Regl. 5293, art. 384-32-480 dup2
STORAGE BATTERIES
Cite as Reglamento Núm. 5293, Art. 384-32-480 dup2
480-1. Scope. The provisions of this article shall apply to all stationary
installations of storage batteries.
480-2. Definitions.
Storage Battery: A battery comprised of one or more rechargeable
cells of the lead-acid, nickel-cadmium, or other rechargeable electrochemical types.
Sealed Cell or Battery: A sealed cell or battery is one that has no provision for the addition of water or electrolyte or for external measurement
of electrolyte specific gravity. The individual cells shall be permitted to
contain a venting arrangement as described in Section 480-9(b).
Nominal Battery Voltage: The voltage computed on the basis of 2.0
volts per cell for the lead-acid type and 1.2 volts per cell for the alkali type.
480-3. Wiring and Equipment Supplied from Batteries. Wiring and
equipment supplied from storage batteries shall be subject to the requirements of this Code applying to wiring and equipment operating at the same
voltage.
Exception: As otherwise provided for communication systems in Article 800.
480-4. Grounding. The requirements of Article 250 shall apply.
480-5. Insulation of Batteries of Not Over 250 Volts. This section shall
apply to storage batteries having cells so connected as to operate at a
nominal battery voltage of not over 250 volts.
(a) Vented Lead-Acid Batteries. Cells and multicompartment batteries
with covers sealed to containers of nonconductive, heat-resistant material
shall not require additional insulating support.
(b) Vented Alkaline-type Batteries. Cells with covers sealed to jars of
nonconductive, heat-resistant material shall require no additional insulation support. Cells in jars of conductive material shall be installed in trays
of nonconductive material with not more than 20 cells (24 volts, nominal)
in the series circuit in any one tray.
(c) Rubber Jars. Cells in rubber or composition containers shall require
no additional insulating support where the total nominal voltage of all cells
in series does not exceed 150 volts. Where the total voltage exceeds 150
volts, batteries shall be sectionalized into groups of 150 volts or less, and
each group shall have the individual cells installed in trays or on racks.
(d) Sealed Cells or Batteries. Sealed cells and multicompartment sealed
batteries constructed of nonconductive, heat-resistant material shall not
70-464
NATIONAL ELECTRICAL CODE
require additional insulating support. Batteries constructed of a conducting
container shall have insulating support if a voltage is present between the
container and ground.
480-6. Insulation of Batteries of Over 250 Volts. The provisions of Section 480-5 shall apply to storage batteries having the cells so connected as
to operate at a nominal voltage exceeding 250 volts, and, in addition, the
provisions of this section shall also apply to such batteries. Cells shall be
installed in groups having a total nominal voltage of not over 250 volts.
Insulation, which can be air, shall be provided between groups and shall
have a minimum separation between live battery parts of opposite polarity
of 2 inches (50.8 mm) for battery voltages not exceeding 600 volts.
480-7. Racks and Trays. Racks and trays shall comply with (a) and
(b) below.
(a) Racks. Racks, as required in this article, are rigid frames designed to
support cells or trays. They shall be substantial and made of:
(1) Metal, so treated as to be resistant to deteriorating action by the
electrolyte and provided with nonconducting members directly supporting
the cells or with continuous insulating material other than paint or conducting members; or
(2) Other construction such as fiberglass or other suitable nonconductive materials.
(b) Trays. Trays are frames, such as crates or shallow boxes usually of
wood or other nonconductive material, so constructed or treated as to be
resistant to deteriorating action by the electrolyte.
480-8. Battery Locations. Battery locations shall conform to (a) and
(b) below.
(a) Ventilation. Provisions shall be made for sufficient diffusion and
ventilation of the gases from the battery to prevent the accumulation of an
explosive mixture.
(b) Live Parts. Guarding of live parts shall comply with Section 110-17.
480-9. Vents.
(a) Vented Cells. Each vented cell shall be equipped with a flame arrestor designed to prevent destruction of the cell due to ignition of gases
within conditions. the cell by an external spark or flame under normal operating
(b) Sealed Cells. Sealed battery/cells shall be equipped with a pressurerelease vent to prevent excessive accumulation of gas pressure, or the
battery/cell shall be designed to prevent scatter of cell parts in event of a
cell explosion.
70-465
Chapter 5. Special Occupancies