Regl. 5293, art. 384-32-470
RESISTORS AND REACTORS
Cite as Reglamento Núm. 5293, Art. 384-32-470
For Rheostats, see Section 430-82.
A. 600 Volts, Nominal, and Under
470-1. Scope. This article covers the installation of separate resistors
and reactors on electric circuits.
Exception: Resistors and reactors that are component parts of other
apparatus.
This article also covers the installation of resistors and reactors in hazardous (classified) locations as modified by Articles 501 through 504.
470-2. Location. Resistors and reactors shall not be placed where
exposed to physical damage.
470-3. Space Separation. A thermal barrier shall be required if the space
between the resistors and reactors and any combustible material is less
than 12 inches (305 mm).
470-4. Conductor Insulation. Insulated conductors used for connections
between resistance elements and controllers shall be suitable for an operating temperature of not less than 90°C (194°F).
Exception: Other conductor insulations shall be permitted for motor
starting service.
B. Over 600 Volts, Nominal
470-18. General.
(a) Protected Against Physical Damage. Resistors and reactors shall be
protected against physical damage.
(b) Isolated by Enclosure or Elevation. Resistors and reactors shall be
isolated by enclosure or elevation to protect personnel from accidental
contact with energized parts.
(c) Combustible Materials. Resistors and reactors shall not be installed
in close enough proximity to combustible materials to constitute a fire hazard and shall have a clearance of not less than 1 foot (305 mm) from combustible materials.
(d) Clearances. Clearances from resistors and reactors to grounded surfaces shall be adequate for the voltage involved.
(FPN): See Article 710.
(e) Temperature Rise from Induced Circulating Currents. Metallic
enclosures of reactors and adjacent metal parts shall be installed so that the
temperature rise from induced circulating currents will not be hazardous to
personnel or constitute a fire hazard.
470-19. Grounding. Resistor and reactor cases or enclosures shall be
grounded in accordance with Article 250.