 600 volts, see Over 600 volts
Calculations for, 220-18
Services, 230-H
Feeder demand factors, Table 220-18
Motor, 430-B
Grounding, 250-60
Motor control, 430-F
Mobile homes, 550-10(e)
Definition, 430-71
Clothing manufacturing plants, 500-7,
Nonincendive
Art. 503; see also Hazardous (clas-
Definition, Art. 100-A
sified) locations
Number of, in enclosures, 90-7(b)
CO/ALR
Power-limited, see Remote control, sig-
Receptacles, 410-56(b)
naling and power-limited circuits
Switches, 380-14(c)
Protectors required, 800-12, 800-31,
Collector rings, 675-11, 710-44
800-32
Definition, 675-2
Remote-control, Art. 725
Definition, Art. 100-A
Collectors, cranes and hoists, 610-22
Motors, controllers, 430-F
Color code
Signal, see Remote-control, signaling,
Branch circuits, 210-5
and power-limited circuits
Conductors, 310-12
Telegraph, see Communications circuits
Grounding conductor, 210-5, 250-57(b),
Telephone, see Communications circuits
310-12(b), 400-23
Underground, see Communications
Heating cables, 424-35
circuits
Higher voltage to ground
Ungrounded, 210-10, 215-7, 410-48
Feeders, 215-8
Panel boards, 384-3(e)
Clamps, ground, 250-113, 250-115,
Service-entrance conductors, 230-56
250-117
Combustible dusts, Art. 502; see also
Class 1, 2, and 3 circuits, see Remote-
Hazardous (classified) locations
control, signaling, and power-
Common grounding electrode, see Eleclimited circuits
trode, grounding, common
Class I, II, and III locations, see Hazard-
Common neutral
ous (classified) locations
Feeders, 215-4
Clean surfaces, grounding conductor
Outside wiring, 225-7(b)
connections, 250-118
Communication circuits, Art. 800
Clearances, see also Enclosures; Space
Access to electrical equipment, 800-5
Antennas, 810-3, 810-18, 810-54
Bonding, 800-40(d), 800-41(b)
Community antenna systems, Art. 820
Cable marking, 800-50
Conductors
Cable substitution, 800-53(e)
Open, outside branch circuits and feed-
Circuits requiring primary protectors,
800-12
ers, 225-18, 225-19
Conductors
Service drop, 230-B
Elevators, dumbwaiters, escalators, mov-
Other circuits with, 800-52, 800-53(c)
ing walks, 620-72
Outside and entering buildings, 800-E
Lighting fixtures, 410-66, 410-76(b)
Overhead, 800-10
Definition, 800-2
Live parts
Essential electrical systems, 517-32(d),
Auxiliary gutters, 374-7
Circuits over 600 volts, 110-B
517-42(d)
Fire resistance, 800-49
Swimming pools, 680-8
Grounding, 800-33, 800-D
Switchboards, panelboards, 384-7, 384-8,
Health care facilities, 517-32(d), 517-F
384-10
Hybrid power and communications
Climbing space, line conductors on
cables, 800-3
poles, 225-14(d)
Installation, 800-50, 800-52
70-880
NATIONAL ELECTRICAL CODE
Lightning conductors, 800-13
Flexible metal conduit, Table 350-3
Listing of communication wires and
Flexible metallic tubing, 349-12
cables, 800-4, 800-50, 800-51,
General installations, 300-17
800-53
Intermediate metal conduit, 345-7
Marking, 800-50
Liquidtight flexible metal conduit, 351-6
Mobile homes, 800-41
Liquidtight flexible nonmetallic conduit,
Protection, 800-C
351-25
Devices, 800-30
Maximum permitted, 300-17
Grounding, 800-40, 800-41
Outlet boxes, etc., 370-6
Requirements, 800-31, 800-32, 800-40,
Remote control circuits, 725-17
800-41
Rigid metal conduit, 346-6
Types of cable, 800-51
Rigid nonmetallic conduit, 347-11
Underground circuits entering buildings,
Signs, 600-21(d)
800-11
Sound recording equipment, 640-3, 640-4
Community antenna television and radio
Surface raceways, 352-4, 352-25
distribution systems, Art. 820
Theaters, 520-5
Access to electrical equipment, 820-4
Underfloor raceways, 354-5
Cables
Wireways, 362-5, 362-7
Aerial entrance, 820-53(d)
X-ray equipment, 660-8
Definitions, 820-3
Conductors, see also Cords, flexible; Fix-
Entering buildings, 820-11
ture wires
Fire resistance of, 820-49
Aluminum, conductor material, 310-14
Listing and marking, 820-50, 820-51,
Aluminum, properties of, Chap. 9,
820-53
Table 8
Outside, 820-10
Motors, 430-B
Types of, 820-51
Ampacities of, 310-15, Tables 310-16 thru
Underground, 820-11
310-19, B-310-1 thru B-310-10,
Within buildings, 820-E
310-69 thru 310-83
Energy limitations, 820-2
Amplifier circuits, 640-5
Grounding, 820-D
Application, 310-12, 310-13
Cables, 820-33, 820-D
Armored cable, Type AC, see Armored
Equipment, 820-41
cable
Installation of cables and equipment,
Bare, see Bare conductors
820-52
Boxes and fittings, junction, 370-16,
Mobile homes, 820-42
370-17
Protection, 820-C, 820-40(5)
Branch circuits, Art. 210
Buried, 310-7
Compressors, refrigeration, Art. 440
Busways, see Busways
Computer rooms, see Electronic
Cabinets and cutout boxes, 373-5 thru
computer/data processing
373-7
equipment
Cablebus, see Cablebus
Concealed
Capacitors, 460-8
Definition, Art. 100-A
Cellular concrete floor raceways, see
Knob-and-tube wiring, see Knob-and-
Cellular concrete floor raceways
tube wiring
Cellular metal floor raceways, see Cellu-
Concentric knockouts, see Knockouts,
lar metal floor raceways
Circuit
bonding service equipment
Communication, Art. 800
Concrete
Control, 517-74
Electrodes encased in, 250-81(c)
Fire protective signaling, Art. 760
Metal raceways and equipment in, 300-6
Less than 50 volts, Art. 720
Conductive surfaces, exposed
Over 600 volts, Art. 710
Definition, 517-2
Signal, remote-control, power-limited,
Art. 725
Conductor fill
Combinations, Chap. 9, Table 1
Auxiliary gutters, 374-5, 374-8(a)
Communications circuits, 800-B, 800-E
Cable trays, 318-8, 318-9
Cellular concrete floor raceways, 358-11
Computations of, examples, Chap. 9,
Part B
Cellular metal floor raceways, 356-5
Concealed knob-and-tube, see Knob and
Control circuits, 517-74(a)
tube wiring
Electrical metallic tubing, 348-6
Conduit or tubing, number in, 331-6,
Electrical nonmetallic tubing, 331-6
345-7, 346-6, 347-11, 348-6, 349-12,
Elevators, 620-32, 620-33
Table 350-3, 351-6, 351-25, Chap. 9
Entering boxes, conduit bodies, or fit-
Tables 3A thru 3C, Table 5B
tings, 370-7
Construction, general, Table 310-13
Fixture wire, 402-7
Cooling of electric equipment, 110-13(b)
INDEX
70-881
Copper, 760-16
Fixtures, flush, recessed, 410-67
Ampacities, Tables 310-16 thru 310-19,
Hazardous (classified) locations, Class
B-310-1 thru B-310-10
I, 501-13
Properties, Chap. 9, Table 8
Motion picture projectors, 540-14
Copper-clad aluminum
Theaters, 520-42
Definition, Art. 100-A
Insulation at bushings, No. 4 and larger,
Cords, flexible, see Cords, flexible
373-6(c)
Corrosive conditions, 300-6, 310-9,
Intrinsically safe, 504-30, 504-50
501-13
Length in boxes, 300-14
Covered
Lighting fixtures, 410-E
Definition, Art. 100-A
Lightning rods, spacing from, 250-46,
Crane and hoists, 610-B, 610-C, 610-31,
800-13, 820-10(e)(3)
610-41
Liquidtight flexible metallic conduit, see
Definitions, Art. 100-A
Liquidtight flexible metallic conduit
Deflection of, see Deflection of conductors
Liquidtight flexible nonmetallic conduit,
Different systems, 300-3, 725-15,
see Liquidtight flexible nonmetallic
725-38(a)(2)
conduit
Dimensions of, Chap. 9, Tables 5 thru 6
Metal-clad cable, see Metal-clad cable
Electrical metallic tubing, see Electrical
Metal enclosures, spacing from lighting
metallic tubing
rods, 250-46
Electrical nonmetallic tubing, see Electri-
Mineral-insulated metal-sheathed cable,
cal nonmetallic tubing
see Mineral-insulated metal-
Elevators, dumbwaiters, escalators, movsheathed cable
ing walks, 620-B thru 620-D
Minimum size, 310-5, 517-74(b)
Enclosure, grounding, 250-1, 250-D
Motion picture projectors, sizes, 540-13
Equipment grounding, see Equipment
Motor circuits, 430-B
grounding conductors
Multioutlet assembly, see Multioutlet
Feeder, Art. 215
assembly
Fire protective signaling systems, 760-15,
Multiple, 250-79(d), 250-95, 300-20,
760-16, 760-50, 760-52
310-4, 520-27(b), 620-12(a)(1) Ex.
Fixture wires, Art. 402
Nonmetallic extensions, see Nonmetallic
Gauges (AWG), general provisions, 110-6
extensions
Generators, size, 445-5
Nonmetallic sheathed cable, Types NM
Grounded, 250-23, 250-25
and NMC, see Nonmetallic-
Alternating current systems, 250-23,
sheathed cable
250-25
Number of, in, see Conductor fill
Identification, 200-2, 210-5, 215-8
Organs, 650-4, 650-5
Change in size, 240-23
Outlet boxes, temperature limits, 410-11
Definition, Art. 100-A
Outside wiring, Art. 225
Different systems, 200-6(d)
Over 600 volts, Art. 710
Fuses in, 430-36
Overcurrent protection, 240-3, 240-4
Multiconductor cables, identification,
Overhead, 800-10
310-12(a) Ex. 4
Paralleled, 250-79(d), 250-95, 300-20,
Identification, 200-2, 210-5, 215-8,
310-4, 520-27(b), 620-12(a) (1) Ex.
310-12
Properties of, Chap. 9, Table 8
Overcurrent protection, 240-22
Raceways, number of conductors in, see
Services
Conductor fill
Disconnection of, 230-75
Radio and television
Overcurrent protection, 230-90(b)
Antenna distribution systems, 810-3,
Switches, disconnection, 380-2(b)
Art. 820
Use and identification, Art. 200
Antenna systems, Art. 810
Grounding, see Grounding conductor
Equipment, Art. 810
Grounding electrode, see Grounding
Railway, power and light from, 110-19
electrode conductor
Recreational vehicle site feeder circuit
Identification, 310-12
Definition, 551-2
In free air, Tables 310-17, 310-19,
Remote-control circuits, Art. 725
B-310-2
Rigid metal conduit, see Rigid metal con-
Induction and dielectric heating equipduit
ment, ampacity of supply, 665-41,
Selection of, examples, Chap. 9, Part B
665-61
Service, 230-10; see also Service cables;
Installation with other systems, 300-8
Service-entrance cable; and
Insulated
Service-entrance conductors
Definition, Art. 100-A
Definition, Art. 100-A
Insulating materials, 310-12, 310-13
Service-entrance, see Service-entrance
Insulation, Art. 310
conductors
Fire protective signaling systems, 760-
Shielded nonmetallic-sheathed cable, see
16(b)
Shielded nonmetallic-sheathed cable
70-882
NATIONAL ELECTRICAL CODE
Signal circuits, Art. 725, Art. 760
Rigid nonmetallic, see Rigid nonmetallic
Signs and outline lighting, 600-21, 600-31
conduit
Single, underground, 300-5(i)
Connections
Sizes, 110-6, Chap. 9, Tables 5 thru 6
Sound recording equipment, 640-3 thru
Aluminum, copper conductors, 110-14
640-9
Cellular metal floor raceways to cabinets
Stranded, 310-3
and extensions, 356-11
Support of, in vertical raceways, 300-19
Essential electrical systems, 517-34,
Surface raceway, see Surface raceway
517-42, 517-43, 517-50
Switchboards and panelboards, 384-3(a),
Feed-through, see Feed-through connec-
384-9
tions
Temperature, limitations of, 310-10,
Grounding conductor, 250-K
338-3(c)
High-impedance grounded neutral sys-
Theaters, portable stage equipment,
tem, 250-22
520-68
Integrity of, 110-12(c)
Underfloor raceway, see Underfloor
Multiple circuit, see Multiple circuit
connections
raceway
Underground feeder and branch-circuit
Point of interconnected power production
cable, see Underground feeder and
sources, 705-12
branch-circuit cable
Splices, 110-14(b)
Ungrounded
Switches, 380-2
Indentification, 210-4(d)
Temperature limitations, 110-14(c)
Services, 230-42(b), 230-90(a)
Terminals, general provisions, 110-14(a)
Welders, electric
X-ray installations, 517-71
Ampacity of supply, 630-11, 630-21,
Connectors
630-31
Armored cable, 333-9
Overcurrent protection, 630-12(b),
Boxes, 370-7
630-22(b), 630-32(b)
Cabinets and cutout boxes, 373-5(c)
Wet locations, 225-4, 310-8
Cable, theater, 520-67
Wireways, see Wireways
Electrical metallic tubing, 348-8, 348-14
X-ray equipment, 517-E, 660-6 thru 660-8
Intermediate metal conduit, 345-9
Conduit bodies
Pressure (solderless)
Definition, Art. 100-A
Definition, Art. 100-A
Number of conductors, 370-16(c)
Rigid metal conduit, 346-9
Pull and junction box, 370-28
Rigid nonmetallic conduit, 347-6
Conduit fill, see also Conductor fill
Constant-potential generators, Art. 445
Equipment grounding conductors, Chap.
