Regl. 5293, art. 384-32
Resolución 2535: adopta el Código Eléctrico Nacional, versión 1993. (Sustituye el Anejo A del Reglamento 4435)
Cite as Reglamento Núm. 5293, Art. 384-32
(d) Fire Pump Installations. Where the transformer is dedicated to supplying power to a fire pump installation, it shall not require secondary
overcurrent protection. Primary overcurrent protection shall be provided
in accordance with Section 450-3(a) or 450-3(b). The primary rating or setting shall be sufficient to carry the equivalent of the transformer secondary
current sum of the locked-rotor currents of the fire pump motor(s) and
associated fire pump accessory equipment indefinitely.
450-4. Autotransformers 600 Volts, Nominal, or Less.
(a) Overcurrent Protection. Each autotransformer 600 volts, nominal,
or less, shall be protected by an individual overcurrent device installed in
series with each ungrounded input conductor. Such overcurrent device
shall be rated or set at not more than 125 percent of the rated full-load input
current of the autotransformer. An overcurrent device shall not be installed
in series with the shunt winding (the winding common to both the input and
the output circuits) of the autotransformer between Points A and B as
shown in Diagram 450-4.
leese
A
ellelle
Shunt winding(s)
B
Diagram 450-4
Exception: Where the rated input current of an autotransformer is
9 amperes or more and 125 percent of this current does not correspond to
a standard rating of a fuse or nonadjustable circuit breaker, the next
higher standard rating described in Section 240-6 shall be permitted.
Where the rated input current is less than 9 amperes, an overcurrent
device rated or set at not more than 167 percent of the input current shall
be permitted.
(b) Transformer Field-Connected as an Autotransformer. A transformer field-connected as an autotransformer shall be identified for use at
elevated voltage.
(FPN): For information on permitted uses of autotransformers, see Section 210-9.
70-448
NATIONAL ELECTRICAL CODE
450-5. Grounding Autotransformers. Grounding autotransformers covered in this section are zig-zag or T-connected transformers connected to
3-phase, 3-wire ungrounded systems for the purpose of creating a 3-phase,
4-wire distribution system or to provide a neutral reference for grounding
purposes. Such transformers shall have a continuous per phase current
rating and a continuous neutral current rating.
(FPN): The phase current in a grounding autotransformer is one-third the neutral current.
(a) Three-Phase, 4-Wire System. A grounding autotransformer used to
create a 3-phase, 4-wire distribution system from a 3-phase, 3-wire
ungrounded system shall conform to the following:
(1) Connections. The transformer shall be directly connected to the
ungrounded phase conductors and shall not be switched or provided with
overcurrent protection that is independent of the main switch and
common-trip overcurrent protection for the 3-phase, 4-wire system.
(2) Overcurrent Protection. An overcurrent sensing device shall be
provided that will cause the main switch or common-trip overcurrent protection referred to in (a)(1) above to open if the load on the autotransformer
reaches or exceeds 125 percent of its continuous current per phase or neutral rating. Delayed tripping for temporary overcurrents sensed at the
autotransformer overcurrent device shall be permitted for the purpose of
allowing proper operation of branch or feeder protective devices on the
4-wire system.
(3) Transformer Fault Sensing. A fault sensing system that will cause
the opening of a main switch or common-trip overcurrent device for the
3-phase, 4-wire system shall be provided to guard against single-phasing or
internal faults.
(FPN): This can be accomplished by the use of two subtractive-connected
donut-type current transformers installed to sense and signal when an unbalance
occurs in the line current to the autotransformer of 50 percent or more of rated
current.
(4) Rating. The autotransformer shall have a continuous neutral current rating sufficient to handle the maximum possible neutral unbalanced
load current of the 4-wire system.
(b) Ground Reference for Fault Protection Devices. A grounding
autotransformer used to make available a specified magnitude of groundfault current for operation of a ground responsive protective device on
a 3-phase, 3-wire ungrounded system shall conform to the following
requirements:
(1) Rating. The autotransformer shall have a continuous neutral current rating sufficient for the specified ground-fault current.
(2) Overcurrent Protection. An overcurrent protective device of adequate short-circuit rating that will open simultaneously all ungrounded conductors when it operates shall be applied in the grounding autotransformer
branch circuit and rated or set at a current not exceeding 125 percent of the
autotransformer continuous per phase current rating or 42 percent of the
continuous current rating of any series connected devices in the autotransformer neutral connection. Delayed tripping for temporary overcurrents to
permit the proper operation of ground responsive tripping devices on the