PHASE CONVERTERS
Cite as Reglamento Núm. 5293, Art. 384-32-455 dup2
70-457
455-7. Overcurrent Protection. The single-phase supply conductor and
phase converter shall be protected from overcurrent at not more than 125
percent of the phase converter nameplate single-phase input full-load
amperes.
Exception No. 1: Where the phase converter supplies specific fixed
loads, the overcurrent protection shall have a rating not greater than 250
percent of the sum of the full-load, 3-phase current rating of the motors
and other loads served where the input and output voltages of the phase
converter are identical.
Where the input and output voltages of the phase converter are different, the current as determined by this section shall be multiplied by the
ratio of output to input voltage.
Exception No. 2: Where the required fuse rating or circuit breaker setting does not correspond to a standard rating or setting, the next higher
standard rating or setting shall be permitted.
455-8. Disconnecting Means. Means shall be provided to disconnect
simultaneously all ungrounded single-phase supply conductors to the phase
converter.
(a) Location. The disconnecting means shall be readily accessible and
located in sight from the phase converter.
(b) Type. The disconnecting means shall be a switch rated in horsepower, a circuit breaker, or a molded-case switch.
Exception: Where only nonmotor loads are served, an ampere-rated
switch shall be permitted.
(c) Rating. The ampere rating of the disconnecting means shall not be
less than 115 percent of the rated maximum single-phase input full-load
amperes.
Exception No. 1: Where the phase converter supplies specific fixed
loads, and the input and output voltages of the phase converter are identical, the disconnecting means shall be permitted to be a circuit breaker or
molded-case switch with an ampere rating not less than 250 percent of the
sum of the following:
a. Full-load 3-phase current ratings of the motors, and
b. Other loads served.
Where the input and output voltages of the phase converter are different, the current shall be multiplied by the ratio of the output to input
voltage.
Exception No. 2: Where the phase converter supplies specific fixed
loads, and the input and output voltages of the phase converter are identical, the disconnecting means shall be permitted to be a switch with a
horsepower rating. The horsepower rating shall be equivalent to 200 percent of the sum of the following:
a. Nonmotor loads,
b. The 3-phase locked-rotor current of the largest motor as determined from Table 430-151, and
70-458
NATIONAL ELECTRICAL CODE
c. The full-load current of all other 3-phase motors operating at
the same time.
Where the input and output voltages of the phase converter are
different, the current shall be multiplied by the ratio of the output to
input voltage.
455-9. Connection of Single-Phase Loads. Where single-phase loads are
connected on the load side of a phase converter, they shall not be connected to the derived phase.
455-10. Terminal Housings. A terminal housing shall be provided on a
phase converter, and the terminal housing shall be in accordance with the
provisions of Section 430-12.
B. Specific Provisions Applicable to
Different Types of Phase Converters
455-20. Disconnecting Means. The single-phase disconnecting means for
the input of a static phase converter shall be permitted to serve as the disconnecting means for the phase converter and a single load if the load is
within sight of the disconnecting means.
455-21. Start-Up. Power to the utilization equipment shall not be supplied until the rotary phase converter has been started.
455-22. Power Interruption. Utilization equipment supplied by a rotary
phase converter shall be controlled in such a manner that power to the
equipment will be disconnected in the event of a power interruption.
(FPN): Magnetic motor starters, magnetic contactors, and similar devices, with
interruption. manual or time delay restarting for the load, will provide restarting after power
455-23. Capacitors. Capacitors that are not an integral part of the rotary
phase conversion system but are installed for a motor load shall be connected to the line side of that motor overload protective device.