Overcurrent protection for, 445-4(a)
9, Note 2 of Notes to the tables
Construction, closed
Grounding conductor, Art. 310 Note 11
Definition, 545-3
of Notes to Ampacity Tables 0-2000
Construction sites
volts
Assured equipment grounding conductor
Conduit nipples, Chap. 9, Note 3 of
program, 305-6(b)
Notes to the tables
Extension cord sets, 305-6(b)
Conduits
Ground-fault circuit-interrupter, protec-
Circuits, physical protection of remote
tion for, 305-6(a)
-
control, 725-18
Continuity
Conductors, number in, Chap. 9, Tables
Electrical, metal raceways and cables,
1 thru 3C, Table 5B
250-75, 250-76
Dimensions, Chap. 9, Table 4
Service equipment, 250-71, 250-72
Electrical metallic tubing, see Electrical
Grounding, metal boxes, grounding-type
metallic tubing
receptacles, 250-74, 250-114
Electrical nonmetallic tubing, see Electri-
Mechanical, raceways and cables, 300-12
cal nonmetallic tubing
Conductors, 300-13
Flexible metal, see Flexible metal
Neutral of multiwire circuits, 300-13(b)
conduit
Intermediate metal, see Intermediate
Continuous duty
metal conduit
Definition, Art. 100-A
Liquidtight flexible metal, see Liquidtight
Continuous industrial processes
flexible metal conduit
Coordination, electric system, 240-12
Liquidtight flexible nonmetallic, see
Ground-fault protection, 230-95(a) Ex. 1
Liquidtight flexible nonmetallic
Orderly shutdown, 430-44
conduit
Power loss hazard, 240-3 Ex. 3
Metallic, grounding runs 25 ft., 250-33
Continuous load
Number of conductors in, 402-7
Applications, 210-22(c), 220-3(a),
Outside wiring, 225-10
220-10(b), 384-16(c)
Rigid metal, see Rigid metal conduit
Definition, Art. 100-A
INDEX
70-883
Control, see also Hazardous (classified)
Power-limited and signal circuits,
locations
remote-control, 725-16
Remote
Pull at joints and terminals, 400-10
Induction and dielectric heating equip-
Repair of, hard service, 400-9
ment, 665-47
Sound recording and similar equipment,
Overcurrent protection, 240-3
grouping conductors, 640-7
Power-limited and signal circuits,
Splices and taps, 400-9, 530-12
Art. 725
Construction sites, 305-4(g)
X-ray equipment, 517-E, 660-B
Types, Table 400-4
Control centers
Heater, Tables 400-4, 422-8(a)
Guarding live parts, 110-17
Tinsel
Headroom, 110-16(f), 110-32
Minimum size, 400-12
Illumination at, 110-16(e), 110-34(d)
Overcurrent protection, 400-13
Motor, 430-H
Uses not permitted, 400-8
Working space, 110-16, 110-33, 110-34
Uses permitted, 400-7
Control circuit, 430-71
Correction factors, ambient temperature,
Control drawing, 504-10(a)
Tables 310-16 thru 310-19, B-310-1
Definition, 504-2
thru B-310-10
Control panels
Corrosion protection, see Protection,
Clearance around, elevators, 620-72
corrosion
Working space, 110-16
Corrosive conditions
Controllers, see also Hazardous (classi-
Bushing, 430-13
fied) locations
Conductor insulation, 310-9, 501-13
Cases, grounding, 250-43(d)
General, 110-11
Definition, Art. 100-A, 430-81(a)
Counter tops, outlets, 210-52
Enclosures, grounding, 250-43(d)
Motor, 430-G
Couplings
Hazardous (classified) locations, 501-6,
Electrical metallic tubing, 348-8
502-6, 503-4
Intermediate metal conduit, 345-9
Ratings, 430-83
Rigid metal conduit, 346-9
Resistors and reactors, see Resistors and
Rigid nonmetallic conduit, 347-9
reactors
Running threads at, 345-9(b), 346-9(b)
Convenience outlets, see Receptacles
Threaded and threadless, 250-72
Conversion table, AC conductor resis-
Cove lighting, space for, 410-9
tances and reactances, Chap. 9,
Covers
Table 9
Auxiliary gutters, 374-4
Converters
Boxes and fittings, 370-15
Phase, see Phase converters
Cable, 650-5(d)
Recreational vehicle
Electrically operated pool, 680-26
Definition, 551-2
Faceplates, see Faceplates
Cooking unit, counter-mounted, see also
Pool
Ranges and Ovens
Definition, 680-4
Branch circuits, 210-19
Electrically operated, 680-26
Definition, Art. 100-A
Wireways, 362-1
Cooling of equipment, 110-13(b)
Cranes, Art. 610
Coordination, electrical systems, 240-12
Conductors, 610-B, 610-C
Feeders, 240-100 (FPN), 517-17
Control, 610-F
Copper conductors, see Conductors, cop-
Electrolytic cells, 668-32
Flexible cords, 400-7
per
Grounding, 250-7(a), 250-43(e), 610-G
Copper-clad aluminum conductors, see
Hazardous (classified) locations, 503-13
Conductors, Copper-clad aluminum
Motors and controllers, disconnecting
Cord sets, see Extension cord sets
means, 430-112
Cords, see also Hazardous (classified)
Overcurrent protection, 610-E
locations
Critical care areas, 517-15(2), 517-19
Flexible, Art. 400, 422-8
Definition, 517-3
Ampacities, Table 400-5
Cross sectional areas
Identified conductors within, 200-6(c)
Lampholders, insulating bushings,
Conductors, Chap. 9, Tables 5 thru 8
410-30(a)
Conduits, Chap. 9, Table 4
Motion picture projectors, 540-15
Current-carrying capacities, see
Overcurrent protection, 240-4, 400-13
Ampacities
70-884
NATIONAL ELECTRICAL CODE
Current-limiting devices, see also Circuit
Diagnostic equipment, 517-73(a)
breakers; Fuses
Definition, 240-11
Diagrams
Curtain machines, theaters, 520-48
Autotransformer overcurrent protection,
Diagram 450-4
Cutout bases, see Fuseholders
Cable installation dimensions, under-
Cutout boxes, see also Cabinets, cutout
ground, Fig. 310-1
boxes, and meter socket enclosures
Feeders, 215-5
Definition, Art. 100-A
Health care facility electrical systems,
Cutouts
Diagrams 517-41 and 517-25, 517-30
Motor feeder and branch circuits, Dia-
Thermal, see Thermal cutouts
gram 430-1
Cutting tables, motion picture, 530-D
Service, Diagram 230-1
Damp or wet locations, 110-11; see also
Spray application, dipping, and coating,
Wet locations
Figs. 516-1 thru 4
Boxes and fittings, 370-5
Swimming pools, 680-8
Cabinets and cutout boxes, 373-2
Dielectric heat generating equipment,
Definition, Art. 100-A
see Induction and dielectric heating
Lampholders, 410-49
equipment
Lighting fixtures, 410-4(a)
Dielectric heating, see also Induction and
Open wiring, 320-13
Overcurrent protection, enclosure,
dielectric heating
Definition, 665-2
240-32
Panelboards, 384-17
Different systems, conductors in same
Receptacles, 410-57
enclosure, 210-5(a), 300-3(c),
318-6(e) and (f), 725-15,
Dampers (flue), control
725-38(a)(2), 760-15, 760-18,
Fixed stage equipment, 520-49
760-52(a), 760-52(b), 800-11(a),
Ventilating openings, transformer vaults,
810-18(c), 820-52(a)
450-45(e)
Dimensions
Dance halls, Art. 518
Conductors, Chap. 9, Tables 5 thru 8
Data processing systems, see Electronic
Conduits and tubing, Chap. 9, Table 4
computer/data processing equipment
Dimmers, stage switchboard, 520-25,
DC systems, grounding, 250-3, 250-22
520-53(e)
Dead ends
Dining areas, essential electrical sys-
Busways, 364-7
tems, 517-42(e)
Cablebus, 365-7
Dip tanks, Art. 516
Flat cable assemblies, 363-11
Wireways, 362-10
Direct burial
Liquidtight flexible metal conduit,
Dead front
351-4(a)
Definition, Art. 100-A, 551-2; see also
Over 600 volts, 710-3(b)
individual articles
Rigid nonmetallic conduit, 347-2(g),
Stage switchboards, 520-21
Tables 300-5, 710-3(b)
Definitions, Art. 100
Bulk storage plants, 515-5(a)
Deflection of conductors
Service stations, 514-8
Auxiliary gutters, 374-9(d)
Underground feeder and branch-circuit
Cabinets and cutout boxes, 373-6
cable, 339-3(a)(3)
Underground service cable, 230-49,
Deicing installations, see Fixed outdoor
310-7, Table 300-5
electric deicing and snow-melting
equipment
Disconnecting means
Air-conditioning and refrigerating equip-
Delta breakers, 384-16(e)
ment, 440-B
Delta-connected, 4-wire, 3-phase supply,
Appliances, 422-D
identifying high leg, 215-8, 230-56,
Capacitors, 460-8(c)
384-3(e)
Cranes, 610-D
Demand factor, see also Loads
Definitions, Art. 100-A, 551-2
Definition, Art. 100-A
Electric space heating equipment, 424-C
Electrolytic cells, 668-13
Detached buildings, oil-insulated trans-
Electronic computer/data processing
formers in, 450-26 Ex. 4
equipment, 645-2(1), 645-10
Detearing equipment, electrostatic, 516-4
Electroplating systems, 669-8, 669-9
Deteriorating agents, 110-11
Elevators, 620-F
Fuses and thermal cutouts, 240-40
Device, see also specific type such as
Identification, 110-22
Switching device
Definition, Art. 100-A
Induction and dielectric heating equipment, 665-43
INDEX
70-885
Interconnected electric power production
Dustproof
sources, 705-20, 705-21
Definition, Art. 100-A
Irrigation machines, 675-8
Dusts, see Hazardous (classified) locations
Mobile homes, 550-6
Motors and controllers, 430-H, 430-127
Dusttight
Recreational vehicles, 551-43
Definition, Art. 100-A
Separate building on same premises,
Duty cycle, welding, 630-31(b)(FPN)
250-24(c)
Duty, types
Services, 230-F
Definitions, Art. 100-A
Connections, ahead of, 230-82, 700-
12(e)
Dwellings, see also Appliances; Boxes;
Over 600 volts, 230-205, 230-206
Branch circuits; Fixtures; Ground-
Signs and outline lighting, 600-2(a)
ing; and similar general categories
Welders, resistance, 630-33
Branch-circuit voltages, 210-6(a)
X-ray equipment, 517-72, 660-5, 660-24
Definitions, Art. 100-A
Farm, services, 220-40(a), 220-41
Discontinued outlets, see Outlets, discon-
Feeder load, calculations for, 220-10(a),
tinued
220-30 thru 220-32, Chap. 9, Part B
Dissimilar metals, see Metals, dissimilar
Lighting fixtures, 410-75, 410-80(b)
Doors, transformer vaults, 450-43, 450-44
Lighting loads for, Table 220-3(b)
Panelboards as services, 384-3(c),
Double insulated, appliances and tools,
384-16(a)
250-45(c), 422-8(d) Ex.
Receptacle circuits required, 220-4(b)
Double locknuts, see Locknuts, double
Receptacle outlets required, 210-52,
Drainage
680-6(a)(2)
Equipment, 501-5(f)
Protection by ground-fault circuit-
Oil-insulated outdoor transformers,
interrupters, 210-8(a), 680-6(a)(1) Ex.
450-27
Eccentric knockouts, see Knockouts,
Raceways, see Raceways, drainage
bonding service equipment
Transformer vaults, 450-46
Elbows, metal, protection from corro-
Dressing rooms
sion, 300-6
Motion picture studios, 530-C
Electric discharge lighting
Theaters, 520-F
Connection to fixtures, 410-14, 410-30(c)
Drip loops
More than 1000 volts, 410-Q
Conductors entering buildings, 225-11,
1000 volts or less, 410-P
230-52
Signs and outline lighting, Art. 600
Service heads, 230-54
Wiring, equipment, 410-P, 410-Q
Driveways
Electric power production sources, see
Clearance of conductors, 225-18
Generators; Interconnected electric
Clearance of service drop, 230-24(b)
power production sources; Solar
Protection of service cables, 230-50(a)
photovoltiac systems
Drop, see Service drop; Voltage drop
Electric signs, see Signs, electric
Dry location, see also Damp or wet
Electric space heating equipment, see
locations
Fixed electric space heating
Definition, Art. 100-A
equipment
Dryers, clothes, see Clothes dryers
Electric welders, see Welders, electric
Dry-type transformers, 450-1 Ex.2,
Electrical ducts
450-3(b), 450-21, 450-22
Definition, 310-15
Dual-voltage motor, locked-rotor rating,
Electrical metallic tubing, Art. 348
430-7(b)(3)
Bends, how made, 348-9
Duct heaters, installation of, 424-F
Bends, number in one run, 348-10
Boxes and fittings, 348-13
Ducts
Connectors and couplings, 348-8
Electrical, 310-15, B-310-15(b)(4)
Construction and installation, 348-B
Lighting fixtures in, 410-4(c)
Marking, 348-15(d)
Wiring in, 300-21, 300-22, 725-2(b),
Minimum and maximum sizes, 348-5
760-2(b), 770-2(b), 800-51(a) and
Number of conductors in, 348-6
(b), 820-53(a)
Reaming of, 348-11
Dumbwaiters, see Elevators, dumbwait-
Splices and taps, 348-14
ers, escalators, moving walks,
Supports for, 348-12
wheelchair lifts, and stairway
Threads on, 348-7
chair lifts
Uses permitted, 348-1
Dust-ignitionproof, 502-1
Wet locations, in, 348-4
70-886
NATIONAL ELECTRICAL CODE
Electrical noise
Elevators, dumbwaiters, escalators,
Grounding, 250-74 Ex. 4, 250-75 Ex.
moving walks, wheelchair lifts,
Panelboards, 384-20
and stairway chair lifts, Art. 620
Receptacles, 410-56(c)
Cables, 620-E
Electrical nonmetallic tubing, 300-4(b),
Conductors, 620-B thru 620-D
Art. 331
Disconnecting means and control, 620-F
Bends, 331-9, 331-10
Essential electrical systems, 517-32(f),
Boxes and fittings, 331-12
517-42(g)
Construction, 331-C
Grounding, 250-43 (e),620-J
Definition, 331-1
Machine room, 620-H
Installation, 331-B
Overcurrent protection, 620-G
Joints, 331-8
Overspeed equipment, 620-K
Number of conductors in, 331-6
Wiring, 620-C
Size, 331-5
Splices and taps, 331-13
Emergency systems, Art. 700; see also
Supports, 331-11
Legally required standby systems;
Trimming, 331-7
Optional standby systems
Uses not permitted, 331-4
Capacity, 700-5
Uses permitted, 331-3
Circuit wiring, 700-B
Circuits for lighting and power, 700-D,
Electrically operated pool covers, see
700-E
Covers, pool, electrically operated
Connections at services, 230-82, 230-83
Electrodes, grounding
Control, 700-E
Aluminum, 250-83(e)
Definitions, 517-3
Common, 250-54
Equipment approval, 700-3
Concrete encased, 250-81(c)
Health care facilities, 517-30(c)(3), 517-31
Gas piping as, 250-83(a)
Overcurrent protection, 700-F
Made, 250-81, 250-83
Service disconnecting means, 230-83
Metal frame of building as, 250-81(b)
Service-drop conductors, 230-2 Ex. 2
Metal water piping system, 250-81(a)
Signals, 700-7
Resistance to ground of, 250-84
Signs, 700-8
Separately derived systems, 250-26(c)
Sources of power, 700-C
Electrolytic cells, Art. 668
Tests and maintenance, 700-4
Auxiliary nonelectric connections, 668-31
Transfer equipment, 700-6
Cell line conductors, 668-12
Unit equipment, 700-12(f)
Cell line working zone, 668-10
Cranes and hoists, 668-32
Enamel, coating of
DC cell line process power supply,
Electrical metallic tubing, 348-1
668-11
General equipment, indoor use only,
Definitions, 668-2
300-6(a)
Disconnecting means, 668-13
Intermediate metal conduit, 345-3
Fixed electrical equipment, 668-30
Metal boxes, 370-20
Grounding, 668-15
Metal cabinets, 373-10(a)
Portable electrical equipment, 668-20,
Removing for grounding connections,
668-21, 668-30
250-75
Shunting means, 668-14
Rigid metal conduit, 346-1(a)
Electronic computer/data processing
Enclosed
equipment, Art. 645
Definition, Art. 100-A
Cables not in computer rooms, 645-6
Enclosures, see also Hazardous (classi-
Circuits and interconnecting cables,
fied) locations
645-5
Arcing parts, 110-18
Disconnecting means, 645-10
Bonding, 250-74, 250-75
Grounding, 645-15
Cabinets and cutout boxes, 373-7 thru
Marking, 645-16
373-9, 373-11
Penetrations, 645-7
Circuits in, number of, 90-8(b)
Special requirements for rooms with,
Cranes, hoists, resistors, 610-2
645-2
Definition, Art. 100-A
Uninterruptible power supplies (UPS),
645-11
Elevators, dumbwaiters, escalators, moving walks, wheelchair lifts, and
Electroplating systems, Art. 669
stairway chair lifts, 620-3, 620-H
Branch-circuit conductors, 669-5
Grounding, 250-D
Disconnecting means, 669-8, 669-9
High-intensity discharge lamp auxiliary
Overcurrent protection, 669-9
equipment, 410-54
Warning signs, 669-7
Induction and dielectric heating, 665-20
Wiring methods, 669-6
Installations over 600 volts, 710-31
Electrostatic equipment, spraying and
Intrinsically safe conductors in,
detearing paint, 516-4
504-30(a)(2)
INDEX
70-887
Overcurrent protection, 240-C
Explosive atmospheres, gases, liquids,
Panelboards, 384-18
dusts, ignitible fibers, lints and
Radio equipment, 810-71(a)
flyings, see Hazardous (classified)
Signs, 600-8, 600-34(g) and (h)
locations
Subsurface, 110-12(b)
Exposed, see also Enclosures
Switches, 380-3
Conductive surfaces
Underground, 110-12(b)
Definition, 517-3
Energized parts, see also Live parts
Extensions, boxes, and fittings, 370-12
Motors, motor circuits, and controllers,
Live parts, 110-16
430-K
Definition, Art. 100-A
Energy-limited, Class 2 and Class 3 con-
Wiring methods
trol and signal circuits, 725-31
Definition, Art. 100-A
Enforcement of code, 90-4, 510-2
Extension cord sets
On construction sites, 305-6(b)
Equipment, see also specific types of
Approval, 90-4, 110-2
Overcurrent protection, 240-4
Cooling of, 110-13(b)
Extensions
Definition, Art. 100-A
Auxiliary gutters, 374-2
Examination of, 90-7, 110-3
Boxes and fittings, exposed, 370-12
Grounding, 250-E
Cellular concrete floor raceways, 358-6
Installation, general provisions, Art. 110
Cellular metal floor raceways, 356-11
Less than 50 volts, Art. 720
Flat cable assemblies, 363-14
More than 600 volts, 710-B
Nonmetallic, see Nonmetallic extensions
Mounting, see Mounting of equipment
Underplaster, see Underplaster extensions
Sealable, see Sealable equipment
Wireways, 362-9, 362-11
Service
Externally operable, see Operable, externally
Definition, Art. 100-A
Faceplates
Equipment grounding conductors
Grounding, 250-33, 250-42, 410-56(d)
Connections at outlets, 250-74, 250-114
Material, 380-9, 410-56(d)
Definition, Art. 100-A
Minimum thicknesses for, 380-9,
Installation, 210-7, 215-6, 250-50 Ex.,
410-56(d)
250-92(b)
Mobile homes, 550-10(d)
Sizing, 250-95
Mounting surfaces, against, 380-10(b),
Types recognized, 250-57, 250-91(b),
410-56(e)
250-92(b)
Fans, ceiling, see Ceiling fans
Equipment system
Definition, 517-3
Farm buildings, feeder calculations,
Escalators, see Elevators, dumbwaiters,
220-40; see also Agricultural buildings
escalators, moving walks, wheel-
Feeder assembly, mobile homes
chair lifts, and stairway chair lifts
Definitions, 550-2
Essential electrical systems, see also
Feeders, Art. 215, Art. 220
Health care facilities
Busways, 364-10
Definition, 517-3
Calculation of loads, 220-10(a), 220-30,
Examples (computations), Chap. 9,
Chap. 9 Part B
Part B
Definition, Art. 100-A
Farm buildings, for, 220-40
Exciters
Ground-fault circuit-interrupters, with,
Leads in enclosure with other conduc-
215-9, 215-10, 517-14
tors, 300-3 (c) Ex. 3
Overcurrent protection for, 445-4(a)
Grounding means, 215-6
Kitchen equipment, commercial, 220-20
Exhaust ducts, see Ducts
Loads, see Loads, feeder
Exit signs, see Signs, exit
Mobile home parks, 550-5(a), 550-C
Exits, emergency lighting for, 700-1(FPN
Motion picture studios, 530-18(b)
No. 3); see also Health care
Motors, 430-B
facilities
Outside, Art. 225
Expansion joints, 250-77, 300-7(b), 347-9,
Overcurrent protection, motor, 430-E
364-28, 374-7, 424-44(c), 424-98(c),
Restaurants, 220-36
426-20(e), 426-22(d), 427-16
Taps, 240-21 Exs., 430-28 Ex.
Explanatory material (FPN), 90-5
Feed-through connections of neutral
Explosionproof apparatus, see also Hazconductors, 300-13(b)
ardous (classified) locations
Ferrous metals, protection from corro-
Definition, Art. 100-A
sion, 300-6
70-888
NATIONAL ELECTRICAL CODE
Festoon lighting
Fire pumps
Conductor size, 225-6
Connection at services, 230-72(a) Ex.,
Definition, 225-6(b)
230-82 Ex. 5, 230-94 Ex. 4
Supports, outside circuits, 225-13
Emergency power supply, Art. 700
Festoons, portable stage equipment,
Installations, 450-3(d)
520-65
Motor, overcurrent protection, 430-31
Fiber bushings, AC cable ends, 333-9
Remote-control circuits, 430-72
Service drops, 230-2 Ex. 1
Fibers, lint, flyings, ignitible, Art. 503,
Service equipment overcurrent protecsee also Hazardous (classified) location, 230-90, Ex. 4
tions
Fire spread along cables, low voltage
Films, motion picture, see also Projecsystems, see type of system
tors, motion picture
involved such as Fire resistance of
Storage vaults, 530-E
cables
Viewing, cutting, patching tables, 530-D
Fire spread, prevention of through walls,
Fine Print Notes (FPN), explanatory.
floors, etc., 300-21, 725-2(a),
material, 110-1
760-2(a), 770-2(a), 800-52(b), 820-
Fire alarms, see Alarm systems; Alarms;
52(b)
Fire protection signaling systems
Fire-stopped partitions, 300-21, see also
Circuits, see Fire protection signaling
Firewalls
systems
Firewalls, wiring through, 300-21,
Connections at services, 230-82 Ex. 5,
800-52(b), 820-52(b)
230-94 Ex. 4
Fittings, Art. 370; see also Wiring Meth-
Fire detectors, line-type, 760-55
ods, types
Conduit bodies, 370-16
Fire protective signaling systems,
Definition, Art. 100-A
Art. 760
Access to electrical equipment, 760-7
Fixed electric heating equipment for
Circuits extending beyond one building,
pipelines and vessels, Art. 427
760-5
Controls, 427-56
Classification, 760-3
Definitions, 427-2
Grounding, 250-43(i), 760-6
Disconnecting means, 427-55
Health care facilities, 517-F
Grounding, 427-21, 427-29, 427-48,
517-13
Identification, 760-4
Location, 760-2
Impedance heating, 427-D
Nonpower-limited circuits, 760-B
Induction heating, 427-E
Installation, 427-B
Cable marking, 760-17
Conductors, 760-16
Nonheating leads, 427-18(a)
Conductors of different circuits in same
Overcurrent protection, 427-57
Resistance heating elements, 427-C
raceway, etc., 760-15
Skin effect heating, 427-F
Location of overcurrent devices,
760-13
Fixed electric space heating equipment,
Art. 424
Multiconductor cable, 760-17
Number of conductors in raceway, etc.
