Regl. 5293, art. 380-4
Resolución 2535: adopta el Código Eléctrico Nacional, versión 1993. (Sustituye el Anejo A del Reglamento 4435)
Cite as Reglamento Núm. 5293, Art. 380-4
(FPN No. 3): For protection against liquids, see Section 430-11.
(b) Wiring Methods. The electric motor and controller shall be connected to a circuit protected by a ground-fault circuit-interrupter.
680-27. Deck Area Heating. The provisions of this section apply to all
pool deck areas, including a covered pool, where electrically operated
comfort heating units are installed within 20 feet (6.1 m) of the inside wall
of the pool.
(a) Unit Heaters. Unit heaters shall be rigidly mounted to the structure
and shall be of the totally enclosed or guarded types. Unit heaters shall not
be mounted over the pool or within the area extending 5 feet (1.52 m) horizontally from the inside walls of a pool.
(b) Permanently Wired Radiant Heaters. Radiant electric heaters shall
be suitably guarded and securely fastened to their mounting device(s).
Heaters shall not be installed over a pool or within the area extending
5 feet (1.52 m) horizontally from the inside walls of the pool and shall be
mounted at least 12 feet (3.66 m) vertically above the pool deck unless otherwise approved.
(c) Radiant Heat Cables Not Permitted. Radiant heating cables embedded in or below the deck shall not be permitted.
C. Storable Pools
680-30. Pumps. A cord-connected pool filter pump shall incorporate an
approved system of double insulation or its equivalent and shall be provided with means for grounding only the internal and nonaccessible
noncurrent-carrying metal parts of the appliance.
The means for grounding shall be an equipment grounding conductor run
with the power-supply conductors in the flexible cord that is properly terminated in a grounding-type attachment plug having a fixed grounding contact member.
ARTICLE 680 - SWIMMING POOLS, FOUNTAINS
70-707
680-31. Ground-Fault Circuit-Interrupters Required. All electric equipment, including power-supply cords, used with storable pools shall be protected by ground-fault circuit-interrupters.
(FPN): Where flexible cords are used, see Section 400-4.
680-32. Lighting Fixtures. A lighting fixture installed in or on the wall of
a storable pool shall be part of a cord- and plug-connected lighting assembly. This assembly shall:
(1) Have no exposed metal parts;
(2) Have a fixture lamp that operates at 15 volts or less;
(3) Have an impact-resistant polymeric lens, fixture body, and transformer enclosure;
(4) Have a transformer meeting the requirements of Section 680-5(a)
with a primary rating not over 150 volts; and
(5) Be listed as an assembly for the purpose.
Exception: A lighting assembly without a transformer, and with the fixture lamp(s) operating at not over 150 volts, shall be permitted to be cordand plug-connected where the assembly complies with all of the following:
a. It has no exposed metal parts.
b. It has an impact-resistant polymeric lens and fixture body.
C. A ground-fault circuit-interrupter with open neutral protection is
provided as an integral part of the assembly.
d. The fixture lamp is permanently connected to the ground-fault
circuit-interrupter with open-neutral protection.
e. It complies with the requirements of Section 680-20(a).
f. It is listed as an assembly for the purpose.
D. Spas and Hot Tubs
680-40. Outdoor Installations. A spa or hot tub installed outdoors shall
comply with the provisions of Parts A and B.
Exception No. 1: Metal bands or hoops used to secure wooden staves
shall be exempt from Section 680-22.
Exception No. 2: Listed packaged units shall be permitted to be cordand plug-connected with a cord no longer than 15 feet (4.57 m) if protected
by a ground-fault circuit-interrupter.
Exception No. 3: Bonding by metal-to-metal mounting on a common
frame or base shall be permitted.
Exception No. 4: Listed packaged units utilizing a factory-installed
remote panelboard shall be permitted to be connected with not more than
3 feet (914 mm) of liquidtight flexible conduit.
680-41. Indoor Installations. A spa or hot tub installed indoors shall conform to the requirements of this part and shall be connected by wiring
methods of Chapter 3.
70-708
NATIONAL ELECTRICAL CODE
Exception: Listed packaged units rated 20 amperes or less shall be permitted to be cord- and plug-connected to facilitate the removal or disconnection for maintenance and repair.
