TRANSFORMERS AND TRANSFORMER VAULTS 70-455
Cite as Reglamento Núm. 5293, Art. 384-32-450 dup4
rating of 3 hours. The authority having jurisdiction shall be permitted to
require such a door for an exterior wall opening where conditions warrant.
Exception: Where transformers are protected with automatic sprinkler,
water spray, carbon dioxide, or halon, construction of 1-hour rating shall
be permitted.
(FPN): For additional information, see Fire Doors and Fire Windows, NFPA
80-1992 (ANSI).
(b) Sills. A door sill or curb of sufficient height to confine within the
vault the oil from the largest transformer shall be provided, and in no case
shall the height be less than 4 inches (102 mm).
(c) Locks. Doors shall be equipped with locks, and doors shall be kept
locked, access being allowed only to qualified persons. Personnel doors
shall swing out and be equipped with panic bars, pressure plates, or other
devices that are normally latched but open under simple pressure.
450-45. Ventilation Openings. Where required by Section 450-9, openings for ventilation shall be provided in accordance with (a) through (f)
below.
(a) Location. Ventilation openings shall be located as far away as possible from doors, windows, fire escapes, and combustible material.
(b) Arrangement. A vault ventilated by natural circulation of air shall be
permitted to have roughly half of the total area of openings required for
ventilation in one or more openings near the floor and the remainder in one
or more openings in the roof or in the sidewalls near the roof, or all of the
area required for ventilation shall be permitted in one or more openings in
or near the roof.
(c) Size. For a vault ventilated by natural circulation of air to an outdoor area, the combined net area of all ventilating openings, after deducting the area occupied by screens, gratings, or louvers, shall not be less than
3 square inches (1936 sq mm) per kVA of transformer capacity in service,
and in no case shall the net area be less than 1 square foot (0.093 sq m) for
any capacity under 50 kVA.
(d) Covering. Ventilation openings shall be covered with durable gratings, screens, or louvers, according to the treatment required in order to
avoid unsafe conditions.
(e) Dampers. All ventilation openings to the indoors shall be provided
with automatic closing fire dampers that operate in response to a vault fire.
Such dampers shall possess a standard fire rating of not less than
1½ hours.
(FPN): See Standard for Fire Dampers, ANSI/UL 555-1972.
(f) Ducts. Ventilating ducts shall be constructed of fire-resistant material.
450-46. Drainage. Where practicable, vaults containing more than 100
kVA transformer capacity shall be provided with a drain or other means
that will carry off any accumulation of oil or water in the vault unless local
conditions make this impracticable. The floor shall be pitched to the drain
where provided.
70-456
NATIONAL ELECTRICAL CODE
450-47. Water Pipes and Accessories. Any pipe or duct system foreign
to the electrical installation shall not enter or pass through a transformer
vault. Piping or other facilities provided for vault fire protection, or for transformer cooling, shall not be considered foreign to the electrical installation.
450-48. Storage in Vaults. Materials shall not be stored in transformer
vaults.