Boilers, protection of, 424-72(a)
Branch circuits for, 424-3
and derating, 760-18
Overcurrent protection, 760-12
Cables, 424-E
Area restrictions, 424-38
Power limitations, 760-11
Wiring method, 760-14, 760-17(d)
Clearances, wiring
Power-limited circuits, 760-C
Ceilings, 424-36
Applications, 760-53
Other objects, openings, 424-39
Walls, 424-37
Cable markings, 760-50
Construction, 424-34
Cable substitutions, 760-54
Finish, ceilings, 424-42
Circuit markings, 760-22
Installation
Conductors and cables, 760-50
Cables, 424-44
Fire resistance of cables, 760-49
Nonheating leads, 424-43
Installation, 760-50, 760-52
Marking, 424-35
Line-type fire detectors, 760-55
Splices, 424-40
Location of overcurrent devices,
Tests, 424-45
760-24
Control and protection, 424-C
Nonpower limited, 760-28(a)
Controllers, 424-20(a)
Overcurrent protection, 760-23
Disconnecting means, 424-19 thru
Power limitations, 760-21
424-21
Separation of conductors, 760-52
Indicating, 424-21
Wiring methods and materials
Overcurrent protection, 424-22
Load side, 760-28
Duct heaters, 424-F
Supply side, 760-25
Air flow, 424-59
INDEX
70-889
Condensation, 424-62
Fixture wires, Art. 402
Disconnecting means, location, 424-65
Ampacities, 402-5
Elevated inlet temperature, 424-60
Grounded conductor, identification,
Fan circuit interlock, 424-63
402-8
Identification, 424-58
Marking, 402-9
Installation, 424-61, 424-66
Minimum size, 402-6
Limit controls, 424-64
Number in conduits, 402-7, Chap. 9,
Electrode-type boilers, 424-H
Table 2
Installation, 424-B
Overcurrent protection, 240-4, 402-12
Grounding, 424-14
Types, 402-3
Location
Uses not permitted, 402-11
Exposed to physical damage,
Uses permitted, 402-10
424-12(a)
Fixtures, see Lighting fixtures
Wet areas, 424-12(b)
Spacing, combustible materials, 424-13
Flame spread, see Fire spread
Special permission, 424-10
Flammable anesthetics, see Anesthetics,
Supply conductors, 424-11
flammable
Marking, 424-D
Flammable gases and vapors, see Haz-
Heating elements, 424-29
ardous (classified) locations
Nameplate, 424-28
Overcurrent protection for, 424-22
Flammable liquids, see Hazardous (classi-
Radiant heating panels and heating panel
fied) locations
sets, 424-J
Flashers, time switches, etc., 380-5,
Clearances, wiring
600-2(b), 600-8(b)
Ceilings, 424-94
Flat cable assemblies, Type FC, Art. 363
Walls, 424-95
Branch-circuit rating, 363-16
Connection, 424-96
Conductor insulations for, 363-8
Definitions, 424-91
Dead ends, 363-11
Installation, 424-93, 424-98, 424-99
Definition, 363-1
Markings, 424-92
Extensions from, 363-14
Nonheating leads, 424-97
Fittings for, 363-13
Resistance-type boilers, 424-G
Fixture hangers for, 363-12
Fixed equipment, grounding, 250-42 thru
Identification, 363-19
250-44, 250-57, 250-58, 517-13
Installation, 363-5
Fixed outdoor electric deicing and
Marking, 363-17
snow-melting equipment, Art. 426
Number of conductors in, 363-6
Branch circuits for, 210-23, 426-4
Protective covers for, 363-18
Connections, 426-24
Size of conductors in, 363-7
Cord- and plug-connected, 426-54
Splices, 363-9
Definitions, 426-2
Supports for, 363-15
Disconnecting means, 426-50
Taps and tap devices, 363-10
Equipment protection, 426-53
Terminal block identification, 363-20
General, 426-10
Uses not permitted, 363-4
Grounding, 426-27, 426-34, 426-44
Uses permitted, 363-3
Identification of, 426-13
Flat conductor cable, Type FCC, Art. 328
Impedance heating, 426-D
Branch-circuit rating, 328-6
Induced currents, 426-33
Cable connections and ends, 328-11
Isolation transformer, 426-32
Construction, 328-C
Personnel protection, 426-30
Conductor identification, 328-32
Voltage limitations, 426-31
Corrosion resistance, 328-33
Marking, 426-25
Insulation, 328-34
Nonheating leads, 426-22, 426-23, 426-25
Markings, 328-31
Overcurrent protection of, 426-52
Receptacles and housings, 328-36
Protection, corrosion, 426-26, 426-43
Transition assemblies, 328-37
Protection, thermal, 426-12
Definitions, 328-2
Resistance heating elements, 424-C
Installation, 328-B
Embedded, 426-20
Alterations, 328-19
Exposed, 426-21
Anchoring, 328-16
Skin effect heating, 426-E
Cable connections and insulating ends,
Conductor ampacity, 426-40
328-13, 328-15
Pull boxes, 426-41
Connections or other systems, 328-15
Single conductor, 426-42
Coverings, 328-10
Special permission, 426-14
Crossings, 328-17
Thermostats for, 426-51
Enclosure and shield connections,
Use of, 426-11
328-13
Fixture stud, construction, 410-16(d)
Receptacles, 328-14
70-890
NATIONAL ELECTRICAL CODE
Shields, 328-12
Two-phase, Table 430-149
System height, 328-18
Direct current, Table 430-147
Polarization, 328-20
Systems alterations, 328-19
Furnaces, see Heating equipment, central
Uses not permitted, 328-5
Furnaces, transformers, installation,
Uses permitted, 328-4
450-26 Ex. 3
Fuseholders
Flatirons, 422-13
Signals, 422-12
Cartridge fuses, 240-F
Stands for, 422-11
Over 600 volts, 710-21(b)
Temperature-limiting means, 422-12 Ex.,
Plug fuses, 240-E
422-13
Rating, motor controllers, 430-90
Type S, 240-53, 240-54
Flexible cords, see Cords, flexible
Fuses, Art. 240; see also Hazardous
Flexible metal conduit, Art. 350
(classified) locations
Bends, 350-6
Cartridge, see Cartridge fuses
Grounding, 350-5
Definition, over 600 volts, 100-B
Minimum size, 350-3
Disconnecting means, 240-40
Number of conductors, 350-7
Enclosures, 240-C
Supports, 350-4
Generators, constant-voltage, 445-4(a)
Uses not permitted, 350-2
Group installation of motors, 430-53(c)
Floating buildings, Art. 553
In parallel, not permitted, 240-8, 380-17
Bonding of noncurrent carrying metal
Location in circuit, 240-21
parts, 553-11
Location on premises, 240-24
Definition, 553-2
Motor branch circuit protection, 430-D
Feeder conductors, 553-6
Motor overload protection, 430-C
Grounding, 553-C
Multiple, see Multiple fuses
Service conductors, 553-5
Plug, Edison-base type, 240-E
Service equipment location, 553-4
Potential (voltage) transformers, 450-3(c)
Services and feeders, installation, 553-7
Ratings, 240-6
Floors, receptacles, 210-52(a),
Services over 600 volts, 230-208(c)
250-74 Ex. 3, 370-17(b)
Type S, 240-53, 240-54
Flue damper control, see Dampers (flue),
Future expansion and convenience, 90-7(a)
control
Garages, commercial, Art. 511
Fluorescent lighting fixtures, 410-P,
Classification of locations, 511-2, 511-3
410-Q
Definition, Art. 100-A
Autotransformers in ballasts, 410-78
Electric vehicle charging, 511-9
Auxiliary equipment, remote from,
Elevators, dumbwaiters, escalators, mov-
410-77
ing walks, in, 620-38
Ballast protection required, 410-73(e)
Equipment, 511-4, 511-7, 511-8
Circuit breakers used to switch,
Ground-fault circuit-interuption protection, 511-10
240-83(d)
Connection of, 410-14, 410-30
Grounding fixed equipment, 250-43(f)
Load calculations
Outlets, 210-52(g)
Sealing, 511-5
Ampere ratings, ballasts, 210-22(b)
Branch circuits, 210-23
Wiring, 511-4, 511-6
Raceways, 410-31
Gas pipe
Snap switches for, 380-14(a)(1), (b)(2)
As grounding electrode, 250-83(a)
Surface-mounted or recessed,
Grounding conductor, connection,
410-8(b)(2), 410-8(d)
250-112
Thermal protection, 410-73(e)
Gases, see Hazardous (classified)
Fluoroscopic equipment, see X-ray
locations
equipment
Gasoline bulk storage plants, see Bulk
Footlights, theaters, 520-43
storage plants; see also Hazardous
Disappearing, 520-43(c)
(classified) locations
Gasoline dispensing and service sta-
Formal interpretations, 90-6
tions, Art. 514; see also Hazardous
Forming shells, underwater pool lighting
(classified) locations
fixtures, 680-20(b)
Circuit disconnects, 514-5
Definition, 680-4
Class I locations, 514-2
Fountains, 680-E
Conductor insulations where exposed to
(FPN), see Fine print notes
gasoline, 310-9, 501-13
Definition, 514-1
Full-load current motors
Equipment, 514-3, 514-4
Alternating current
Sealing, 514-6
Single-phase, Table 430-148
Wiring, 514-3, 514-4, 514-8
Three-phase, Table 430-150
Gauges, conductors, 110-6
INDEX
70-891
General care areas, 517-15(1), 517-18
Goosenecks, service cables, 230-54
Definition, 517-3
"Greenfield", see Flexible metal conduit
General provisions, installation of wiring
Ground
and equipment, Art. 110
Definition, Art. 100-A
General requirements for wiring meth-
Voltage to
ods, Art. 300
Definition, Art. 100-A
Boxes or fittings, where required, 300-15
Ground clamps, 250-113, 250-115, 250-117
Changing raceway, cable to open wiring,
Ground ring, 250-81(d)
300-16
Conductors, 300-3
Grounded
Different systems, 300-3(c)
Definition, Art. 100-A
Installation with other systems, 300-8
Effectively, 250-81(b)(FPN)
Insulating bushings for raceways,
CATV system, 820-30, 820-D
373-6(c)
Communication system, 800-D
Number and sizes of, in raceways,
Definition, 100-A
300-17
Grounded conductor, see Conductors,
Supporting, vertical raceways, 300-19
Grounded; Neutral
Expansion joints, raceways, 300-7(b)
Ground-fault circuit-interrupters
Exhaust and ventilating ducts, wiring,
Definition, Art. 100-A
300-22
Deicing and snow-melting equipment,
Feed-through neutral connections,
426-31 Ex.
300-13(b)
Electrically operated pool covers,
Free length of wire at outlets, 300-14,
680-26(b)
550-10(h), 551-48(b)
Fountains, 680-51(a)
Grounding metal enclosures, 300-9
Garages, commercial, 511-10
Induced currents in metal enclosures,
Permitted uses, 210-8, 215-9
300-20
Personnel, protection for, 426-30, 426-31
Mechanical and electrical continuity,
Ex.
conductors, raceways, cables,
Pipeline heating, 427-26 Ex.
300-10, 300-12, 300-13
Receptacles, 210-7(d), 210-8
Over 600 volts, 110-B, 300-B, Art. 710
Bathrooms, in dwelling units,
Protection against
210-8(a)(1)
Corrosion, 300-6
Bathrooms in hotels and motels,
Physical damage, 300-4
210-8(b)
Raceways as a means of support,
Boathouses, 210-8(a)(6)
300-11(b)
Construction sites, at, 305-6
Raceways exposed to different tempera-
Existing, 210-7(d)
tures, 300-7
Garages, in dwelling units, 210-8(a)(2)
Sealing, raceways, change in tempera-
Health care facilities, 517-20(1)
ture, 300-7(a)
Kitchens in dwelling units, 210-8(a)(5)
Securing and supporting, 300-11
Marinas and boatyards, 555-3
Spread of fire or products of combustion,
Mobile homes, 550-8(b), 550-23(d)
300-21
Pools, 680-5, 680-6, 680-21, 680-31,
Through studs, joists, rafters, 300-4(a)
680-62(a)
Underground installations, 300-5, 300-37
Recreational vehicles, 551-41(c), 551-71
Voltage limitations, 300-2
Ground-fault protection
Wiring in ducts, plenums, air-handling
Emergency systems, not required, 700-26
spaces, 300-22
Equipment, 215-10, 240-13
Generators, Art. 445
Definition, of, Art. 100-A
Bushings, 445-8
Health care facilities, 517-17
Conductor, ampacity of, 445-5
Personnel, 215-9
Emergency systems, 700-12(b)
Service disconnecting means, 230-95
Essential electrical systems, 517-32(e),
Grounding, Art. 250
517-42(f)
AC systems, 250-5, 250-23, 250-25
Grounding, 250-6, 250-43
Air-conditioning units, 250-45
Guards for attendants, 445-7
Anesthetizing locations, 517-62
Health care facilities, 517-32(e), 517-35,
Antenna, 810-15, 810-21, 810-58, 810-71
517-42(f)
Appliances, 250-45, 422-16
Location, 445-2
Bonding, 250-G
Marking, 445-3
Busways, over 600 volts, 364-22
Overcurrent protection, 445-4
Cablebus, 365-9
Portable, 250-6
Capacitors, 460-10
Protection of live parts, 445-6
CATV systems, 820-D
Recreational vehicles, 551-7
Circuits, 250-A, 250-B
Standby systems, Art. 701, 702
Less than 50 volts, 720-10
70-892
NATIONAL ELECTRICAL CODE
Clothes dryers, 250-60
Separate buildings, 250-24
Clothes washers, 250-45
Separately derived systems, 250-5(d),
Communications systems, 800-33, 800-D
250-26
Connections, location, 250-C, 250-K
Services, 230-63
Construction sites, 305-5
Signs and outline lighting, 600-5
Continuity, 250-75
Sound recording equipment, 640-4(d)
Control circuits, 725-20, 725-43
Spas and tubs, 680-41(f), 680-41(g)
Control, radio equipment, 810-71(b)
Surge arresters, 280-25
Cranes and hoists, 610-61
Swimming pools, 680-7, 680-21(d),
DC systems, 250-3, 250-22
680-24, 680-25
Deicing, snow-melting systems, 426-27
Switchboard frames, 384-11
Dishwashers, 250-45(c) and (d)
Switchboards, 384-12
Electrode system, 250-H
Switches, 380-12
Electronic computer/data processing
Systems, 250-A, 250-B
equipment, 645-15
Theaters and similar locations, 520-81
Elevators, 620-J
Tools, motor operated, 250-45
Enclosures, metal, wiring methods, 300-9
Transformers, 450-10
Equipment, cord- and plug-connected,
X-ray equipment, 517-77, 660-D
250-45
Grounding conductors, 250-J
Fire protective signaling circuits, 250-
Connections, 250-K
43(i), 760-6
Definition, Art. 100-A
Fixed electric space heating equipment,
Earth as, 250-51, 250-91(c)
424-14
Enclosures, 250-D
Fixed equipment, 250-42, 250-43, 250-57,
Identification, multiconductor cable,
517-13
250-57(b) Ex. 3, 310-12(b) Ex. 2
Fixtures, lampholders, etc., 410-E
Installation, 250-92
Material, 250-91
Fountains, 680-54, 680-55
Objectionable current over, 250-21
Freezers, 250-45
Sizes, 250-95
Generators, 445-1
Grounding electrode conductors
Portable and vehicle mounted, 250-6
Connection to electrodes, 250-K
Hazardous (classified) locations, 501-16,
Definition, Art. 100-A
502-16, 503-16
Installation, 250-92
Health care facilities, 517-13, 517-19
Material, 250-91
Induction and dielectric heating equip-
Sizing, 250-93, 250-94
ment, 665-B
Grounding point
Instrument transformers, relays, etc.,
250-L
Patient equipment
Definition, 517-3
Intrinsically safe systems, 504-50
Reference
Lightning surge arresters, 280-25
Definition, 517-3
Metal boxes, 370-40
Grounding-type attachment plugs, see
Metal enclosures for conductors, 250-33
Attachment plugs, Grounding-type
Metal faceplates, 410-18(a), 410-56(d)
Group installation, motors, 430-53
Metal siding, 250-44 (FPN)
Fire pumps, 230-72(b)
Methods, 250-F
Mobile homes, 550-11
Grouping, switches, circuit breakers,
380-8; see also Accessible
More than 600 volts between conductors,
710-6, 710-7
Grouping of disconnects, 230-72
Motion picture studios, 530-20, 530-66
Guarded
Motors and controllers, 430-L
Definition, Art. 100-A
Nonelectrical equipment, 250-44
Guarding, guards, see also Enclosures;
Organs, 650-4
Live parts
Over 600 volts, 300-36, 710-47, 710-60,
Circuit breaker handles, 240-41(b)
710-74
Construction sites, 305-7
Over 1000 volts, 250-M
Elevators, dumbwaiters, escalators, mov-
Panelboards, 384-20, 517-19(d)
ing walks, 620-71
Patient care areas, 517-19(c)
Generators, 445-7
Portable equipment, 250-45
Handlamps, portable, 410-42(b)
Radio and television, 810-15, 810-21,
Induction and dielectric heating equipment, 665-B
810-58, 810-71
Lamps, theaters, dressing rooms, etc.,
Ranges and similar appliances, 250-60
520-44, 520-47, 520-65, 520-72
Receptacles, 210-7, 250-74, 250-114,
Live parts
410-58, 517-13, 517-19(g)
General, 110-17
Recreational vehicles, 551-54, 551-55,
In theaters, 520-6
551-75, 551-77
On stage switchboards, 520-22
Refrigerators, 250-45(c) and (d)
Motion picture studios, 530-15, 530-64
INDEX
70-893
Motors and motor controllers, 430-K,
Receptacles and attachment plugs,
430-143
501-12
Over 600 volts, 110-34, 305-7, 710-3(b)(1)
Sealing, fittings and compound, 501-5
Transformers, 450-8
Signal, alarm, remote-control, and com-
X-ray installations, 517-77
munication systems, 501-14
Guest rooms, outlets, 210-63(b)
Surge protection, 501-17
Switches, 501-6
Gutters, auxiliary, see Auxiliary gutters
Transformers and capacitors, 501-2
Hallways, outlets, 200-52(h)
Utilization equipment, 501-10
Handlamps, portable, 410-42(b)
Wiring methods, 501-4
Hangars, aircraft, see Aircraft hangars
Hazardous (classified) locations, Class
Hazard current
II, Art. 502
Definition, 517-3
Bonding, 502-16(a)
Circuit breakers, 502-6
Hazardous areas, see Hazardous (classi-
Control transformers and resistors, 502-7
fied) locations
Cranes and hoists, 610-2
Hazardous atmospheres, Art. 500
Flexible cords, 502-12
Class I locations, 500-5
Fuses, 502-6
Class II locations, 500-6
Grounding, 502-16
Class III locations, 500-7
Lighting fixtures, 502-11
Special precautions and Groups A-G,
Live parts, 502-15
500-3
Motor controllers, 502-6
Specific occupancies, 500-4, Art. 510
Motors and generators, 502-8
Hazardous (classified) locations,
Receptacles and attachment plugs,
Art. 500
502-13
Aircraft hangars, 513-2
Sealing, 502-5
Anesthetizing locations, 517-60, 517-61
Signal, alarm, remote-control, and com-
Approval for class and properties,
munication systems, meters, instru-
500-3(c)
ments, and relays, 502-14
Bulk storage plants, 515-2
Surge protection, 502-17
Dusts, explosive, Art. 502
Switches, 502-6
Fibers, flyings, lint, highly combustible
Transformers and capacitors, 502-2
material, Art. 503
Utilization equipment, 502-10
Garages, commercial, 511-2, 511-3
Ventilating piping, 502-9
Gases, flammable, Arts. 500, 501
Wiring methods, 502-4
Gasoline service stations, see Gasoline
Hazardous (classified) locations, Class
dispensing and service stations