(a) Receptacles. At least one convenience receptacle shall be located a
minimum of 5 feet (1.52 m) from and not more than 10 feet (3.05 m) from
the inside wall of the spa or hot tub.
(1) Receptacles on the property shall be located at least 5 feet (1.52 m)
from the inside walls of the spa or hot tub.
(2) 125-volt receptacles located within 10 feet (3.05 m) of the inside
walls of a spa or hot tub shall be protected by a ground-fault circuitinterrupter.
(FPN): In determining the above dimensions, the distance to be measured is the
shortest path the supply cord of an appliance connected to the receptacle would follow without piercing a floor, wall, or ceiling of a building or other effective permanent barrier.
(3) Receptacles that provide power for a spa or hot tub shall be
ground-fault circuit-interrupter protected.
(b) Lighting Fixtures, Lighting Outlets, and Ceiling Fans.
(1) Lighting fixtures, lighting outlets, and ceiling fans located over the
spa or hot tub or within 5 feet (1.52 m) from the inside walls of the spa or
hot tub shall be a minimum of 7 feet 6 inches (2.29 m) above the maximum
water level and shall be protected by a ground-fault circuit-interrupter.
Exception No. 1: Lighting fixtures, lighting outlets, and ceiling fans
located 12 feet (3.66 m) or more above the maximum water level shall not
require protection by a ground-fault circuit-interrupter.
Exception No. 2: Lighting fixtures meeting the requirements of items a or
b below and protected by a ground-fault circuit-interrupter shall be permitted
to be installed less than 7 feet 6 inches (2.29 m) over a spa or hot tub.
a. Recessed fixtures with a glass or plastic lens and nonmetallic or
electrically isolated metal trim, suitable for use in damp locations.
b. Surface-mounted fixtures with a glass or plastic globe and a nonmetallic body or a metallic body isolated from contact. Such fixtures shall
be suitable for use in damp locations.
(2) Underwater lighting fixtures shall comply with the provisions of
Part B or Part C of this article.
(c) Wall Switches. Switches shall be located at least 5 feet (1.52 m),
measured horizontally, from the inside walls of the spa or hot tub.
(d) Bonding. The following parts shall be bonded together:
(1) All metal fittings within or attached to the spa or hot tub structure.
(2) Metal parts of electric equipment associated with the spa or hot tub
water circulating system, including pump motors.
(3) Metal conduit and metal piping within 5 feet (1.52 m) of the inside
walls of the spa or hot tub and that are not separated from the spa or hot
tub by a permanent barrier.
ARTICLE 680 - SWIMMING POOLS, FOUNTAINS
70-709
(4) All metal surfaces that are within 5 feet (1.52 m) of the inside walls
of the spa or hot tub and not separated from the spa or hot tub area by a
permanent barrier.
Exception: Small conductive surfaces not likely to become energized,
such as air and water jets and drain fittings, where not connected to metallic piping, towel bars, mirror frames, and similar nonelectric equipment,
need not be bonded.
(5) Electrical devices and controls not associated with the spas or hot
tubs shall be located a minimum of 5 feet (1.52 m) away from such units or
be bonded to the spa or hot tub system.
(e) Methods of Bonding. All metal parts associated with the spa or hot
tub shall be bonded by any of the following methods: the interconnection
of threaded metal piping and fittings; metal-to-metal mounting on a common frame or base; or by the provisions of a copper bonding jumper, insulated, covered, or bare, not smaller than No. 8 solid.
(f) Grounding. The following equipment shall be grounded:
(1) All electric equipment located within 5 feet (1.52 m) of the inside
wall of the spa or hot tub.
(2) All electric equipment associated with the circulating system of the
spa or hot tub.
(g) Methods of Grounding.
(1) All electric equipment shall be grounded in accordance with Article 250 and connected by the wiring methods of Chapter 3.
(2) Where equipment is connected with a flexible cord, the equipment
grounding conductor shall be connected to a fixed metal part of the assembly.
(h) Electric Water Heaters. All electric spa or hot tub water heaters
shall be listed and have the heating elements subdivided into loads not
exceeding 48 amperes and protected at not more than 60 amperes.
