Regl. 5293, art. 318-9(c)-321
MESSENGER SUPPORTED WIRING
Cite as Reglamento Núm. 5293, Art. 318-9(c)-321
70-209
and at least as high as the insulating supports, placed on each side of and
close to the wiring; (2) by a substantial running board at least ½ inch
(12.7 mm) thick back of the conductors with side protections. Running
boards shall extend at least 1 inch (25.4 mm) outside the conductors, but
not more than 2 inches (50.8 mm), and the protecting sides shall be at least
2 inches (50.8 mm) high and at least 1 inch (25.4 mm) nominal in thickness;
(3) by boxing made as above and furnished with a cover kept at least 1 inch
(25.4 mm) away from the conductors within. Where protecting vertical
conductors on side walls, the boxing shall be closed at the top and the
holes through which the conductors pass shall be bushed; (4) by rigid metal
conduit, intermediate metal conduit, rigid nonmetallic conduit, or electrical
metallic tubing, in which case the rules of Article 345, 346, 347, or 348 shall
apply; or by metal piping, in which case the conductors shall be encased in
continuous lengths of approved flexible tubing. The conductors passing
through metal enclosures shall be so grouped that current in both directions is approximately equal.
320-15. Unfinished Attics and Roof Spaces. Conductors in unfinished
attics and roof spaces shall comply with (a) or (b) below.
(a) Accessible by Stairway or Permanent Ladder. Conductors shall be
installed along the side of or through bored holes in floor joists, studs, or
rafters. Where run through bored holes, conductors in the joists and in
studs or rafters to a height of not less than 7 feet (2.13 m) above the floor
or floor joists shall be protected by substantial running boards extending
not less than 1 inch (25.4 mm) on each side of the conductors. Running
boards shall be securely fastened in place. Running boards and guard strips
shall not be required for conductors installed along the sides of joists,
studs, or rafters.
(b) Not Accessible by Stairway or Permanent Ladder. Conductors shall
be installed along the sides of or through bored holes in floor joists, studs,
or rafters.
Exception: In buildings completed before wiring is installed and having
head room at all points of less than 3 feet (914 mm).
320-16. Switches. Surface-type snap switches shall be mounted in accordance with Section 380-10(a), and boxes shall not be required. Other type
switches shall be installed in accordance with Section 380-4.