III, Art. 503
Group classifications, 500-3(a) and (b)
Bonding, 503-16(a)
Hoists, 503-13
Circuit breakers, 503-4
Inhalation anesthetizing locations, see
Control transformers and resistors, 503-5
Anesthetizing locations
Cranes and hoists, 503-13, 610-2
Liquids, flammable, Art. 500, 501
Flexible cords, 503-10
Marking, 500-3(b)
Fuses, 503-4
Temperature, 500-3(e) and (f)
Grounding, 503-16
Special precautions, 500-3
Lighting fixtures, 503-9
Spray application, dipping and coating
Live parts, 503-15
processes, 516-2
Motor controllers, 503-4
Vapors, flammable, Art. 500, 501
Motors and generators, 503-6
Hazardous (classified) locations, Class I,
Receptacles and attachment plugs,
Art. 501
503-11
Bonding, 500-2, 501-16(a), 504-60
Signal, alarm, remote-control, and local
Circuit breakers, 501-6
loudspeaker intercommunications,
Conductor insulation, 501-13
503-12
Control transformers and resistors, 501-7
Storage battery charging equipment,
Cranes and hoists, 610-2
503-14
Drainage of equipment, 501-5(f)
Switches, 503-4
Flexible cords, 501-11
Transformers and capacitors, 503-2
Fuses, 501-6
Utilization equipment, 503-8
Grounding, 501-16
Ventilation piping, 503-7
Induction and dielectric heating equip-
Wiring methods, 503-3
ment, 665-4
Headers
Lighting fixtures, 501-9
Cellular concrete floor raceways, 358-2,
Live parts, 501-15
358-5, 358-6, 358-9
Meters, instruments, and relays, 501-3
Cellular metal floor raceways, 356-1,
Motor controllers, 501-6
356-2, 356-5, 356-6
Motors and generators, 501-8
Definition, 356-1, 358-2
70-894
NATIONAL ELECTRICAL CODE
Health care facilities, Art. 517
Heating
Communications, signaling systems, data
Dielectric
systems, less than 120 volts, nomi-
Definition, 665-2
nal, 517-F
Fixed electric space, see Fixed electric
Other-than-patient care areas, 517-81
space heating equipment
Patient care areas, 517-80
Induction
Signal transmission between appli-
Definition, 665-2
ances, 517-82
Heating appliances, Art. 422
Definitions, 517-3
Heating cables, Art. 424
Essential electrical systems, 517-C
Heating elements
Clinics, medical and dental offices, and
Marking, 422-31
outpatient facilities, 517-50
Resistance
Connections
Definition, 427-2
Alternate power source, 517-34
Heating equipment
Critical branch, 517-43
Definition, 665-2
Life safety branch, 517-42
Outside, 550-15(b)
Critical branch, 517-33
Heating equipment, central, 422-7
Emergency system, 517-31
Heating panels and heating panel sets,
Hospitals, 517-30
radiant, 424-J
Life safety branch, 517-32
Heating, pipelines, and vessels
Nursing homes and residential custodial
Definition, 427-2
care facilities, 517-40
Heavy-duty lampholders
Power sources, 517-35, 517-44
Branch circuits, 210-21(a), 210-23, Table
General, 517-2
210-24
Inhalation anesthetizing locations, 517-D
Unit loads, 220-3(c)
Circuits, 517-63
Hermetic refrigerant motor compressors,
Classification, 517-60
see also Air-conditioning and refrig-
Grounding, 517-62
eration equipment
Low-voltage equipment and instru-
Ampacity and rating, 440-12(a)
ments, 517-64
Definition, 440-2
Wiring and equipment, 517-61,
Marking, 440-4
517-160(c)
Rating and interrupting capacity,
Isolated power systems, 517-19(f), 517-G
440-12(a)
Grounded power systems in anesthetiz-
High-impedance grounded neutral sysing locations, 517-160(c)
tems, 250-27
Installation, 517-160(a)
Hoists, Art. 610
Line isolation monitor, 517-160(b)
Conductors, contact, 610-C
Wiring and protection, 517-B
Control, 610-F
Applicability, 517-10
Electrolytic cells, 668-32
Critical care areas, 517-15(2), 517-19
Flexible cords, 400-7
Fixed electrical equipment, 517-13
Grounding, 250-7, 250-43, 610-G
General care areas, 517-15(1), 517-18
Hazardous (classified) locations, 503-13
General installation/construction crite-
Motors and controllers, disconnecting
ria, 517-11
means, 430-112, 610-D
Ground-fault protection, 517-17
Overcurrent protection, 610-E
Grounding, 517-13
Wiring, 610-B
Potential bonding, 517-14
Hoistways
Receptacles, 517-13, 517-16
Definition, Art. 100-A
Wet locations, 517-20
Wiring in, 620-37, 725-38(a)(3)
Wiring methods, 517-12
Hood, metal, stage switchboard, 520-24
X-ray installations, 517-E
Hoods for commercial cooking, lighting
Connection to supply circuit, 517-71
in, 410-4(c)
Control circuit conductors, 517-74
Hospitals, see also Health care facilities
Disconnecting means, 517-72
Definition, 517-3
Equipment installations, 517-75
Essential electrical systems, 517-30
Patient care areas
Guarding and grounding, 517-77
Overcurrent protection, 517-73
Definition, 517-3
Psychiatric
Rating of supply conductors, 517-73
Definition, 517-3
Transformers and capacitors, 517-76
Hot tubs, see Spas and hot tubs
Heat generating equipment, see Induc-
Hotels and motels
tion and dielectric heating equip-
Lighting load, Table 220-3(b)
ment
Receptacle ground-fault circuit inter-
Heat tape outlet, mobile home, 550-8(g)
rupter protection, 210-8(b)
Heater cords, see Cords, Heater
Receptacle outlets required, guest rooms,
210-60
INDEX
70-895
Houseboats, see Floating buildings
Motor-generator equipment, 665-C
Hydromassage bathtubs, 680-G
Other equipment, 665-D
Definition, 680-4
Output, 665-44
Identification
Induction heating
Disconnecting means, 110-22
Definition, 665-2
Fire protective signaling circuits, 760-4
Inductive loads
Flexible cords
Motors, 430-83, 430-109
Grounded-conductor, 400-22
Signs, 600-2(b)
Grounding-conductor, 400-23
Switches, types, ratings, 380-14
Grounded conductors, Art. 200
High leg, 215-8, 230-56, 384-3(e)
Industrial machinery, Art. 670
Intrinsically safe systems, 504-80
Clearance, 670-5
Panelboard circuits, 384-13
Definition, 670-2
Service disconnecting means, 230-70
Nameplate data, 670-3
Ungrounded conductors, 210-4(d)
Supply conductors and overcurrent protection, 670-4
Wiring device terminals, 250-119, 504-80
Infrared lamp heating appliances, 422-15
Identified
Branch circuits, 210-23(c) and (d),
Definition, Art. 100-A
424-3(a) Ex.
Illumination, task
Overcurrent protection, 422-27(c)
Definition, 517-3
Inhalation anesthesizing location, see
Immersible appliances, 422-24
Anesthesizing location
Immersion heaters, cord- and plug-
Inserts
connected, 422-9
Cellular concrete floor raceways, 358-9
In sight from
Cellular metal floor raceways, 356-10
Underfloor raceways, 354-14
Air-conditioning or refrigerating equipment, 440-14
Institutions, emergency lighting, Art. 700
Center pivot irrigation machines,
Instructions, 110-3(b), 230-95(c)
675-8(b)
Instrument transformers, see Transform-
Definition, Art. 100-A
ers, Instrument
Duct heaters, 424-65
Electric-discharge lighting, 410-81(b)
Instruments, meters, relays
Fixed electric space heating equipment,
Grounding, 250-L
424-19
Hazardous (classified) location, 501-3,
502-14
Motor driven appliances, 422-26
Motors, motor controllers, 430-102
Low-voltage, 517-64
Room air conditioners, 440-63
Insulation
Signs, 600-2(a)
Conductors, Art. 310
Incandescent lamps, Art. 410; see also
Construction and application, 310-13
Hazardous (classified) locations
Hazardous (classified) location, Class I,
Guards
501-13
Aircraft hangars, 513-5(a)
Identification, 310-12
Garages, 511-7(a) and (b)
Line-type fire detectors, 760-55(b)
Theater dressing rooms, 520-72
Marking, 310-11
Lamp wattage, marking on fixture,
Motion picture projectors, 540-14
410-70
Theaters, 520-42
Meduim and mogul bases, 410-53
Double, see Double insulated
Snap switches for, 380-14
Equipment, 110-3(a)(4)
Fixture wire, 402-3
Independent
Flexible cords, Table 400-4, 400-B
Emergency lighting supply, 700-17
Heating cables, 424-E, 426-24
Supports, services, over buildings,
Integrity, 110-7
230-29
Service conductors, 230-22, 230-30,
Wiring, emergency circuits, 700-9
230-41
X-ray control, 660-24
Splices and joints, 110-14(b), 305-4(g),
Individual branch circuits, see Branch
400-9, 530-12
circuits, individual
Insulation levels
Induced currents, metal enclosures,
Definitions, Table 310-64
300-20, 334-12
Insulators, nonabsorbent, 230-27, 710-32
Induction and dielectric heating equip-
Insulators, open wiring, see Open wiring
ment, Art. 665
on insulators
Definitions, 665-2
Integrated electrical systems, Art. 685
Guarding, grounding, and labeling, 665-B
Orderly shutdown, 685-B
70-896
NATIONAL ELECTRICAL CODE
Integrated gas spacer cable, Type IGS,
Grounding, 504-50
Art. 325
Hazardous (classified locations), 500-2,
Ampacity, 325-14
504-60
Bends, 325-11, 325-12
Identification, 504-80
Conductors, 325-20
Sealing, 504-70
Construction, 325-C
Wiring methods, 504-20
Definition, 325-1
Introduction, Art. 90
Fittings, 325-13
Irons, see Flatirons
Installation, 325-B
Insulation, 325-21
Irrigation machines, Art. 675
Uses not permitted, 325-4
Bonding, 675-14
Uses permitted, 325-3
Center pivot
Definition, 675-2
Interactive systems
Center pivot irrigation machines, 675-B
Definition, 690-2, 705-2
Collector rings, 675-11
Intercommunication systems, see Com-
Conductors, 675-5, 675-9
munication circuits; Hazardous
Control panel marking, 675-6
(classified) locations
Current ratings, 675-7
Interconnected electric power produc-
Definitions, 675-2
tion sources, Art. 705
Grounding, 675-12, 675-13
Irrigation cable, 675-4
Definitions, 705-2
Lightning protection, 675-15
Directory, 705-10
Motors on branch circuit, 675-10
Disconnect device, 705-22
Disconnecting means, equipment, 705-21
Isolated
Disconnecting means, sources, 705-20
Arcing parts, 110-18
Ground-fault protection, 705-32
Definition, Art. 100-A
Grounding, 705-50
Equipment grounding conductor, 250-74
Interrupting and withstand rating, 705-16
(FPN)
Loss of primary source, 705-40
Phase installations, 300-5(i), Ex. 2
Output characteristics, 705-14
Power systems, 517-G, 517-64(c)
Overcurrent protection, 705-30
Definition, 517-3
Point of connection, 705-12
Essential electrical systems, 517-30(c)
Synchronous generators, 705-43
Grounding, 517-19(g)
Unbalanced interconnections, 705-42
Installation, 517-160(a)
Intermediate metal conduit, Art. 345
Location, 517-160(c)(5)
Bends, 345-10, 345-11
Isolating means, over 600 volts, 710-22
Bushings, 345-15
Isolating switch, see Switch, Isolating
Construction, 345-C
Couplings and connectors, 345-9
Isolation by elevation
Circuits over 600 volts, 110-34(e)
Definition, 345-1
Circuits under 600 volts, 110-17
Number of conductors, 345-7
Reaming and threading, 345-8
Isolation transformer
Size, 345-6
Definition, 517-3
Splices and taps, 345-14
Joints, see also Splices and taps
Supports, 345-12
Expansion, see Expansion joints
Uses permitted, 345-3
Grounding electrode conductor, 250-91(a)
Wet locations, 345-5
Insulation, fixtures, 410-16(e)
Intermittent duty
Insulation of, 110-14(b)
Definition, Art. 100-A
Strain at, 400-10
Motors, 430-22(a) Ex. 1
Joists
Interpretations, formal, see Formal inter-
Air-handling, space, 300-22(c) Ex. 5
pretations
Armored cable, 333-11 Ex. 2, 333-12
Interrupter switch, see Switches, Interrupter
Boxes on, 370-23(a) and (d)
Concealed knob-and-tube wiring, 324-11
Interrupting capacity, 110-9, 110-10,
Electric space heating cables, 424-41(j)
240-60(c), 240-83(c)
Holes through or notches in, 300-4(a)
Interrupting rating, 110-9, 240-60(c),
Nonmetallic sheathed cable, 336-12
240-83(c)
Open wiring, crossing, 320-14
Definition, Art. 100-A
Jumpers, bonding, 250-79
Intrinsically safe equipment, Art. 504
Circuit
Bonding, 504-60
Definition, Art. 100-A
Conductors, separation of, 504-30
Conduit joints, hazardous (classified)
Definitions, 504-2
locations, 500-2
Equipment approval, 504-4
Equipment
Equipment installation, 504-10
Definition, Art. 100-A
INDEX
70-897
Expansion joints, telescoping sections of
Heavy-duty, see Heavy-duty
raceways, 250-77
lampholders
Grounding-type receptacles, 250-74
Infrared lamps, 422-15
Hazardous (classified) locations, 501-
Mogul base, see Mogul base lampholders
16(a), 502-16(b), 503-16
Outdoor, 225-25
Health care facilities, 517-19(c) and (d)
Pendant
Main
Bathrooms, 410-4(d)
Definition, Art. 100-A
Not in clothes closets, 410-8(c)
Piping systems, 250-80
Not in theater dressing rooms, 520-71
Service equipment, 250-72(d), 250-79(d)
Screw-shell types for lamps only, 410-47
Junction boxes, see also Boxes; Pull
Signs and outline lighting, 600-22
boxes
Unswitched over combustible material,
Accessibility, 370-29
410-6
Cellular concrete floor raceways, 358-7
Lamps, Art. 410; see also Lighting; Light-
Cellular metal floor raceways, 356-9
ing fixtures; Hazardous (classified)
Covers, 370-28(c)
locations
Deicing and snow-melting cables, 426-24
Arc, see Arc lamps
Motor controllers and disconnects,
Clothes closets, in, 410-8
430-10
Electric discharge, 410-P, 410-Q
Nonheating cable leads, 424-43
Electric discharge, enclosure, 410-54
Separation from motors, 430-145(b)
Fluorescent, see Fluorescent lighting
Size
fixture
Conductors No. 4 and larger, 370-28
Guards, see Guarding and guards
Conductors No. 6 and smaller, 370-16
Headlamps, see Handlamps
Construction specifications, 370-C
Incandescent, see Incandescent lamps
Supports, 370-23
Infrared, see Infrared lamp heating
Swimming pools, 680-21
appliances
Switch enclosures, 373-8, 710-59
Motion picture projectors, 540-14, 540-20
Underfloor raceways, 354-13
Motion picture studios
Kitchen equipment, commercial, 220-20
Film storage vaults, 530-51
Stages, 530-16, 530-17
Knife switches
Viewing, cutting tables, 530-41
Connection, 380-6(c)
Outdoor, location, 225-25
Construction specifications, 380-B
Portable
Enclosures, 380-3
Flexible cords for, 400-7
Position, 380-6
Motion picture studios, in, 530-16,
Ratings, 380-13
530-17
Knob-and-tube wiring, Art. 324
Show windows, show cases, 400-11
Clearance
Track-lamps, 410-105
Conductor, 324-8
Theaters
Piping, exposed conductors, 324-10
Border and proscenium, 520-44
Conductor supports, 324-6
Dressing rooms, 520-72
Conductors, 324-5
Festoons, 520-65
Definition, 324-1
Footlights, 520-43
Splices, 324-12
Scene docks in, 520-47
Through walls, floors, etc., 324-9
Stage, arc, 520-61
Tie wires, 324-7
Switchboards, pilot lights, 520-53(g)
Uses not permitted, 324-4
Wattage marking, flush and recessed
Uses permitted, 324-3
fixtures, 410-70
Knockouts
Laundry, outlets, dwellings, 210-50(c),
Bonding service equipment, 250-72(d)
210-52(f), 220-4(c)
Openings to be closed, 110-12, 370-7,
370-8, 373-4
Laundry area, mobile home parks
Definition, 550-2
Labeled
Definition, Art. 100-A
Legally required standby systems,
Art. 701
Labels required, 551-47(q)(3), 551-47(r)(4)
Capacity and rating, 701-6
Lacquers and paints
Circuit wiring, 701-B
Application, Art. 516
Overcurrent protection, 701-D
Atmospheres, 500-3, 500-5, Art. 501
Signals, 701-8
Lampholders
Signs, 701-9
Branch circuits supplying, 210-23
Sources or power, 701-C
Circuits less than 50 volts, 720-5
Tests and maintenance, 701-5
Construction, 410-J
Transfer equipment, 701-7
Damp or wet locations, 410-4(a), 410-49
Lengths
Double-pole switched, 410-48
Busways used as branch circuits, 364-14
70-898
NATIONAL ELECTRICAL CODE
Free conductors at outlets and switches,
Electric discharge, see Electric discharge
300-14, 424-43, 426-23, 550-10(h)
lighting
Intermediate metal conduit, 345-16(a)
Fluorescent, see Fluorescent lighting
Nonmetallic flexible tubing with open
fixtures
wiring, 320-10
Flush, 410-M, 410-N
Nonmetallic rigid metal conduit, 347-17
Fountains, 680-51
Pull and junction boxes, 370-28, 370-71
Grounding, 410-E
Rigid metal conduit, 346-15(a)
Live parts, 410-3
Space heating cable, nonheating leads,
Location, 410-B
424-34
Motion picture studios, Art. 530
Taps, 210-19, 240-21
Mounting, 410-76, 410-77
10-ft. rule, 240-21 Ex. 2
No-niche, 680-20(d)
25-ft. rule, 240-21 Ex. 3
Definition, 680-4
25-ft. rule, transformers, 240-21 Ex. 8
Outdoors, 410-4(a)
100-ft. rule, 240-21 Ex. 10
Outlets required, 210-70
Motor feeders, 430-28, 430-53(d)
Overcurrent protection, wires and cords,
240-4
Life safety branch
Polarization, 410-23
Definition, 517-3
Raceways, 410-31
Essential electrical systems, 517-32,
Recessed, see Recessed lighting fixtures
517-42
Recreational vehicles, 551-53
Life support equipment, electrical
Show windows, 410-7
Definition, 517-3
Spas and hot tubs, 680-41(b)
Supports, 410-D
Lighting
Swimming pools, 680-20, 680-32
Branch circuits, calculation of load,
Theaters, Art. 520
220-3(b)
Wet, 410-4
Cove, 410-9
Wet-niche, 680-20(b)
Electric discharge, see Electric discharge
Definition, 680-4
lighting
Wiring, 410-F
Emergency, Art. 700
Lighting outlets, 210-70
Feeders, calculation of load, 220-10(a),
220-30
Lightning rods
Festoon, see Festoon lighting
As a ground, 250-86
Fixtures, see Lighting fixtures
Irrigation machines, 675-15
Outlets, 210-70
Spacing from, 250-46
Outline, see Outline lighting
Lightning (surge) arresters, Art. 280
Track, 220-3(c)(6) 410-R
Antenna discharge units, 810-20
Connections at services, 230-82 Ex. 4
Lighting assembly, cord- and plug-
Grounding, 250-46, 250-86, 280-25
connected, 680-56