The ampacity of the branch-circuit conductors, and the rating or setting
of overcurrent protective devices, shall not be less than 125 percent of the
total load of the nameplate rating.
(i) Underwater Audio Equipment. Underwater audio equipment shall
comply with the provisions of Part B or Part C of this article.
680-42. Protection. Spas and hot tubs and associated electrical components shall be protected by ground-fault circuit-interrupters. This requirement shall become effective on January 1, 1994.
E. Fountains
680-50. General. The provisions of Part E shall apply to all fountains as
defined in Section 680-4. Fountains that have water common to a pool shall
comply with the pool requirements of this article.
Exception: Self-contained, portable fountains no larger than 5 feet
(1.52 m) in any dimension are not covered by Part E.
70-710
NATIONAL ELECTRICAL CODE
680-51. Lighting Fixtures, Submersible Pumps, and Other Submersible
Equipment.
(a) Ground-Fault Circuit-Interrupter. A ground-fault circuit-interrupter
shall be installed in the branch circuit supplying fountain equipment.
Exception: Ground-fault circuit-interrupters shall not be required for
equipment operating at 15 volts or less and supplied by a transformer
complying with Section 680-5(a).
(b) Operating Voltage. All lighting fixtures shall be installed for operation
at 150 volts or less between conductors. Submersible pumps and other submersible equipment shall operate at 300 volts or less between conductors.
(c) Lighting Fixture Lenses. Lighting fixtures shall be installed with the
top of the fixture lens below the normal water level of the fountain unless
approved for above-water locations. A lighting fixture facing upward shall
have the lens adequately guarded to prevent contact by any person.
(d) Overheating Protection. Electric equipment that depends on submersion for safe operation shall be protected against overheating by a lowwater cutoff or other approved means when not submerged.
(e) Wiring. Equipment shall be equipped with provisions for threaded
conduit entries or be provided with a suitable flexible cord. The maximum
length of exposed cord in the fountain shall be limited to 10 feet (3.05 m).
Cords extending beyond the fountain perimeter shall be enclosed in
approved wiring enclosures. Metal parts of equipment in contact with
water shall be of brass or other approved corrosion-resistant metal.
(f) Servicing. All equipment shall be removable from the water for
relamping or normal maintenance. Fixtures shall not be permanently
imbedded into the fountain structure so that the water level must be
reduced or the fountain drained for relamping, maintenance, or inspection.
(g) Stability. Equipment shall be inherently stable or be securely fastened in place.
680-52. Junction Boxes and Other Enclosures.
(a) General. Junction boxes and other enclosures used for other than
underwater installation shall comply with Sections 680-21(a) (1), (2), and
(3); and (b), (c), and (d).
(b) Underwater Junction Boxes and Other Underwater Enclosures.
Junction boxes and other underwater enclosures shall be submersible and
(1) be equipped with provisions for threaded conduit entries or compression glands or seals for cord entry; (2) be of copper, brass, or other
approved corrosion-resistant material; (3) be filled with an approved potting compound to prevent the entry of moisture; and (4) be firmly attached
to the supports or directly to the fountain surface and bonded as required.
Where the junction box is supported only by the conduit, the conduit shall
be of copper, brass, or other approved corrosion-resistant metal. Where
the box is fed by nonmetallic conduit, it shall have additional supports and
fasteners of copper, brass, or other approved corrosion-resistant material.
(FPN): See Section 370-23 for support of enclosures.
ARTICLE 680 - SWIMMING POOLS, FOUNTAINS
70-711
680-53. Bonding. All metal piping systems associated with the fountain
shall be bonded to the equipment grounding conductor of the branch circuit supplying the fountain.
(FPN): See Section 250-95 for sizing of these conductors.
680-54. Grounding. The following equipment shall be grounded: (1) all
electric equipment located within the fountain or within 5 feet (1.52 m) of
the inside wall of the fountain; (2) all electric equipment associated with the
recirculating system of the fountain; (3) panelboards that are not part of the
service equipment and that supply any electric equipment associated with
the fountain.
680-55. Methods of Grounding.
(a) Applied Provisions. The provisions of Section 680-25 shall apply,
excluding paragraph (e).
