INTEGRATED ELECTRICAL SYSTEMS
Cite as Reglamento Núm. 5293, Art. 380-4-685 dup2
A. General
685-1. Scope. This article covers integrated electrical systems, other
than unit equipment, in which orderly shutdown is necessary to assure safe
operation. An integrated electrical system as used in this article is a unitized segment of an industrial wiring system where all of the following conditions are met: (1) an orderly shutdown is required to minimize personnel
hazard and equipment damage; (2) the conditions of maintenance and
supervision assure that qualified persons will service the system; and
(3) effective safeguards, acceptable to the authority having jurisdiction, are
established and maintained.
685-2. Application of Other Articles. In other articles applying to particular cases of installation of conductors and equipment, there are orderly
shutdown requirements that are in addition to those of this article or are
modifications of them:
Section
More than One Building or Other Structure
225-8
Ground-Fault Protection of Equipment
230-95, Exception No. 1
Protection of Conductors
240-3(a)
Electrical System Coordination
240-12
Ground-Fault Protection of Equipment
240-13, Exception No. 1
Grounding ac Systems of 50 to 1000 Volts
250-5(b), Exception No. 3
Orderly Shutdown
430-44
Disconnection
430-74, Exception Nos. 1 and 2
Disconnecting Means in Sight from Controller
430-102, Exception No. 2
Energy from More than One Source
430-113, Exception Nos. 1 and 2
Disconnecting Means
645-110, Exception
Point of Connection
705-12, Exception No. 1
B. Orderly Shutdown
685-10. Location of Overcurrent Devices in or on Premises. Location of
overcurrent devices that are critical to integrated electrical systems shall be
permitted to be accessible, with mounting heights allowed to assure security from operation by nonqualified personnel.
70-714
NATIONAL ELECTRICAL CODE
685-12. Direct-Current System Grounding. Two-wire direct-current circuits shall be permitted to be ungrounded.
685-14. Ungrounded Control Circuits. Where operational continuity is
required, control circuits of 150 volts or less from separately derived systems shall be permitted to be ungrounded.