Radio and television equipment
Definition, 680-4
Receiving stations (antenna discharge
Lighting fixtures, Art. 410; see also Hazunits), 810-20
ardous (classified) locations
Transmitting stations, 810-57
Arc, 520-61, 530-17
Services over 600 volts, 230-209
Autotransformers
Lightning (surge) protection, Art. 280
Ballasts supplying fluorescent fixtures,
Communication circuit conductors,
410-78
800-13
Supply circuits, 210-9
Hazardous (classified) locations, 501-17,
Auxiliary equipment, 410-77
502-17
Boxes, canopies, pans, 410-C
Lights, see also Lamps; Lighting
Branch circuits
Border, cables for, theaters, 520-44(b)
Computation of, 220-3(a), (b), and (c)
From railway conductors, 110-19
Sizes, 210-22, 210-23
Scenery, theaters, halls, 520-63
Voltages, 210-6, 410-73
Clothes closets, 410-8
Limited care facility
Definition, 410-8(a)
Definition, 517-3
Combustible material, near, 410-5, 410-76
Line isolation monitor, 517-160(b)
Connection, fluorescent, 410-14, 410-30
Definition, 517-3
Construction, 410-M, 410-N
Lint, flyings, Art. 503
Corrosive, 410-4(b)
Liquidtight flexible metal conduit, 351-A
Damp, wet, or corrosive locations,
Bends, 351-10
410-4, 410-49
Definition, 351-2
Dry-niche, 680-20(e)
Fittings, 351-7
Definition, 680-4
Grounding, 351-9
Ducts or hoods, in, 410-4(c)
Number of conductors in, 351-6
INDEX
70-899
Size, 351-5
Generators, 445-2
Supports, 351-8
Grounding connections at electrodes,
Use, 351-4
250-112
Liquidtight flexible nonmetallic conduit,
Hazardous, see Hazardous (classified)
351-B
locations
Bends, 351-30
Junction boxes, 370-19
Definition, 351-22
Lamps, outdoors, 225-25
Fittings, 351-26
Lighting fixtures, 410-B
Grounding, 351-27
Mobile homes disconnecting means and
Number of conductors in, 351-25
branch-circuit protective equip-
Size, 351-24
ment, 550-6
Splices and taps, 351-29
Motion picture projection equipment,
540-11
Supports, 351-27
Use, 351-23
Motor disconnecting means, 430-102
Motor feeder taps, 430-28
Listed
Motors, 430-14
Definition, Art. 100-A
Overcurrent devices, 240-B
Live parts, see also Enclosures; Energized
Panelboards, 384-17
parts; Guarding
Protective devices for communication
Appliances, 422-D
circuits, 800-30
Capacitors, 460-2
Recreational vehicle disconnecting means
Exposed, 110-16
and distribution panelboard,
Generators, 445-6
551-13(b)
Guarding, 110-17
Resistors and reactors, 470-2
Hazardous (classified) locations, 501-15,
Service disconnecting means, 230-70(a),
502-15, 503-15
230-72(c)
In theaters, 520-6
Service heads, 230-54
Lamp terminals and lampholders, 410-82
Service overcurrent protection, 230-91,
Lighting fixtures, lampholders, lamps,
230-92
receptacles, 410-3, 410-46
Sign switches, 600-2(a)
Lighting systems, electric discharge,
Splices and taps
410-P, 410-Q
Auxiliary gutters, 374-8(a)
Transformers, guarding, 450-8
Wireways, 362-7
Surge arresters, 280-11
Loads
Swimming pool junction box and trans-
Appliances, household cooking, demand
former enclosures, 680-21
table, 220-19
Switchboards, 384-5 thru 384-7
Branch circuits
Switches, 380-4
Calculations, Art. 220, Chap. 9 Part B
System grounding connections, 250-C
Maximum, 210-22, Table 210-24
Transformers and vaults, 450-1, 450-13
Mobile homes, 550-13
Ventilation openings for transformer
Permissible, 210-23, Table 210-24
vaults, 450-45(a)
Continuous, see Continuous loads
Wet, see Wet locations and Damp or wet
Demand
locations
Clothes dryers, 220-18
Household cooking appliances, 220-19
Locked rotor motor current
Farm, 220-40
Code letters, 430-7(b), Table 430-7(b)
Feeder, 220-B, Chap. 9 Part B
Conversion, Table 430-151
Calculations, Art. 220
Hermetic refrigerant motor-compressors,
Inductive, see Inductive loads
440-3(a)
Mobile home parks, 550-22
Locknuts, double, where required
Mobile homes, 550-13
Hazardous (classified) locations,
Motors, conductors, 430-B
501-16(a)
Stage equipment, circuit loads, 520-41
Mobile homes, 550-10(f)
Locations
Over 250 volts to ground, 250-76
Capacitors, 460-2(a)
Recreational vehicles, 551-47(b)
Crane and hoist disconnecting means,
Wholly insulated bushings used, 373-6(c)
610-D
Low-voltage circuits, see also Remote-
Damp or wet, see Damp or wet locations
control, signaling, and power-
Definition, Art. 100-A
limited circuits
Dry, see Dry locations
Definition, 551-2
Electric discharge lighting transformers,
Less than 50 volts, Art. 720
over 1000 volts, 410-86
Elevator motor disconnecting means,
Low-voltage equipment and instruments
620-51(b)
Definition, 517-2
Foreign pipes, accessories, transformer
Lugs
vaults, 450-47
Connection of service conductors, 230-81
70-900
NATIONAL ELECTRICAL CODE
Connection to terminals, 110-14(a)
Metal working machine tools and plastic
Solderless type at electrodes, 250-115
machinery, see Industrial machinery
Machine tools, see Industrial machinery
Metal-clad cable, Art. 334
Made electrodes, 250-83
Ampacity, 334-13
Mandatory rules, 90-5
Bends, 334-11
Conductors, 334-20
Manholes, 300-32 Ex. 2, 725-15 Ex. 2
Construction, 334-C
Manufactured buildings, Art. 545
Definition, 334-1
Bonding and grounding, 545-11
Fittings for, 334-12
Boxes, 545-9
Grounding, 334-23
Component interconnections, 545-13
Installation, 334-B
Definitions, 545-3
Marking, 310-11(b)(2) Ex. 3, 334-24
Grounding electrode conductor, 545-12
Supports, 334-10
Protection of conductors and equipment,
Through studs, joists, and rafters,
545-8
300-4(a)
Receptacle or switch with integral enclo-
Uses not permitted, 334-3
sure, 545-10
Uses permitted, 334-3
Service-entrance conductors, 545-5,
Voltages, 334-2
545-6
Service equipment location, 545-7
Metal-enclosed switchgear, see
Wiring methods, 545-4
Switchgear, metal-enclosed
Manufactured wiring systems, Art. 604
Metals
Construction, 604-6
Dissimilar, 110-14, 250-115, 345-3(a),
Definition, 604-2
346-1(b), 348-1
Unused outlets, 604-7
Ferrous, see Ferrous metals
Uses not permitted, 604-5
Meter socket enclosures, 373-1; see also
Uses permitted, 604-4
Cabinets, cutout boxes, and meter
Marinas and boatyards, Art. 555
socket enclosures
Feeders and services, 555-5
Meters
Gasoline dispensing stations, 555-9
Connection and location at services,
Grounding, 555-7
230-82 Ex. 3, 230-94 Ex. 5
Receptacles, 555-3
Branch circuits for, 555-4
Grounding of cases, 250-123, 250-124
Wiring methods for, 555-6
Grounding to circuit connector, 250-61(b)
Ex. 3
Over and under navigable water, 555-8
Hazardous (classified) locations, 501-3,
Markings, see articles on wiring and
502-14
equipment involved
Metric units of measurement, 90-9
Means of egress
Health care facilities, 517-32(a)
Mineral-insulated metal-sheathed
Illumination, 517-32(a), 517-42(a)
cable, Type MI, Art. 330
Mechanical execution of work, 110-12
Bends, 330-13
Medium voltage cable, Type MV,
Construction specifications, 330-C
Art. 326
Definition, 330-1
Ampacity, 326-6
Fittings, 330-14
Construction, 326-5
Supports, 330-12
Definition, 326-1
Terminating seals, 330-15
Marking, 326-7
Through or parallel to studs, joists, or
Uses not permitted, 326-4
metal rafters, 300-4, 330-11
Uses permitted, 326-3
Uses not permitted, 330-4
Uses permitted, 330-3
Messenger supported wiring, Art. 321
Definition, 321-1
Wet locations, 300-6(c), 330-10
Messenger support, 321-6
Mobile home parks, Art. 550
Splices and taps, 321-8
Definitions, 550-2
Uses not permitted, 321-4
Distribution system, 550-21
Uses permitted, 321-3
Electrical wiring system
Metal frame of building
Feeder and service demand factors,
Grounding electrode, 250-81(b)
550-5, 550-C, Table 550-22
Not permitted as equipment grounding
Minimum allowable demand factor,
conductor, 250-58(a)
550-22
Metal hood, stage switchboard, see
Mobile home service equipment,
Hood, Metal
550-23(a)
Metal outlet boxes, see Boxes, Metallic
Mobile homes, Art. 550
Accessory buildings or structures
Metal siding, grounding of, 250-44 (FPN)
Definition, 550-2
Metal wireways, see Wireways, metal
Appliances, 550-9
INDEX
70-901
Branch circuit protective equipment,
Circuits, 430-B
550-6(b)
Code letters, Table 430-7(b)
Branch circuits, 550-7
Coded and noncoded, setting of branch
Calculations of loads, 550-13
circuit devices, Table 430-152
Communications circuits, 800-41
Combined overcurrent protection, 430-55
Definitions, 550-2
Conductors, 430-B
Disconnecting means, 550-6(a)
Control circuits, 430-F
Expandable and dual units, wiring,
Controllers, see Controllers, Motor
550-14
Current, full load, see Full load current
Fixtures, 550-9
motors
General requirements, 550-4
Curtain, theater, 520-48
Ground-fault circuit interrupter, 550-8(b)
Disconnecting means, 430-H
Grounding, 550-11
Energized parts protection, 430-K
Heat tape outlet, 550-8(g)
Feeder demand factor, 430-26
Insulated neutral required, 550-11(a)
Feeders, calculation of load, 220-10,
Nameplates, 550-6(d)
220-30
Outdoor outlets, fixtures, air-cooling
Full-load current, see Full-load current
equipment, 550-15
motors
Power supply, 550-5
Fuseholder, size of, 430-57
Receptacle outlets, 550-8
General, 430-A
Service equipment
Ground-fault protection, 430-D, 430-E
Definition, 550-2
Grounding, 250-E, 430-L
Testing, 550-12
Grouped, 430-24, 430-42, 430-53, 430-87,
Wiring methods and materials, 550-10
430-112
Mobile X-ray equipment, 660-4(b)
Guarding, 430-133
Definition, 660-2
Hazardous (classified) locations, 501-8,
Module, solar voltaic systems
502-8, 503-6
Definition, 690-2
Highest-rated or smallest-rated, 430-17
Mogul base lampholders, 210-6, 410-53
Industrial machinery, Art. 670
Liquids, protection from, 430-11
Monorails, Art. 610
Location, 430-14
Motion picture and television studios,
Maintenance, 430-14
Art. 530
Marking, 430-7
Definitions, 530-2
Terminals, 430-9(a)
Dressing rooms, 530-C
Motor control centers, 430-H
Feeder conductors, sizing, 530-19
Multispeed, see Multispeed motors
Film storage vault, 530-E
Over 600 volts, 430-J
Grounding, 530-20
Overcurrent protection, 430-C
Lamps, 530-16, 530-17
Overheating, dust accumulations, 430-16
Live parts, 530-15
Overload protection, 430-C
Overcurrent protection, 530-18
Part winding, see Part winding motors
Stage or set, 530-B
Restarting, automatic, 430-43
Substations, 530-F
Short circuit protection, 430-D, 430-E
Wiring, 530-11, 530-12
Starting, shunting, 430-35
Motion picture projectors, see Projectors,
Tables, 430-M
Motion picture
Terminal housings, size, 430-12
Motion picture theaters, see Theaters
Terminals, 430-9
Motor home
Three running overload units, Table
Definition, 551-2
430-37
Motor-circuit switches, see Switches,
Ultimate trip current, 430-32(a)(2)
Motor-circuit
Ventilation, 430-14(a)
Welders, arc, motor-generator, 630-C
Motor-generator arc welders, 630-C
Wiring diagram, Diagram 430-1
Motors, Art. 430
Wiring space in enclosures, 430-10
Air conditioning units, Art. 440
Mounting of equipment, 110-13, 300-11,
Appliances, motor driven, 430-H
370-23, 380-10(b), 410-D
Branch circuits, 430-B
Combination loads, 430-25, 430-63
Moving walks, see Elevators, dumbwait-
Continuous duty, 430-22
ers, escalators, moving walks,
Intermittent duty, 430-22
wheelchair lifts, and stairway chair
lifts
Several motors, 430-24
Single motor, 430-22
Multioutlet assembly, Art. 353
Taps, 430-28 Ex., 430-53
Calculation of load, 220-3(c)
Torque motors, 430-52(b)
Definition, Art. 100-A
Wound rotor secondary, 430-23
Metal, through dry partitions, 353-3
Capacitor, 460-8, 460-9
Use, 353-2
70-902
NATIONAL ELECTRICAL CODE
Multiple circuit connections, grounding,
Uses not permitted, 342-4
250-62
Uses permitted, 342-3
Multiple conductors (conductors in par-
Nonmetallic pipelines, 427-23
allel), see Conductors, Multiple
Nonmetallic rigid conduit, see Rigid non-
Multiple fuses (fuses in parallel), 240-8,
metallic conduit
380-17
Definition, 100-B
Nonmetallic wireways, see Wireways,
nonmetallic
Multispeed motors
Nonmetallic-sheathed cable, 300-4(b),
Branch circuits, 430-22(a)
Art. 336
Locked-rotor code letters, 430-7(b)
Accessible attics, 336-13
Marking, 430-7
Bends, 336-14
Overload protection, 430-32(a) and (c)
Conductors, 336-26
Multiwire branch circuit, 210-4
Construction, 336-C
Definition, Art. 100-A
Definition, 336-1
Nameplates, see articles on wiring and
Devices with integral enclosures, 336-18
equipment involved
Exposed work, 336-10
Neat and workmanlike installation,
Installation, 336-B
110-12
Insulating devices, 336-16
Marking, 336-27
Neutral, see also Conductors, Grounded
Nonmetallic outlet boxes, 336-17
Bare, 230-22 Ex., 230-30 Ex., 230-41 Ex.
Supports, 336-15
Bonding to service equipment, 250-72(a)
Common, see Common neutral
Three floor limitation, 336-4(a)(1)
Conductor, Art. 310 Notes 3 and 10 of
Through or parallel to studs, joists,
Ampacity Tables 0-2000 volts,
rafters, 300-4(a), 336-11
Tables B-310-1 thru B-310-10
Unfinished basements, 336-12
Continuity of, 300-13
Uses not permitted, 336-4
Definition, Art. 100-A
Uses permitted, 336-3
Equipment, grounding to, 250-61
Nontamperable
Feeder load, 220-22
Circuit breakers, 240-82--
Grounding of
Type S fuses, 240-54(d)
AC systems, 250-5, 250-25, 250-26
DC systems, 250-3, 250-22
Number of services, 230-2
Identification, Art. 200
Nurses' stations
Ranges and dryers, grounding, 250-60
Definition, 517-3
Uninsulated, where permitted, 230-22
Nursing homes
Ex., 230-30 Ex., 230-41 Ex.,
Definition, 517-3
250-60(c), 338-3(b)
Essential electrical systems, 517-40
Nightclubs, Art. 518
Occupancy, lighting loads, Table
Nipples, conduit, see Conduit nipples
220-3(b), 220-3(c)
Noise, see Electrical noise
Office furnishings, Art. 605
Nonautomatic
General, 605-2
Definition, Art. 100-A
Lighting, 605-5
Partitions
Nonelectrical equipment, grounding,
250-44
Interconnections, 605-4
Fixed-type, 605-6
Nongrounding-type receptacles, replace-
Freestanding type, 506-7, 506-8
ments, see Receptacles,
Wireways, 605-3
Nongrounding type
Official interpretations, see Formal inter-
Nonincentive circuit
pretations
Definition, 100-A
Oil (filled) cutout
Nonmetallic boxes, see Boxes, Nonmetallic
Definition, 100-B
Nonmetallic conduit, preassembled
Open wiring on insulators, Art. 320
cable in, see Preassembled cable in
Accessible attics, 320-15
nonmetallic conduit
Ampacity, 320-5(b)
Nonmetallic extensions, Art. 342
Conductors, types permitted, 320-5(a)
Definition, 342-1
Definition, 320-1
Fittings, 342-6
Drip loops, 320-13
Installation
Flexible nonmetallic tubing, 320-10
As aerial cable, 342-7(b)
Passing through walls and floors, 320-11
As surface extensions, 342-7(a)
Separation from metal work and piping,
Marking, 342-8
320-12
Splices and taps, 342-5
Supports, 320-6, 320-7
INDEX
70-903
Switches, 320-16
Power
Tie wires, 320-8
Definition, Art. 100-A
Use permitted, 320-3
Receptacle
Openings in equipment to be closed,
Definition, Art. 100-A
110-12(a), 370-8, 373-4
Required, 210-C
Rooftop heating, air-conditioning, and
Operable, externally
refrigeration equipment, 210-63
Definition, Art. 100-A
Outline lighting, Art. 600
Operating rooms, hospital, 517-D
Definition, Art. 100-A
Emergency lighting system, Art. 700
Grounding, conductor size, 250-97
Optical fiber cables, Art. 770
Output circuits
Access to electrical equipment, 770-7
Amplifiers, 640-5
Cable trays, 770-6
Heat generating equipment, 665-44,
Cables
665-64
Application, 770-53
Marking, 770-50
Outside branch circuits and feeders,
Substitutions, 770-53
Art. 225
Definition, 770-3
Calculation of load
Fire resistance of, 770-49
Branch circuits, 220-3, 225-3(a)
Grounding of entrance cables, 770-33
Feeders, 220-B, 225-3(b)
Installation, 770-50, 770-52
Circuit entrances and exits, buildings,
Listing requirements, 770-50, 770-51
225-11(c)
Location, 770-2
Conductors
Marking, 770-50
Clearance
Optical fibers and electrical conductors,
From buildings, 225-19
770-52
From ground, 225-18
Raceway system, 770-5
Covering, 225-4
Types, 770-4, 770-6, 770-51
Size, 225-5, 225-6
Within buildings, 770-C
Disconnection, 225-8
Festoon supports, 225-13
Optional standby systems, Art. 702
Lighting equipment on poles or other
Capacity and rating, 702-5
structures, 225-7
Circuit wiring, 702-B
Location of outdoor lamps, 225-25
Definition, 702-2
Mechanical protection, 225-20
Equipment approval, 702-3
More than one building or structure,
Signals, 702-7
225-11
Signs, 702-8
Outdoor lampholders, 225-24, 225-25
Transfer equipment, 702-6
Overcurrent protection, 225-9
Organs
Point of attachment, 225-16
Electronic, 640-1
Spacing, open conductors, 225-14
Pipe, Art. 650
Supports
Conductors, 650-5, 650-6
Festoons, 225-13
Grounding, 650-4
Open conductors, 225-12
Installation of conductors, 650-6
Over buildings, 225-15
Overcurrent protection, 650-7
Vegetation, live, 225-26
Source of energy, 650-3
Wiring on buildings, 225-10
Outdoor receptacles, 210-8(a)(3),
Outside of buildings, when services
210-52(e), 410-57, 550-8(e), 680-6
considered, 230-6
Outlet boxes, see Boxes, Outlet
Ovens, wall-mounted, see also Cooking
Outlet spacing, dwelling baseboard
units; Ranges
Branch circuits, 210-19, 210-23
heaters, 210-52(a) Ex.