(b) Supplied by a Flexible Cord. Electric equipment that is supplied by
a flexible cord shall have all exposed noncurrent-carrying metal parts
grounded by an insulated copper equipment grounding conductor that is an
integral part of this cord. This grounding conductor shall be connected to
a grounding terminal in the supply junction box, transformer enclosure, or
other enclosure.
680-56. Cord- and Plug-Connected Equipment.
(a) Ground-Fault Circuit-Interrupter. All electric equipment, including
power-supply cords, shall be protected by ground-fault circuit-interrupters.
(b) Cord Type. Flexible cord immersed in or exposed to water shall be
of the hard service type as designated in Table 400-4 and shall be marked
water-resistant.
(c) Sealing. The end of the flexible cord jacket and the flexible cord conductor termination within equipment shall be covered with, or encapsulated
in, a suitable potting compound to prevent the entry of water into the equipment through the cord or its conductors. In addition, the ground connection
within equipment shall be similarly treated to protect such connections from
the deteriorating effect of water that may enter into the equipment.
(d) Terminations. Connections with flexible cord shall be permanent,
except that grounding-type attachment plugs and receptacles shall be permitted to facilitate removal or disconnection for maintenance, repair, or
storage of fixed or stationary equipment not located in any watercontaining part of a fountain.
F. Therapeutic Pools and Tubs in Health Care Facilities
680-60. General. The provisions of Part F include therapeutic pools and
tubs in health care facilities. See Section 517-2 for definition of health care
facilities. Portable therapeutic appliances. shall comply with Article 422.
680-61. Permanently Installed Therapeutic Pools. Therapeutic pools that
are constructed in the ground, on the ground, or in a building in such a
manner that the pool cannot be readily disassembled shall comply with
Parts A and B of this article.
70-712
NATIONAL ELECTRICAL CODE
Exception: The limitations of Sections 680-6(b)(1) and (2) shall not apply
where all lighting fixtures are of the totally enclosed type.
680-62. Therapeutic Tubs (Hydrotherapeutic Tanks). Therapeutic tubs,
used for the submersion and treatment of patients, that are not easily
moved from one place to another in normal use or that are fastened or otherwise secured at a specific location, including associated piping systems,
shall conform to this part.
(a) Ground-Fault Circuit-Interrupter. A ground-fault circuit-interrupter
shall protect all therapeutic equipment.
Exception: Portable therapeutic appliances shall comply with Section
250-45.
(b) Bonding. The following parts shall be bonded together:
(1) All metal fittings within or attached to the tub structure.
(2) Metal parts of electric equipment associated with the tub water circulating system, including pump motors.
(3) Metal-sheathed cables and raceways and metal piping that are
within 5 feet (1.52 m) of the inside walls of the tub and not separated from
the tub by a permanent barrier.
(4) All metal surfaces that are within 5 feet (1.52 m) of the inside walls
of the tub and not separated from the tub area by a permanent barrier.
(5) Electrical devices and controls not associated with the therapeutic
tubs shall be located a minimum of 5 feet (1.52 m) away from such units or
be bonded to the therapeutic tub system.
(c) Methods of Bonding. All metal parts associated with the tub shall be
bonded by any of the following methods: the interconnection of threaded
metal piping and fittings; metal-to-metal mounting on a common frame or
base; connections by suitable metal clamps; or by the provisions of a solid
I
copper bonding jumper, insulated, covered, or bare, not smaller than No. 8.
(d) Grounding. The following equipment shall be grounded:
(1) All electric equipment located within 5 feet (1.52 m) of the inside
wall of the tub.
(2) All electric equipment associated with the circulating system of the
tub.
(e) Methods of Grounding.
(1) All electric equipment shall be grounded in accordance with Article 250 and connected by wiring methods of Chapter 3.
(2) Where equipment is connected with a flexible cord, the equipment
grounding conductor shall be connected to a fixed metal part of the assembly.
(f) Receptacles. All receptacles within 5 feet (1.52 m) of a therapeutic
tub shall be protected by a ground-fault circuit-interrupter.
(g) Lighting Fixtures. All. lighting fixtures used in therapeutic tub areas
shall be of the totally enclosed type.