Regl. 5293, art. 380-4-702
OPTIONAL STANDBY SYSTEMS
Cite as Reglamento Núm. 5293, Art. 380-4-702
70-733
legally required standby service shall be sufficiently separated from the
normal main service disconnecting means to prevent simultaneous interruption of supply through an occurrence within the building or groups of
buildings served.
(FPN): See Section 230-82 for equipment permitted on the supply side of a service disconnecting means.
(f) Unit Equipment. Individual unit equipment for legally required
standby illumination shall consist of (1) a rechargeable battery; (2) a battery
charging means; (3) provisions for one or more lamps mounted on the
equipment and shall be permitted to have terminals for remote lamps; and
I
(4) a relaying device arranged to energize the lamps automatically upon
failure of the supply to the unit equipment. The batteries shall be of suitable rating and capacity to supply and maintain at not less than 87½ percent of the nominal battery voltage for the total lamp load associated with
the unit for a period of at least 1½ hours, or the unit equipment shall supply and maintain not less than 60 percent of the initial legally required
standby illumination for a period of at least 1½ hours. Storage batteries,
whether of the acid or alkali type, shall be designed and constructed to
meet the requirements of emergency service.
Unit equipment shall be permanently fixed in place (i.e., not portable)
and shall have all wiring to each unit installed in accordance with the
requirements of any of the wiring methods in Chapter 3. Flexible cord- and
plug-connection shall be permitted, provided that the cord does not exceed
3 feet (914 mm) in length. The branch circuit feeding the unit equipment
shall be the same branch circuit as that serving the normal lighting in the
area and connected ahead of any local switches. Legally required standby
illumination fixtures that obtain power from a unit equipment and are not
part of the unit equipment shall be wired to the unit equipment by one of
the wiring methods of Chapter 3.
D. Overcurrent Protection
701-15. Accessibility. The branch-circuit overcurrent devices in legally
required standby circuits shall be accessible to authorized persons only.
701-17. Ground-Fault Protection of Equipment. The alternate source for
legally required standby systems shall not be required to have ground-fault
protection of equipment.