Connections, 422-17
Outlets
Definition, Art. 100-A
Appliance, 210-50(c)
Demand loads, Table 220-19
Definition, Art. 100-A
Grounding, 250-57, 250-60
Devices, branch circuits, 210-7
Over 600 volts, Art. 710
Discontinued
Ampacity, 310-15, 318-13
Cellular concrete floor raceways,
Binding, 300-34
358-13
Boxes, pull and junction, 370-D
Cellular metal floor raceways, 356-7
Busways, 364-B
Underfloor raceways, 354-7
Capacitors, 460-B
Laundry, 210-52(f), 220-3(c)
Circuit conductors, 710-32
Lighting, 210-70
Circuit interrupting devices, 710-21
Definition, Art. 100-A
Conductors, 110-B, 710-5
Multioutlet assembly, see Multioutlet
Definition, Art. 100-B
assembly
Electrode type boilers, 710-G
70-904
NATIONAL ELECTRICAL CODE
Elevation of unguarded live parts,
Fuses and fuseholders, 240-8, 240-E,
110-34(e)
240-F
Enclosure for electrical installations,
Generators, 445-4
110-31
Grounded conductor, 240-22
Equipment, 710-B, 710-C
Induction and dielectric heating equip-
Grounding, 300-36, 710-7
ment, 665-42
Headroom above working spaces, 110-32
Installation, 240-A
Illumination of working spaces, 110-34(d)
Interconnected electric power production
Indoor installations, 710-11
sources, 705-30
Insulation shielding, 710-6
Legally required standby systems, 701-D
Isolating means, 710-22
Lighting track, 410-103
Metal-enclosed equipment, 710-13,
Location, 230-91, 240-B
710-24
Mobile home, 550-6
Mobile and portable equipment, 710-E
Motion picture and television studios,
Moisture, mechanical protection, metal-
530-18, 530-63
sheathed cables, 710-8
Motors, motor circuits, controllers,
Oil-filled cutouts, 710-21(d)
430-C, 430-D
Outdoor installations, 710-12
Control circuits, 430-72
Overcurrent protection, 240-H, 710-20
Over 600 volts, 430-124, 430-125
Protection of equipment, 710-9
Multiple fuses and circuit breakers (in
Resistors and reactors, 470-B
parallel), 240-8, 380-17
Separation, 384-36, 710-33
Occupant access to, 240-24(b)
Services, 230-H
Organs, 650-7
Shielding solid dielectric-insulated con-
Outside branch circuits and feeders,
ductors, 310-6
225-9
Temporary, 305-5
Over 600 volts, 240-H, 460-25, 710-20,
Tray installations, Art. 318
710-42, 710-52
Tunnel installation, 710-F
Panelboards, 384-15; 384-16
Voltage regulators, 710-23
Paralleled fuses and circuit breakers,
Wiring methods, 300-B, 710-4
240-8, 380-17
Overcurrent
Recreational vehicles, 551-10(e), 551-43,
551-45
Definition, Art. 100-A
Remote-control circuits, 240-3 Ex. 1,
Devices, standard, 240-6
Art. 725
Overcurrent protection, Art. 240
Services
Air-conditioning and refrigerating equip-
Entrance conductor, 230-G
ment, 440-C
Over 600 volts, 230-208
Appliances, 422-28
Single appliance, 210-20
Branch circuits, 210-20
Solar photovoltaic systems, 690-9
Busways, 364-9 thru 364-13
Sound recording equipment, 640-10
Capacitors, 460-8(b)
Supplementary, 240-10
Circuit breakers, 240-8, 240-G
Switchboards, 384-2
Circuits less than 50 volts, 720-8
Television studios, see Motion picture
Circuits, remote control, signaling, and
and television studios
power-limited
Theaters, stage switchboards, 520-23,
Class 1 systems, 725-12
520-25(a), 520-52, 520-53, 520-62
Class 2 and Class 3 systems, 725-35,
Transformers, 450-3 thru 450-5
725-36
Vertical position, enclosures, 240-33
Communications systems, 800-12,
Welders, 630-12, 630-32
800-13, 800-C, 800-D
X-ray equipment, 517-73, 660-6
Cords, flexible and tinsel, 240-4, 400-13
Overhead spans, 225-6(a)
Cranes and hoists, 610-E
Overload
Current-limiting
Definition, 240-11
Definition, Art. 100-A
Disconnecting and guarding, 240-D
Panel, solar photovoltaic systems
Electric space heating equipment, 424-22
Definition, 690-2
Electroplating systems, 669-9
Panelboards, Art. 384, see also Hazard-
Elevators, dumbwaiters, escalators, movous (classified) locations
ing walks, wheelchair lifts, stairway
Bonding, 517-14
chair lifts, 620-G
Component parts, 384-33
Emergency systems, 700-F
Damp or wet locations, 384-17
Enclosures, 240-C
Definition, Art. 100-A
Feeder taps, 240-21, 430-28
Distribution
Fire protective signaling systems, 760-12,
Definition, Art. 100-A, 551-2
760-13, 760-23, 760-24
Enclosure, 384-18
Fixture wires, 240-4, 402-12
General, 384-13
Flexible cords, see Cords, Flexible
Grounding, 384-20, 517-19(d)
INDEX
70-905
Health care facilities, 517-14, 517-19(d)
Definition, 455-2
Lighting and appliance branch-circuit
Different types of, 455-B
Definition, 384-14
Disconnecting means, 455-8, 455-20
Number of overcurrent devices, 384-15
Grounding, 455-5
Overcurrent protection, 384-16
Marking, 455-4
Relative arrangement of switches and
Overcurrent protection, 455-7
fuses, 384-19
Power interruption, 455-22
Service equipment, 230-G, 230-H, 384-
Terminal housings, 455-10
3(c), 384-16(a)
Photovoltaic systems, see Solar
Spacing, minimum, 384-36
photovoltaic systems
Support for busbars and conductors,
384-3
Physical damage, see Protection, Physi-
Use as junction boxes, etc., 373-8
cal damage
Wire bending space, 384-35
Pipe, gas, see Gas pipe
Pans, fixture, 410-13
Pipe electrodes, 250-83(c)
Paralleled
Pipe organs, see Organs, Pipe
Alternate sources, 230-83 Ex. 2, Art. 705
Pipeline
Elevators, dumbwaiters, escalators, mov-
Definition, 427-2
ing walks, 620-12(a)(1) Ex.
Piping systems, bonding, 250-80
Power production sources, Art. 705
Places of assembly, see Assembly,
Paralleled circuit breakers and fuses,
places of
see Fuses, In parallel
Plants
Paralleled conductors, see Conductors,
Bulk storage, Art. 515
Parallel
Cleaning and dyeing, 500-4, Art. 501
Parts, see specific type such as Live parts
Clothing manufacturing, 500-6, Art. 503
Part-winding motors, 430-3
Woodworking, 500-6, Art. 503
Code letter markings, 430-7(b)(5)
Plate electrodes, 250-83(d)
Patching tables, motion picture, 530-D
Plenums, 300-22
Path, grounding, 250-51, 250-53
Definition, Art. 100-A
Wiring in, 300-22
Patient bed location
Definition, 517-3
Pliable raceways, see Raceways, Pliable
Plugging boxes, motion picture studios,
Patient care areas, 517-13(a), 517-80; see
530-14, 530-18(d)
also Health care facilities
Definition, 530-3
Definition, 517-3
Plugs, attachment, see Attachment plugs
Patient vicinity
Definition, 517-3
Polarity identification
Conductors, 310-12(a)
Pediatric and psychiatric locations,
Systems and circuits, Art. 200
517-18(c)
Polarization
Pendant conductors, lamps, 410-27
Appliances, 422-23
Pendants
Lighting fixtures, 410-23
Aircraft hangars, 513-4(b)
Plugs, receptacles, and connectors,
Anesthetizing locations, 517-61(b)(3)
200-10(c)
Ex. 2, 517-61(c)(1) Ex.
Portable handlamps, 410-42(a)
Bathrooms, 410-4(d)
Receptacle adapters, 410-58(b)(3)
Clothes closets, 410-8(c)
Screw-shell type lampholders, 410-47
Dressing rooms, theater, 520-71
Poles
Flexible cord, 400-7(a)
Climbing space, conductors, 225-14(d)
Garages, commercial, 511-6(b)
Conductors, mechanical protection,
Mobile homes, 550-9(c)
225-20, 230-50(b), 230-51
Receptacle cord, 210-50(a)
Supporting lighting fixtures, 410-15(b)
Periodic duty
Pool cover, see Covers, Pool, Electrically
Definition, Art. 100-A
operated
Permanent plaque or directory, 230-2,
Pools, see also Swimming pools, foun-
705-10
tains, and similar installations
Definition, 680-4
Permission, special
Definition, Art. 100-A
Portable appliances, see Appliances
Portable equipment
Person, qualified
Definition, 530-3
Definition, Art. 100-A
Disconnecting means, 517-72(c)
Phase converters, Art. 455
Double insulation, 250-45
Capacitors, 455-10
Generators, 250-6
Conductors, 455-6
Grounding, 250-45, 250-59
70-906
NATIONAL ELECTRICAL CODE
Grounding, conductor size, 250-95
Projectors, motion picture, 520-2, Art.
X-ray, 600-4(b)
540
Definition, 660-2
Definitions, 540-B
Portable handlamps, see Handlamps,
Grounding, 250-43(h)
Portable
Protection
Portable lamps, 410-42, 410-105, 516-3(d),
Combustible material, appliances, 422-10
530-16, see also Lamps, Portable
Corrosion
Portable stage equipment, see Stage
Boxes, metal, 370-40, 370-72
equipment, Portable
Conductors, 310-9
Portable switchboards, see Switch-
Electrical metallic tubing, 348-1
boards, Portable
General equipment, 300-6
Intermediate metal conduit, 345-3
Portable wiring, motion picture studios,
Metal-clad cable, 334-4
530-12
MI cable, 330-3, 330-4
Positive-pressure ventilation, see Venti-
Nometallic sheathed cable, 336-4(b)
lation, Positive-pressure
Rigid metal conduit, 346-1
Potheads, 230-202(f)
Underfloor raceways, 354-2
Power, emergency systems, see Emer-
Liquids, motors, 430-11
gency systems
Live parts, 110-17, 445-6, 450-8(c) and (d)
Motor overload, 430-C
Power and control tray cable, Type TC,
Overcurrent, see Overcurrent protection
Art. 340
Physical damage
Ampacity, 340-7
Armored cable, 333-6
Bends, 340-8
Construction, 340-3
Busways, 364-4(b)
Definition, 340-1
Conductors, 300-4, 710-3(b)(1)
Marking, 340-6
Electrical metallic tubing, 348-1
Uses not permitted, 340-5
Electrical nonmetallic tubing, 331-4
Uses permitted, 340-4
Lamps, electric discharge lighting,
410-90
Power conditioning unit, solar
Lighting track, 410-101(c)
photovoltaic systems
Liquidtight flexible metal conduit,
Definition, 690-2
351-4(b)(1)
Output circuit
Definition, 690-2
Liquidtight flexible nonmetallic conduit,
351-23(b)(1)
Power outlet, see Outlets, Power
Metal-clad cable, 334-3
Power production sources, see Intercon-
Mineral-insulated metal-sheathed cable,
nected electric power production
330-3
sources
Multioutlet assembly, 353-2
Power source, alternate
Nonmetallic-sheathed cable, 336-4
Definition, 517-3
Open conductors and cables, 230-50(b)
Power supply, mobile homes, 550-5
Open wiring, 320-10, 320-14
Overcurrent devices, 240-24(c)
Power supply assembly, recreational
Raceways, 300-5(d), 710-3(b)
vehicles, 551-42(d)
Recreational vehicle park underground
Definition, 551-2
branch circuits and feeders,
Power-limited tray cable, Type PLTC
551-80(b)
Class I, Division 2 locations, 501-4(b)
Resistors and reactors, 470-3
Class 3 circuits, 725-51(e)
Rigid nonmetallic conduit, 347-3(c)
Marking, 310-11
Shielded nonmetallic sheathed cable,
Preassembled cable in nonmetallic
337-5
conduit, Art. 343
Space heating systems, 424-12
Construction, 343-C
Surface raceways, 352-1, 352-22
Description, 343-1
Transformers, 450-8(a)
Installation, 343-B
UF cable, 339-3(a)(3)
Use, 343-3, 343-4
Underground installations, 230-49,
Premises wiring (system)
300-5(d)
Definition, Art. 100-A
Wireways, 362-2
Pressure connector, see Connector,
Protective devices, see Circuit breakers;
Pressure
Fuses; Overcurrent protection;
Prevention of fire spread, see Fire spread
Thermal cutouts
through walls, floors, etc.
Protective equipment, see Guarding and
Programmed power distribution, see
guards
Closed-loop and programmed
Public address systems, Art. 640
power distribution
Emergency lighting systems, 700-1 (FPN 3)
INDEX
70-907
Public assembly places, Art. 518
Underground, 300-5(c)
Emergency lighting system, Art. 700
Wireways, see Wireways
Pull boxes, see also Boxes; Junction
Wiring, exterior surfaces of buildings,
boxes
225-22
Accessibility, 370-29
Radio and television equipment, Art.
Construction specifications, 370-C,
370-72
810; see also Community antenna
television and radio distribution
Sizes
No. 4 and larger conductors, 370-28
system
No. 6 and smaller conductors,
Amateur transmitting and receiving sta-
370-16(c)
tions, 810-C
Over 600 volts, 370-71
Interior installation - transmitting stations, 810-D
Pumps, floating lake, 680-H
Receiving equipment - antenna systems,
Qualified person, see Person, Qualified
810-B
Raceways
Radiographic equipment, 660-23(a)
Bonding, 230-63, 250-G, 501-16(a),
502-16(a), 503-16(a)
Railway conductors, power and light,
Busways, see Busways
110-19
Cellular concrete floor, see Cellular con-
Rainproof
crete floor raceways
Definition, Art. 100-A
Cellular metal floor, see Cellular metal
floor raceways
Raintight
Conductors in service, 230-7
Definition, Art. 100-A
Continuity, 300-10, 300-12
Ranges, 422-17, 422-22(b), see also Cook-
Definition, Art. 100-A
ing units; Ovens
Drainage, 225-22, 230-53, 230-202(g)
Branch circuits
Electrical metallic tubing, see Electrical
Calculation of load, Table 220-19
metallic tubing
Conductors, 210-19
Emergency circuits, independent, 700-9
Expansion joints, 250-77, 300-7(b), 347-9
Maximum load, 210-22
Exposed to different temperatures, 300-7
Feeders; calculation of load, 220-10(a),
Fixtures as, 410-31
220-30
Flexible metal conduit, see Flexible
Grounding, 250-60
metal conduit
Loads, demand, Table 220-19
Flexible metallic tubing, see Flexible
Receptacles, 210-7, 250-60(d)
metallic tubing
Grounding, 250-D, 250-56
Rated load current, 440-4(a)
Definition 440-2
Short sections, 250-33 Ex. 2, 250-56
Induced currents, 300-20
Reactors, see Resistors and reactors
Insulating bushings, 300-16, 373-6(c)
Readily accessible, see Accessible,
Intermediate metal conduit, see Interme-
Readily
diate metal conduit
Liquidtight flexible metal conduit, see
Reaming, ends of metal conduits, 345-8,
Liquidtight flexible metal conduit
346-7, 348-11
Liquidtight flexible nonmetallic conduit,
Re-bar electrodes, 250-81(c)
see Liquidtight flexible nonmetallic
conduit
Receptacles, 410-L
Metal-trough, sound recording, 640-4
Anesthetizing locations, 517-64(f)
Number of conductors, 300-17
Branch circuits, 210-7, 210-52
Pliable, 331-1
Configurations, Figs. 550-5(c), 551-46(c)
Rigid metal conduit, see Rigid metal
Critical branch, 517-33(a)
conduit
Definition, Art. 100-A
Rigid nonmetallic conduit, see Rigid non-
Disconnecting means, 422-22, 440-63
metallic conduit
Secured, 300-11
Faceplates, 410-56(d)
Service, see Service raceways
Grounding type, 250-50(b) Ex., 250-74,
Signaling and power circuits, power-
410-58, 517-13, 517-19(g)
limited, 725-15, 725-16, 725-38(a)
Hazardous (classified) locations, 501-12,
Support for nonelectrical equipment,
502-13, 503-11
300-11
Health care facilities, 517-13, 517-18,
Supporting conductors, vertical, 300-19
517-19
Surface metallic, see Suface metallic
Insulated grounded terminals, 517-16
raceways
Less than 50 volts, 720-6, 720-7
Surface nonmetallic, see Surface nonme-
Marinas and boatyards, 555-3
tallic raceways
Maximum cord- and plug-connected load
Underfloor, see Underfloor raceways
to, Table 210-21(b)(2)
70-908
NATIONAL ELECTRICAL CODE
Minimum ratings, 410-56(a)
Power supply, 551-46
Mobile homes, 550-8
Splices and terminals, 551-50
Nongrounding-type, replacement, 210-7 Ex.
