Regl. 5293, art. 380-4-690 dup2
Resolución 2535: adopta el Código Eléctrico Nacional, versión 1993. (Sustituye el Anejo A del Reglamento 4435)
Cite as Reglamento Núm. 5293, Art. 380-4-690 dup2
(3) Overcurrent protection for a transformer with a source(s) on each
side shall be provided in accordance with Section 450-3 by considering first
one side of the transformer, then the other side of the transformer, as the
primary.
705-32. Ground-Fault Protection. Where ground-fault protection is used,
the output of an interactive system shall be connected to the supply side of
the ground-fault protection.
Exception: Connection shall be permitted to be made to the load side of
ground-fault protection provided that there is ground-fault protection for
equipment from all ground-fault current sources.
705-40. Loss of Primary Source. Upon loss of primary source, an electric power production source shall be automatically disconnected from all
ungrounded conductors of the primary source and shall not be reconnected
until the primary source is restored.
(FPN No. 1): Risks to personnel and equipment associated with the primary
source may occur if an interactive electric power production source can operate as
an island. Special detection methods may be required to determine that a primary
source supply system outage has occurred, and whether there should be automatic
disconnection. When the primary source supply system is restored, special detection methods may be required to limit exposure of power production sources to outof-phase reconnection.
(FPN No. 2): Induction generating equipment on systems with significant
capacitance may become self-excited upon loss of primary source and experience
severe over-voltage as a result.
705-42. Unbalanced Interconnections. A 3-phase electric power production source shall be automatically disconnected from all ungrounded conductors of the interconnected systems when one of the phases of that
source opens.
Exception: An electric power production source providing power for an
emergency or legally required standby system.
705-43. Synchronous Generators. Synchronous generators in a parallel
system shall be provided with the necessary equipment to establish and
maintain a synchronous condition.
705-50. Grounding. Interconnected electric power production sources
shall be grounded in accordance with Article 250.
Exception: For direct-current systems connected through an inverter
directly to a grounded service, other methods that accomplish equivalent
system protection and that utilize equipment listed and identified for the
use shall be permitted.
70-738
NATIONAL ELECTRICAL CODE