Regl. 5293, art. 318-9(c)-324
CONCEALED KNOB-AND-TUBE WIRING
Cite as Reglamento Núm. 5293, Art. 318-9(c)-324
324-1. Definition. Concealed knob-and-tube wiring is a wiring method
using knobs, tubes, and flexible nonmetallic tubing for the protection and
support of single insulated conductors concealed in hollow spaces of walls
and ceilings of buildings.
324-2. Other Articles. Concealed knob-and-tube wiring shall comply with
this article and also with the applicable provisions of other articles in this
Code, especially Article 300.
324-3. Uses Permitted. Concealed knob-and-tube wiring shall be permitted to be used only for extensions of existing installations and elsewhere
only by special permission under the following conditions:
(1) In the hollow spaces of walls and ceilings.
(2) In unfinished attic and roof spaces as provided in Section 324-11.
324-4. Uses Not Permitted. Concealed knob-and-tube wiring shall not be
used in commercial garages, theaters and similar locations, motion picture
studios, hazardous (classified) locations, or in the hollow spaces of walls,
ceilings, and attics where such spaces are insulated by loose, rolled, or
foamed-in-place insulating material that envelops the conductors.
324-5. Conductors.
(a) Type. Conductors shall be of a type specified by Article 310.
(b) Ampacity. The ampacity shall be determined by Section 310-15.
324-6. Conductor Supports. Conductors shall be rigidly supported on
noncombustible, nonabsorbent insulating materials and shall not contact
any other objects. Supports shall be installed as follows: (1) within 6 inches
(152 mm) of each side of each tap or splice, and (2) at intervals not exceeding 4½ feet (1.37 m).
Exception: If it is not practicable to provide supports in dry locations, it
shall be permissible to fish conductors through hollow spaces if each conductor is individually enclosed in flexible nonmetallic tubing. The tubing
shall be in continuous lengths between supports, between boxes, or
between a support and a box.
324-7. Tie Wires. Where solid knobs are used, conductors shall be
securely tied thereto by tie wires having insulation equivalent to that of the
conductor.
324-8. Conductor Clearances. A clearance of not less than 3 inches
(76 mm) shall be maintained between conductors and of not less than 1 inch
(25.4 mm) between the conductor and the surface over which it passes.
Exception: Where space is too limited to provide the above minimum
clearances, such as at meters, panelboards, outlets, and switch points, the
conductors shall be individually enclosed in flexible nonmetallic tubing,
which shall be in continuous lengths between the last support or box and
the terminal point.
70-212
NATIONAL ELECTRICAL CODE
324-9. Through Walls, Floors, Wood Cross Members, etc. Conductors
shall comply with Section 320-11 where passing through holes in structural
members. Where passing through wood cross members in plastered partitions, conductors shall be protected by noncombustible, nonabsorbent,
insulating tubes extending not less than 3 inches (76 mm) beyond the wood
member.
324-10. Clearance from Piping, Exposed Conductors, etc. Conductors
shall comply with Section 320-12 for clearances from other exposed conductors, piping, etc.
324-11. Unfinished Attics and Roof Spaces. Conductors in unfinished
attics and roof spaces shall comply with (a) or (b) below.
(FPN): See Section 310-10 for temperature limitation of conductors.
(a) Accessible by Stairway or Permanent Ladder. Conductors shall be
installed along the side of or through bored holes in floor joists, studs, or
rafters. Where run through bored holes, conductors in the joists and in
studs or rafters to a height of not less than 7 feet (2.13 m) above the floor
or floor joists shall be protected by substantial running boards extending
not less than 1 inch (25.4 mm) on each side of the conductors. Running
boards shall be securely fastened in place. Running boards and guard strips
shall not be required where conductors are installed along the sides of
joists, studs, or rafters.
(b) Not Accessible by Stairway or Permanent Ladder. Conductors shall
be installed along the sides of or through bored holes in floor joists, studs,
or rafters.
Exception: In buildings completed before wiring is installed and having
head room at all points of less than 3 feet (914 mm).
324-12. Splices. Splices shall be soldered unless approved splicing
devices are used. In-line or strain splices shall not be used.
324-13. Boxes. Outlet boxes shall comply with Article 370.
324-14. Switches. Switches shall comply with Sections 380-4 and 380-10(b).