Definitions, 551-2
Outdoor, see Outdoor receptacles
Distribution panelboard, 551-45
Outlet
Expandable units, connection, 551-47(p)
Definition, Art. 100-A
Generator installations, 551-30
Outlets, where required, dwellings,
Ground-fault circuit-interrupter, 551-41(c)
210-52
Grounding, 551-54, 551-55
Patient bed location, 517-18(b), 517-19(b)
Grounding conductor splices, 551-50
Ratings for various size circuits, Table
Identification of grounded conductor,
210-21(b)(3)
551-49
Recreational vehicles, 551-52
Lighting fixtures, 551-53
Selected, health care facilities, 517-33(a)
Low voltage systems, 551-B
Definition, 517-3
Multiple supply source, 551-31
Show windows, in, 210-62
Outlet boxes, 551-48
Swimming pools, 680-6
Overcurrent protection
Branch circuit, 551-43
Temporary wiring, 305-4(c) and (d),
305-6
Distribution panelboard, 551-45
Low voltage wiring, 551-10(e)
Terminals, identification, 200-10
Power sources, other, 551-D
Theaters, 520-23, 520-45
Power supply assembly, 551-44, 551-46
Recessed lighting fixtures, 410-M
Receptacles, 551-20(f), 551-41, 551-52
As raceways, 410-11, 410-31
Switches, 551-51
Clearances, installation, 410-66
System voltages, 551-E
Construction, 410-N
Tags, labels, and marking, 551-46(d)
Temperatures, 410-65
Tests, factory, 551-F
Wiring, 410-67
Wiring methods, 551-10(c), 551-47
Recording systems, Art. 640
Refrigeration compressor motors and
Recreational areas, essential electrical
controls, Art. 440
systems, 517-42(e)
Refrigerators, grounding, 250-45
Recreational vehicle parks, 551-G
Regulator bypass switch
Calculated load, 551-73
Definition, 110-B
Demand factors, Table 551-73
Relays
Definitions, 551-2
Overload, motor overcurrent protection,
Disconnecting means, 551-76(b)
430-40
Distribution system, 551-72
Reverse-current, transformers, 450-5(b)
Ground-fault circuit-interrupter protec-
Remote-control, signaling, and powertion, 551-71
limited circuits, 250-43(i), Art. 725
Grounding, 551-75, 551-77
Class 1 circuits, 725-B
Outdoor equipment, protection of, 551-78
Circuits beyond one building, 725-19
Overcurrent protection, 551-74
Conductors, 725-16
Overhead conductors, 551-79
Different systems, 725-15
Receptacles, 551-71, 551-81
Insulation, 725-16(b)
Recreational vehicle site supply equip-
Number in raceways, 725-17
ment, 551-76
Overcurrent protection, 725-12
Underground wiring, 551-80
Size and use, 725-16(a)
Recreational vehicle site
Grounding, 725-20
Definition, 551-2
Location, 725-2, 725-13
Stand
Overcurrent protection, 725-12, 725-13
Definition, 551-2
Physical protection, 725-18
Power limitations, 725-11
Recreational vehicles (camping trailers,
Wiring methods, 725-14
motor homes, travel trailers,
Class 2 and Class 3 circuits, 725-C
truck campers), Art. 551
Applications of PLTC cables, 725-53
Appliance accessibility, 551-57
Circuits beyond one building, 725-42
Attachment plugs, 551-20(f), 551-46(c)
Conductors, 725-38, 725-42
Batteries, 551-10(d)
Fire resistance of cable, 725-49
Bonding, 551-56
Grounding, 725-43
Branch circuits, 551-42
Installation, 725-50, 725-52
Calculation for loads, 551-42(d)
Interconnection of power supplies,
Combination electrical systems, 551-C
725-32
Conductors, 551-10(b), 551-48
Location, 725-2
Connections
Marking, 725-34, 725-50
Grounding, 551-54, 551-55
Overcurrent protection, 725-35, 725-36
INDEX
70-909
Power limitations, 725-31, Tables 725-
Uses not permitted, 347-3
31(a) and (b)
Uses permitted, 347-2
Types of cable, 725-51
Road show connection panel, 520-50
Wiring methods
Load side, 725-38
Rod electrodes, 250-83(c)
Supply side, 725-37
"Romex", see Nonmetallic-sheathed cable
Classifications, 725-3
Room air conditioners, see Air condition-
Class 1 and Class 4, 725-11
ers, room
Class 2 and Class 3, 725-31
Communication cables, 725-5
Running threads, 345-9(b), 346-9(b)
Motors, 430-F
Safety, examination of equipment for,
Safety-control equipment, 725-4
90-7
Remote-control circuit, see Circuits,
Screw shells
Remote-control
Identification
Remote-control switches, 517-160(c)(4)
Polarity, 200-10(c), 410-23
Terminals, 200-10
Requirements for electrical installations,
Lampholders, 410-H
Art. 110
Sealable equipment
Residential occupancies, see Dwellings
Definition, Art. 100-A
Resistance
Sealing, conduit systems, 501-5, 502-5;
AC resistance and reactance, cables,
see also Hazardous (classified)
Chap. 9 Table 9
locations
Conductor properties, Chap. 9 Table 8
Intrinsically safe systems, 504-70
Insulation, 110-7
Temperature changes, 300-7(a)
Welders, 630-D
Underground services, 230-8.
Resistance to ground, made electrodes,
Secondary ties, transformers, 450-6
250-84
Separately derived systems, 250-5(d),
Resistors and reactors, Art. 470
250-26
Combustible material, on, near, 470-3
Definition, Art. 100-A
Conductor insulation, 470-4
Location, 470-2
Service cables, Art. 338
Over 600 volts, 470-B
Buildings, 230-51
Definition, Art. 100-A
Rheostats, construction specifications,
Installation, Art. 338
430-82(c)
Physical damage, 230-50
Rigid metal conduit, Art. 346
Service head, 230-54
Bends, 346-10, 346-11
Terminating, service equipment, 230-55
Boxes and fittings, 346-13
Underground, 230-C, 300-5
Bushings, 346-8
Service conductors, see Conductors,
Cinder fill, 346-3
Service
Construction specifications, 346-B
Couplings and connectors, 346-9
Service drops
Expansion joints, 300-7(b)
Clearances, 230-24
Minimum size, 346-5
Connections, service head, 230-54
Number of conductors, 346-6, Chap. 9
Definition, Art. 100-A
Table 1
Means of attachment, 230-27
Reaming ends, 346-7
Minimum size, 230-23
Splices and taps, 346-14
Number, 230-2, 230-21
Supports, 346-12
Point of attachment, 230-26; 230-28
Use, 346-1
Supports over buildings, 230-29
Wet locations, 346-4
Termination, 230-24, 230-26, 230-28
Rigid nonmetallic conduit, Art. 347
Service equipment
Bends, 347-13, 347-14
Definition, Art. 100-A
Boxes and fittings, 347-15, 370-13
Service lateral
Bushings, 347-12
Definition, Art. 100-A
Construction specifications, 347-17
Service loads, calculations, Art. 220
Description, 347-1
Expansion joints, 300-7(b), 347-9
Service raceways
Joints, 347-6
Conductors, others permitted in, 230-7
Minimum size, 347-10
Drainage, raintight, 230-53, 230-202(g)
Number of conductors, 347-11
Grounding and bonding, 230-63
PVC Schedule 80, 300-5(d), 551-80(b),
Service head, 230-54
710-3(b)(1)
Terminating at service equipment, 230-55
Splices and taps, 347-16
Underground, 230-C
Supports, 347-8, Table 347-8
Service stations, gasoline, see Gasoline
Trimming ends, 347-5
dispensing and service stations
70-910
NATIONAL ELECTRICAL CODE
Service-entrance cable, Type SE, USE,
Ground-fault protection, 230-95
Art. 338
Insulation, 230-22, 230-23
Branch circuits or feeders, 338-3
Number, 230-2
Definition, 338-1
Over 600 volts, 230-H
Grounding frames of ranges and clothes
Supply to one building through another,
dryers, 250-60(c)
230-3
Installation methods, interior, 338-4
Two or more buildings, 250-24
Marking, 338-5
Underground, 230-C
Service-entrance conductors, Art. 230-D,
Setting (of circuit breaker)
338-2
Definition, Art. 100-A
Underground, 338-1(b)
Use, 338-1 thru 338-3
Shafts, wiring, in, 725-38(a)(4)
Service-entrance conductors, 230-D,
Shielded nonmetallic-sheathed cable,
338-2
Type SNM, Art. 337
Conductor sets, number of, 230-40
Bends, 337-4
Considered outside of building, 230-6
Bonding, 337-7
Definitions, Art. 100-A
Construction, 337-8
Disconnecting means, 230-F
Definition, 337-1
Drip loops, 230-52
Fittings, 337-6
Insulation, 230-41
Handling, 337-5
Over 600 volts, 230-H
Marking, 337-9
Overcurrent protection, 230-90, 230-91,
Uses permitted, 337-3
230-208
Shielding, see Guarding, guards
Physical damage, 230-49, 230-50
Short-circuit withstand rating
Service head, 230-54
Definition, 430-83
Size, 230-42
Splices, 230-46
Short-time duty
Underground, 230-49
Definition, Art. 100-A
Wiring methods, 230-43
Show cases, wall cases, 410-29
Service-entrance equipment
Show windows
Disconnecting means, 230-F
Definition, Art. 100-A
Connections, ahead of, 230-82
Flexible cords, 400-11
Connections to terminals, 230-81
Lighting fixtures, 410-7
Disconnection of grounded conductor,
Branch circuits, 220-3(c)
230-75
Feeders, 220-10(a), 220-12
Electrically operated, 230-94 Ex. 6
Receptacles, 210-62, 370-17(b) Ex.
Externally operable, 230-78
Signs, 600-34(e)
Ground-fault, protection at, 230-95,
Sidelights, borders and proscenium,
705-32
520-44
Indicating, 230-77
Location, 230-70(a)
Signaling circuits, see also Fire protec-
Marking, 230-66, 230-70(b)
tive signaling systems; Remote-
Maximum number of disconnects, six
control, Signaling and powerswitch rule, 230-71
limited circuits
Multiple occupancy buildings, 230-72(c)
Definition, Art. 100-A
Over 600 volts, 230-205, 230-206
Health care facilities, 517-F
Rating, 230-79
Installation requirements, Art. 725
Simultaneous openings, 230-74
Signals for heated appliances, 422-12
Six switch rule, 230-71
Signs
Suitable for use, 230-70(c)
Electric, Art. 600
Transfer equipment, 230-83
Definition, Art. 100-A
Grounding, bonding, guarding, 230-62,
Over 1000 volts, 600-C under 1000
230-63, 230-62
volts, 600-B
Overcurrent protection, 230-G
Exit, health care facilities, 517-32(b),
Location, 230-91, 230-92
517-42(b)
Over 600 volts, 230-208
Discharge, lighting, electric, 410-P,
Relative location, 230-94
410-Q
Specific circuits, 230-93
Grounding, 250-43(g)
Ungrounded conductors, 230-90(a)
Mandated standby, 701-9
Panelboards as, 384-B
Outline lighting, Art. 600
Service-point (over 600 volts), 230-200
Size of conductors, 600-21(b), 600-31(b)
Definition, Art. 100-A
Standby, 702-8
Services, Art. 230
Warning, see Warning signs
Definition, Art. 100-A
Snap switches
Emergency systems, 700-12(d)
Accessibility, grouping, 380-8
Farm, 220-40
Definition, Art. 100-A
INDEX
70-911
Motors, 430-83, 430-109
Open wiring, 320-6
Panelboards, 384-16(b), 384-19
Space heating cables, 424-40
Ratings, 380-14
Surface raceways, 352-7
Snow melting, see Fixed outdoor electric
Underfloor raceways, 354-6
deicing and snow-melting equipment
Underground, 300-5(e)
Wireways, 362-7
Solar cell
Definition, 690-2
Spray, application, dipping, and coating
processes, Art. 516
Solar photovoltaic systems, Art. 690
Classification of locations, 516-2
Circuit sizing and current, 690-8
Equipment, 516-3 thru 516-5, 516-7
Connection to other sources, 690-G
Powder coating, 516-6
Definitions, Art. 100-A, 690-2
Spray washers 422-8(d)(3)
Disconnecting means, 690-C
Wiring, 516-3, 516-7
Grounding, 690-E
Installation, 690-4
Spread of fire or products of combustion, see Fire spread
Marking, 690-F
Maximum voltage, 690-7
Stage equipment, theaters
Overcurrent protection, 690-9
Fixed, 520-C
Storage batteries, 690-H
Portable, 520-E
Wiring methods, 690-D
Stages, motion picture and television,
Solderless (pressure) connector, see
530-B
Connectors, Pressure (solderless)
Switchboards, 520-B, 520-D
Sound recording equipment, Art. 640
Stairway chair lifts, see Elevators, dumb-
Motion picture projectors, 540-50
waiters, escalators, moving walks,
Theaters, 520-3
wheelchair lifts, and stairway chair
lifts
Space
Stand-alone system
Cabinets and cutout boxes, 373-7, 373-9,
Definition, 690-2
373-11
Climbing, see Climbing space
Standby systems, see Emergency sys-
Lightning rods, conductor enclosures,
tems; Legally required standby sysequipment, 250-46, 250-86
tems; Optional standby systems
Outside branch circuits and feeders,
Steel siding, 250-44 (FPN)
225-14
Storage batteries, Art. 480
Over 600 volts, separation, 110-33,
Aircraft hangars, 513-9
230-202(d)
Charging equipment, 503-14
Service conductors, 230-51(c)
Definition, 480-2
Working, see Working space
Emergency systems, 700-12(a) and (f)
Space heating, fixed, see Fixed electric
Garages, 511-8
space heating equipment
Insulation, 480-5, 480-6
Locations, 480-8
Spacing between bare metal parts, Table
Racks and trays, 480-7
384-26
Recreational vehicles, 551-5
Spas and hot tubs, 680-D
Solar photovoltaic systems, 690-H
Indoor installations, 680-41
Sound recording equipment, 640-9
Outdoor installations, 680-40
Vents, 480-9
Protection, 680-42
Submersible equipment, 680-51
Special permission, see Permission, Special
Substations
Splices and taps
Motion picture and television studios,
Antennas, 810-14
530-F
Auxiliary gutters, 374-8
Over 600 volts, 710-24
Cabinets and cutout boxes, 373-8 Ex.
Subsurface
Cellular concrete floor raceways, 358-12
Enclosures, 110-12(b)
Cellular metal floor raceways, 356-6
Supports, see articles on wiring and
Concealed knob-and-tube, 324-12
equipment
Conduit bodies, 370-6(c)
Suppressors, radio noise, 810-4
Construction sites, 305-4(g)
Surface metal raceways, 352-A
Deicing and snow-melting, 426-24(b)
Combination, 352-6
Electrical metallic tubing, 348-14
Conductors, 352-3, 352-4
Flat cable assemblies, 363-9, 363-10
Extension through floors and walls, 352-5
Flexible cords, 400-9
General and installed, 352-8
General provisions, 110-14
Grounding, 352-9
Messenger supported wiring, 321-8
Splices and taps, 352-7
Nonmetallic extensions, 342-5
Use, 352-1
70-912
NATIONAL ELECTRICAL CODE
Surface nonmetallic raceways, 352-B
Wet locations, 384-6
Combination, 352-26
Working spaces about, 110-16, 384-4
Conductors, 352-24, 352-25
Switches, Art. 380; see also Hazardous
Description, 352-21
(classified) locations; specific types
Extension through walls and floors,
of switches
352-28
Accessibility and grouping, 380-8
General, 352-27
Splices and taps, 352-29
AC general use snap switch, 380-14(a)
Use, 352-22
AC-DC general use snap switches, see
AC-DC general use snap switches
Surfaces, exposed conductive
Air-conditioning and refrigerating equip-
Definition, 517-2
ment, 440-B
Surge arresters, see Lightning (surge)
Appliances, 422-25
arresters
Bypass isolation
Surge protection, see Lightning (surge)
Definition, Art. 100-A
protection
Circuit breakers used as, 240-83(d)
Definitions, Art. 100-A
Swimming pools, fountains, and similar
Devices over 600 volts
installations, Art. 680
Definition, 100-B
Approval of equipment, 680-2
Bonding, 680-22
Disconnecting means
Ceiling fans, 680-6
Appliances, 422-D
Cord- and plug-connected equipment,
Motors, controller, 430-H
680-7
Services, 230-F
Deck area heating, 680-27
Emergency systems, 700-E
Definitions, 680-4
Heat generating equipment, 665-47
Floating lake pumps, 680-H
X-ray equipment, 517-72, 660-B
Ground-fault circuit-interrupters, 680-5
Enclosures, installation in, 450-8(c)
Fountains, 680-51
Essential electrical systems, 517-41(b)
Hydromassage bathtubs, 680-70
General use, Art. 380
Junction boxes for, 680-21
Definition, Art. 100-A
Receptacles, 680-6
Identification, 110-22
Spas, hot tubs, 680-40
Interrupter
Storable pool wiring, required for,
Definition, 100-B
680-31
Isolating
Therapeutic pools, 680-62
Definition, Art. 100-A
Wiring to, 680-21(b)
Motors over 100 HP, 430-109 Ex. 4
Grounding, 680-24, 680-25
Services over 600 volts, 230-204
Hydromassage bathtubs, 680-G
Knife, see Knife switches
Junction boxes and enclosures, 680-21
Limit, cranes and hoists, 610-33
Lighting, 680-6
Manually operable, Art. 380
Overhead conductor clearances, 680-8
Mobile homes, fixtures and appliances,
Permanently installed, 680-B
550-9(e)
Receptacles, location and protection,
Motor circuit
680-6
Definition, Art. 100-A
Spas and hot tubs, 680-D
Motor controllers, 430-G
Storable, 680-C
Panelboards, 384-16(b), 384-19
Switching devices, 680-6
Regulator bypass, see Regulator bypass
Therapeutic pools and tubs, 680-F
switch
Transformers, 680-5, 680-20(a)(1), 680-
Service, 230-F
21(b)
Signs, outline lighting, 600-2, 600-35
Underwater audio equipment, 680-23
Snap, see Snap switches
Underwater lighting fixtures, 680-20
Theater dressing rooms, 520-73
Switchboards, Art. 384
Transfer
Clearances, 110-16, 384-7, 384-8
Definition, Art. 100-A
Conductor insulation, 384-9
Unit, appliances, 422-25
Construction specifications, 384-C
Definition, Art. 100-A
Switchgear, metal-enclosed, 230-202(h),
Easily ignitable materials, near, 384-7
230-208, 710-9, 710-24
Grounding frames, 384-11
Tables, Chap.9, App. B
Grounding instruments, 384-12
AC resistance and reactance cables,
Guarding live parts, 110-17
Chap. 9, Table 9
Illumination, 110-16(e)
Ampacities
Location, 384-3, 384-5 thru 384-7
Cable, IGS, Table 325-14
Portable, theater stages, 520-D
Cable insulated, over 2000 volts
Stage, 520-B
Three conductor aluminum in isolated
Support, busbars, conductors, 384-3
conduit in air, Table 310-76
INDEX
70-913
Three conductor aluminum in under-
Wound-rotor secondaries, Table 430-23(c)
ground electrical ducts, Table
Bare metal parts, spacings between
310-80
switchboard and panelboard, Table
Three conductor aluminum isolated in
384-26
air, Table 310-72
Branch-circuit requirements, Table
Three conductor copper in under-
210-24
ground electrical ducts, Table
Cable markings, Tables 725-50, 760-19,
310-79
760-50, 770-50, 800-50, 820-50
Three conductor copper isolated in
Cable substitutions, Table 760-53
air, Table 310-71
Cable trays, grounding, Table 318-7(b)(2)
Triplexed or three single conductor
Cable fill, Tables 318-9, 318-10
aluminum in underground electrical
ducts, Table 310-77
Calculation of feeder loads by occupancies, Table 220-11
Triplexed or three single conductor
Conductors
aluminum in isolated conduit in air,
Table 310-74
Application, Tables 310-13, 310-61,
402-3
Triplexed or three single conductor
copper in isolated conduit in air,
Clearances, services, Table 230-51(c)
Table 310-73
Deflection, minimum bending space in
Conductor, single insulated, isolated in
cabinets, cutout boxes, Tables
air, over 2000 volts
373-6(a), 373-6(b)
Dimensions
Aluminum, Table 310-70
Copper, Table 310-69
Aluminum building wiring, Chap. 9
Table 5A
Conductors, three single insulated in
underground electrical ducts, over
Asbestos-varnished-cambric, Chap. 9
Table 7
2000 volts, Table 310-78
Crane and hoist motor conductors,
Lead-covered, Chap. 9 Table 6
Table 610-14(a)
Rubber, thermoplastic-covered,
Fixture wire, Table 402-3
Chap. 9 Table 5
