Regl. 5293, art. 318-9(c)-325 dup2
INTEGRATED GAS SPACER CABLE
Cite as Reglamento Núm. 5293, Art. 318-9(c)-325 dup2
70-213
325-3. Uses Permitted. The Type IGS cable shall be permitted for use
underground, including direct burial in the earth, as service-entrance conductors, or as feeder or branch-circuit conductors.
325-4. Uses Not Permitted. The Type IGS cable shall not be used as
interior wiring or exposed in contact with buildings.
B. Installation
325-11. Bending Radius. Where the coilable nonmetallic conduit and
cable is bent for installation purposes or is flexed or bent during shipment
or installation, the radii of bends measured to the inside of the bend shall
not be less than specified in Table 325-11.
Table 325-11. Minimum Radii of Bends
Conduit
Trade
Minimum
Size
Radii
2 inch
24 inches (610 mm)
3 inch
35 inches (889 mm)
4 inch
45 inches (1.14 m)
325-12. Bends. A run of Type IGS cable between pull boxes or terminations shall not contain more than the equivalent of four quarter bends (360
degrees, total), including those bends located immediately at the pull box
or terminations.
325-13. Fittings. Terminations and splices for the Type IGS cable shall
be identified as a type that is suitable for maintaining the gas pressure
within the conduit. A valve and cap shall be provided for each length of the
cable and conduit to check the gas pressure or to inject gas into the
conduit.
325-14. Ampacity. The ampacity of the Type IGS cable and conduit shall
not exceed values shown in Table 325-14 for single conductor or multiconductor cable.
C. Construction Specifications
325-20. Conductors. The conductors shall be solid aluminum rods, laid
parallel, consisting of one to nineteen 1/2-inch (12.7-mm) diameter rods.
The minimum conductor size shall be 250 kcmil and the maximum size
shall be 4750 kcmil.
70-214
NATIONAL ELECTRICAL CODE
Table 325-14. Ampacity Type IGS
Size
kcmil
Amperes
250
119
500
168
750
206
1000
238
1250
266
1500
292
1750
315
2000
336
2250
357
2500
376
3000
412
3250
429
3500
445
3750
461
4000
476
4250
491
4500
505
4750
519
325-21. Insulation. The insulation shall be dry kraft paper tapes and a
pressurized sulfur hexafluoride gas (SF₆), both approved for electrical use.
The nominal gas pressure shall be 20 pounds per square inch gauge (psig)
(138 kPa gauge).
The thickness of the paper spacer shall be as specified in Table 325-21.
Table 325-21. Paper Spacer Thickness
Size
Thickness
kcmil
Inches (mm)
250-1000
.040 (1.02)
1250-4750
.060 (1.52)
325-22. Conduit. The conduit shall be an approved medium density polyethylene identified as suitable for use with natural gas rated pipe in 2
inches, 3 inches, or 4 inches trade size. The percent fill dimensions for the
conduit are shown in Table 325-22.
The size of the conduit permitted for each conductor size shall be calculated for a percent fill not to exceed Table 1, Chapter 9.