Flexible cord, Table 400-4
Fire protective signaling systems,
General conductors, 0 through 2000 volts
Table 760-51
Aluminum, copper, or copper-clad
Fixture wires, Chap. 9, Table 402-3
aluminum in raceways or cables
Flexible cords and cables, types, Table
types AC, NM, NMC SE, Tables
400-4
310-16, 310-18
Grounding, size
Aluminum, copper, or copper-clad
For AC equipment, Table 250-95
aluminum, single conductor in free
For grounded systems, Table 250-94
air, Tables 310-17, 310-19
Insulations, Tables 310-13, 310-61 thru
Bare or covered conductors, Table
310-63
B-310-4
Maximum number, Chap. 9, Tables 3A
Multiconductor cables, types TC,
thru 3F
MC, MI, and SNM in free air,
Number in metal boxes, Table 370-6(a)
Table B-310-3
Over 600 to 35,000 volts
Three conductor cable in raceway in
Ampacities, Tables 310-81 thru
free air, Table B-310-1
310-84
Three insulated conductors in cable
Shielding, solid dielectric-insulated
in underground electrical ducts,
conductors, Table 310-64
Table B-310-6
Varnished cambric, multiple-
Three single insulated conductors
conductor cables, Table 310-66
directly buried in earth, types UF,
Varnished cambric, single-
USE, Table B-310-10
conductors, Table 310-65
Three single insulated conductors in
Support, vertical raceways, 300-19(a)
nonmagnetic underground electrical
Volume required per conductor,
ducts, Table B-310-5
Table 370-6(b)
Three single insulated conductors in
Conduit or tubing
underground electrical ducts, Table
Combination of conductors, percent
B-310-7
area fill, Chap. 9 Table 1
Three triplexed single insulated con-
Dimensions, Table 325-22, Chap. 9
ductors directly buried in earth (UF
Table 4
and USE cables), Table B-310-9
Expansion characteristics, Chap. 9,
Two or three insulated conductors
Tables 10 and 11
cabled within an overall covering
Flexible metal (g in.), Table 350-3
directly buried in earth, Table
Number of conductors in, Chap. 9
B-310-8
Tables 1, 2, 3A, 3B, 3C
Two or three single insulated Con-
Radius of bends, rigid metal conduit,
ductors supported on a messenger,
Table 346-10
Table B-310-2
Supports, Tables 346-12, 347-8
70-914
NATIONAL ELECTRICAL CODE
Cooking appliances, demand factors and
Transformers, medium and high voltage,
loads, Tables 220-19, 220-20
Tables 450-3(a)(1), 450-3(a)(2)(b)
Farm load, method for computing,
Tamperability
Tables 220-40, 220-41
Circuit breakers, 240-82
General lighting unit loads by occupan-
Type S fuses, 240-54(d), 550-6
cies, Table 220-3(b)
Household clothes dryers, demand loads,
Tamperproof receptacles, see Recepta-
Table 220-18
cles, Tamperproof
Household ranges and similar cooking
Taps, see also Splices and taps
appliances, demand loads, Table
Branch circuit, 210-19
220-19
Busways, 364-12 Ex. 1
Integrated gas spacer cable
Feeders, see Feeders, Taps
Ampacity, Table 325-14
Overcurrent protection, 240-21
Conduit dimensions, Table 325-22
Service-entrance conductors, 230-46
Minimum radius of bends, Table 325-11
Task illumination, 517-33(a)
Paper spacer thickness, Table 325-22
Definition, 517-3
Live parts, separation
Over 600 volts
Telegraph systems, see Communication
circuits
Air separation, indoors, Table 710-33
Elevation, Table 110-34(e)
Telephone equipment, 800-51(i); see also
Working space, Table 110-34(a)
Communication circuits
Working clearances, Table 110-16(a)
Telephone exchanges, circuit load,
Minimum radius of bend, IGS cable,
220-3(c) Ex. 4
Table 325-11
Minimum size of conductors, Table 310-5
Telephone systems, see Communication
Minimum wire bending space, Tables
circuits
373-6(a) and (b)
Television and radio distribution sys-
Mobile home park demand factors, Table
tems, see Community antenna tele-
550-22
vision and radio distribution
Motors
systems
Controller enclosure selection, Table
Television equipment, see Radio and tele-
430-91
vision equipment
Full-load currents, Tables 430-147 thru
430-150
Television studios, Art. 520, Art. 530
Locked-rotor, code letters, Table
Temperature limitations
430-7(b)
Conductors, 310-10
Locked-rotor current conversion,
In outlet boxes for fixtures, 410-11
Table 430-151
Nonmetallic raceways and tubing, see
Marking on motors, 430-7(a) and (b)
Raceway of tubing type
Maximum rating or setting, branch
Service-entrance cable, 338-3(c)
circuit protective devices, Table
430-152
Temporary wiring, Art. 305
Number and location, overload units,
Branch circuits, 305-4(c)
Table 430-37
Disconnecting means, 305-4(e)
Terminal, spacing and housing, Tables
Feeders, 305-4(b)
430-12(b) and (c)
Grounding, 305-5
Multifamily dwellings, optional calcula-
Guarding over 600 volts, 305-7
tion demand factors, Table 220-32
Lamp protection, 305-4(f)
Optional load calculations, one family
Receptacles, 305-4(d), 305-6
residences, Tables 220-30, 220-31
Services, 305-4(a)
Time constraints, 305-3
Overcurrent protective device, maximum
rating, Table 430-72(b)
Terminal housing, grounding through
Paper spacer thickness, IGS cable, Table
motor, 430-145(a)
325-21
Terminals
Radio and TV equipment, antenna sizes
Connections to, 110-14, 250-112, 250-113
Amateur stations, Table 810-52
Electric discharge tubing, signs, etc.,
Receiving stations, Table 810-16(a)
600-34
Rating factors for power resistors, Table
Flat conductor cable, 363-20
430-29
Identification
Receptacle loads, nondwelling units,
Fire protective signaling system, 760-4
Table 220-13
Motors, controllers, 430-9
Recreational vehicle park demand fac-
Polarity, 200-9 thru 200-11
tors, Table 551-73
Wiring device, 250-119
Restaurants, optional method load calculation, Table 220-36
Tests
Schools, optional method load calcula-
Emergency systems, 700-4
tion, Table 220-34
Ground-fault protection, 230-95(c)
INDEX
70-915
Insulation resistance, space heating
1000 volts or less, 410-P
cables, 424-45
More than 1000 volts, 410-Q
Legally required standby systems, 701-5
Instrument, grounding, 250-L
Lighting fixtures, 410-45
Connections at services, 230-82 Ex. 4
Mobile homes, 550-12
Isolation
Recreational vehicles, 551-60
Anesthetizing locations and patient care
Theaters, Art. 520
areas, 517-19(f), 517-20, 517-63(a)
Arc lamps, 410-55
Definition, 517-3
Dressing room, 520-F
Less-flammable liquid-insulated, 450-23
Emergency lighting systems, Art. 700
Location, 450-13
Grounding, 520-G
Modification of, 450-28
Fixed electric equipment, 250-43(f)
Motor control circuit, 430-72(c)
Overcurrent protection, 450-3
Stage equipment
Power-limited and signaling circuits,
Fixed, 520-C
remote control, 725-11(a)(1), 725-31
Portable, 520-E
Switchboard
Remote control circuits for, 430-74(b),
725-11, 725-31
Fixed, 520-B
Research and development, 450-1 Ex. 8
Portable, 520-D
Signs and outline lighting, 600-32
Therapeutic equipment, 517-73(b)
Special provisions, 450-B
Therapeutic high-frequency diathermy
Two-winding, underwater lighting,
equipment
680-5(a)
Vaults, 450-C
Definition, 517-3
X-ray equipment, 517-76, 660-C
Therapeutic pools and tubs, 517-90(c),
Transmitting stations, radio and televi-
680-4, 680-F
sion, 810-C
Thermal cutouts
Travel trailer
Definition, Art. 100-A
Definition, 551-2
Disconnecting means, 240-40
Trays, storage batteries, 480-7(b)
Thermal devices
Trees, lighting fixtures supported by,
Overcurrent protection, 240-9
410-16(h)
Thermal protector
Truck camper
Definition, Art. 100-A
Definition, 551-2
Thermal resistivity, B-310-15(b)(2)
Tubing, see also Conduit
Electric discharge, signs, etc., 600-33,
Thermally protected (thermal protection)
600-34
Definition, Art. 100-A
Electrical metallic, see Electrical metallic
Fixtures, recessed, 410-65(c)
tubing
Fluorescent lamp ballasts in fixtures,
Electrical nonmetallic, see Electrical
410-73(e)
nonmetallic tubing
Three overload units, motors, Table
Flexible metallic, see Flexible metallic
430-37
tubing
TV, see Television
Tools
Double insulated, 250-45(b) Ex. 3
Underfloor raceways, Art. 354
Metal working machine, see Industrial
Conductors, 354-4, 354-5
machinery
Connections to cabinets, wall outlets,
354-15
Motor-operated, hand-held, grounding,
250-45(c)
Covering, 354-3
Dead ends, 354-10
Trailers, types of
Discontinued outlets, 354-7
Definition, 551-2
Inserts, 354-14
Transfer switch
Junction boxes, 354-13
Definition, Art. 100-A
Laid in straight lines, 354-8
Markers, where required, 354-9
Transformer vaults, 450-C
Splices and taps, junction boxes, 354-6
Transformers, Art. 450; see also Hazard-
Use, 354-2
ous (classified) locations
Underground circuits, communication,
Arc welders, 630-B
800-11
Autotransformers, 450-4, 450-5
Underground enclosures, 110-12(b)
Capacitors, 460-2
Underground feeder and branch circuit
Installation, Art. 450
cable, Type UF, Art. 339
X-ray equipment, 517-148, 660-C
Ampacity, 339-5
Definitions, 450-2
Description and marking, 339-1
Dry-type, 450-21, 450-22
Overcurrent protection, 339-4
Electric discharge lighting systems
Use, 339-3
70-916
NATIONAL ELECTRICAL CODE
Underground wiring, see also Hazardous
Drop
(classified) locations
Branch circuits, 210-19(a)(FPN)
Buried conductors, Types USE, UF,
Conductors sized to prevent, 310-
338-1(b), 339-3
15(b)(FPN)
Conductor types in raceways, 310-8
Feeders, 215-2(FPN)
Intermediate metal conduit, 345-3
Electric discharge lighting, 410-P, 410-Q
Liquidtight flexible metal conduit, 351-4
General provisions, 110-4
Minimum cover requirements, 300-5(a)
Ground to
Over 600 volts, 710-3(b)
Definition, Art. 100-A
Rigid metal conduit, 346-1
High
Rigid nonmetallic conduit, 347-2
Definition, 710-2
Services, 230-30, 230-41
Less than 50, Art. 720
Splices and taps, 300-5(e)
Limitations, elevators, dumbwaiters,
Swimming pools, 680-10
escalators, moving walks, 620-2
Wet locations, 310-8
Marking, 240-83(e)
Nominal
Uninterruptible power supplies (UPS),
645-11
Definition, Art. 100-A
Nominal battery
Unit equipment, emergency and standby
Definition, 480-2
systems, 700-12(f), 701-11(f)
Over 600 volts, Art. 710
Unused openings
Swimming pool underwater lighting fixtures, 680-20
Boxes and fittings, 110-12, 370-18
Cabinets and cutout boxes, 373-4
Wiring methods, 300-2
Utilization equipment
Wading pools
Definition, 680-4
Definition, Art. 100-A
Wall or show cases, see Show cases, wall
Vapors, flammable, see Hazardous (clascases
sified) locations
Wall-mounted ovens, see Ovens, Wall-
Varying duty
mounted
Definition, Art. 100-A
Warning signs (labels), at equipment
Vaults
Aircraft hangars, 513-6 thru 513-11
Capacitors, 460-2
Electroplating, 669-7
Film storage, 530-E
Electrostatic hand spraying, 516-5(c)
Service over 600 volts, 230-208, 110-31,
Guarding live parts 600 volts or less,
710-31
110-17(c)(FPN)
Service 600 volts or less, 230-6
Induction and dielectric heating, 665-23
Transformers, 450-C
Locked room or enclosure with live parts
over 600 volts, 110-34(c), 710-
Vehicles
Electric, charging, 511-8
21(c)(2), 710-24(o)(2), 710-43, 710-45
Services over 600 volts, 230-203
Recreation
Definition, 551-2
Transformers, 450-8(d)
Water heaters, 422-14
Ventilated
Nameplate load, 220-32(c)(3)
Definition, Art. 100-A
Protection, 422-14
Ventilating ducts, wiring, 300-21, 300-22
Water pipe
Ventilating piping for motors, etc., 502-9,
As grounding electrode, 250-81(a)
503-7
Bonding (metal), 250-80(a)
Ventilation
Connections, 250-112, 250-113
Aircraft hangars, 513-2(d)
Water pumps, 547-8(d)
Battery locations, 480-8
Watertight
Equipment, general, 110-13(b)
Definition, Art. 100-A
Motors, 430-14(a), 430-16
Positive-pressure, 500-2 Ex., (FPN No. 2)
Weatherproof
Transformers, 450-9, 450-45
Definition, Art. 100-A
Vessel, fixed electric heating equipment for
Welders, electric, Art. 630
Definition, 427-2
Definition, Art. 100-A
Motor-generator arc, 630-C
Viewing tables, motion picture, 530-D
Resistance, 630-D
Volatile flammable liquid
Transformer and rectifier arc, 630-B
Definition, Art. 100-A
Welding cable, 630-E
Voltage and volts
Well casings, metal, 547-8(d)
Branch circuits, limits, 210-6
Wet locations, see also Damp or wet
Circuit
locations
Definition, Art. 100-A
Conductors, types, 310-8, Table 310-13
INDEX
70-917
Definition, Art. 100-A
Extensions through walls, 362-24
Electrical metallic tubing, 348-4
Marking, 362-27
Enameled equipment, 300-6(a)
Splices and taps, 362-21
Fixtures in, 410-4
Supports, 362-22
Health care facilities, 517-20
Uses, 362-15, 362-16
Intermediate metal conduit, 345-5
Mounting of equipment, 300-6(c)
Wiring methods; Art. 300; see also Haz-
Rigid metal conduit, 346-4
ardous (classified) locations
Rigid nonmetallic conduit, 347-2(d)
Ducts, 300-21, 300-22
Switchboards, 384-5
General requirements for, see General
Switches, 380-4
requirements for wiring methods
Wheelchair lifts, see Elevators, dumbwait-
Health care facilities, 517-B
ers, escalators, moving walks,
Intrinsically safe systems, 504-20
wheelchair lifts, and stairway chair
Mobile homes, 550-10
lifts
Planning, 90-8
Windows, show, see Show windows
Recreational vehicles, 551-10(c), 551-47
Temporary, see Temporary wiring
Wire in concrete footings, electrodes,
Theaters, 520-4
250-81(c)
Types and materials, Chap. 3
Wired fixture sections, 410-77(c)
Within sight from, see In sight from
Wires, see Conductors; Cords; Fixture
wire
Working space
About electrical equipment, 110-16,
Wireways, metal, 362-A
110-32 thru 110-34
Conductors, 362-4, 362-5
Adjacent to live parts (circuits over 600
Dead ends, 362-10
volts), 110-33, 110-34
Definition, 362-1
Motion picture projectors, 540-12
Deflected insulated, 362-6
Service equipment, 230-64
Extensions, 362-11
Switchboards, 384-4, 384-8
Extensions through walls, 362-9
Grounding, 362-13
Workmanlike installation, 110-12
Marking, 362-12
X-ray equipment, 517-E, Art. 660
Splices and taps, 362-7
Control, 517-74, 660-B
Supports, 362-8
Fixed and stationary
Use, 362-2
Definition, 660-2
Wireways, nonmetallic, 362-B
Guarding and grounding, 517-77, 660-D
Conductors, 362-18 thru 362-20
Installation, 517-E
Dead ends, 362-25
Definition, 517-3
Definition, 362-14
Transformers and capacitors, 517-76,
Expansion joints, 362-23
660-C
Extensions, 362-26
Types of, 600-4(b)
2. Adoption by Transcription - A. Public authorities with lawmaking or rulemaking powers only, upon written notice to the NFPA (Attention: Secretary, Standards
Council), will be granted a royalty-free license to print and republish this document
in whole or in part, with changes and additions, if any, noted separately, in laws, ordinances, regulations, administrative orders or similar instruments having the force of
law, provided that: (1) due notice of NFPA's copyright is contained in each law and in
each copy thereof; and, (2) that such printing and republication is limited to numbers
sufficient to satisfy the jurisdiction's lawmaking or rulemaking process. B. Once this
NFPA Code or Standard has been adopted into law, all printings of this document by
public authorities with lawmaking or rulemaking powers or any other persons desiring
to reproduce this document or its contents as adopted by the jurisdiction in whole or
in part, in any form, upon written request to NFPA (Attention: Secretary, Standards
Council), will be granted a nonexclusive license to print, republish, and vend this document in whole or in part, with changes and additions, if any, noted separately provided
that due notice of NFPA's copyright is contained in each copy. Such license shall be
granted only upon agreement to pay NFPA a royalty. This royalty is required to provide funds for the research and development necessary to continue the work of NFPA
and its volunteers in continually updating and revising NFPA standards. Under certain
circumstances, public authorities with lawmaking or rulemaking powers may apply for
and may receive a special royalty when the public interest will be served thereby.
3. Scope of License Grant - The terms and conditions set forth above do not
extend to the index to this document.
(For further explanation, see the Policy Concerning the Adoption, Printing and
Publication of NFPA Documents which is available upon request from the NFPA.)
Statement on NFPA Procedures
This material has been developed under the published procedures of the National
Fire Protection Association, which are designed to assure the appointment of technically
competent Committees having balanced representation. While these procedures assure
the highest degree of care, neither the National Fire Protection Association, its members,
nor those participating in its activities accepts any liability resulting from compliance
or noncompliance with the provisions given herein, for any restrictions imposed on
materials or processes, or for the completeness of the text.
NFPA has no power or authority to police or enforce compliance with the contents
of this document and any certification of products stating compliance with requirements
of this document is made at the peril of the certifier.
R
National Fire Protection Association Membership
When you join NFPA, you join more than 60,000 fire
protection professionals in the fight against loss of life and
property from fire.
There are many membership benefits, including your
opportunity to vote on changing codes and standards, your
free subscriptions to the NFPA Journal and Fire News
newsletter, a 10% discount on all NFPA products, services
and seminars, and much more!
Join today and become an active leader in the fire protection
industry. Call toll-free 1-800-344-355!
The 1993 NEC® Handbook takes the guess-work out of
interpreting the new Code!
The NEC Handbook is the key to understanding the
National Electrical Code® and applying it to real situations.
This powerful reference pulls together all the extra facts,
figures, and explanations you need to interpret the Code- -
and presents them to you in one easy-to-use reference. It
includes the entire text of the 1993 Code, plus helpful
commentary written by Code authorities.
The Handbook - or annotated Code - is a valuable,
time-saving tool that will help you work more efficiently
and get the job done right!
To place an order or request a free catalog call toll-free
1-800-344-355!