Regl. 5293, art. 384-32-500
HAZARDOUS (CLASSIFIED) LOCATIONS
Cite as Reglamento Núm. 5293, Art. 384-32-500
500-1. Scope - Articles 500 Through 504. Articles 500 through 504
cover the requirements for electrical equipment and wiring for all voltages
in locations where fire or explosion hazards may exist due to flammable
gases or vapors, flammable liquids, combustible dust, or ignitible fibers or
flyings.
500-2. Location and General Requirements. Locations shall be classified
depending on the properties of the flammable vapors, liquids or gases, or
combustible dusts or fibers that may be present and the likelihood that a
flammable or combustible concentration or quantity is present. Where
pyrophoric materials are the only materials used or handled, these locations shall not be classified.
Each room, section, or area shall be considered individually in determining its classification.
Exception: Except as modified in Articles 500 through 504, all other
applicable rules contained in this Code shall apply to electric equipment
and wiring installed in hazardous (classified) locations.
(FPN No. 1): For definitions of "approved" and "explosionproof" as used in
these articles, see Article 100; "dust-ignition-proof" is defined in Section 502-1.
Intrinsically safe apparatus and wiring shall be permitted in any hazardous (classified) location for which it is approved, and the provisions of
Articles 501 through 503 and 510 through 516 shall not be considered applicable to such installations except as required by Article 504.
Wiring of intrinsically safe circuits shall be physically separated from
wiring of all other circuits that are not intrinsically safe. Means shall be
provided to minimize the passage of gases and vapors.
Installation of intrinsically safe apparatus and wiring shall be in accordance with the requirements of Article 504.
(FPN No. 2): Through the exercise of ingenuity in the layout of electrical installations for hazardous (classified) locations, it is frequently possible to locate much
of the equipment in less hazardous or in nonhazardous locations and, thus, to reduce
the amount of special equipment required. In some cases, hazards may be reduced
or hazardous (classified) locations limited or eliminated by adequate positivepressure ventilation from a source of clean air in conjunction with effective safeguards against ventilation failure. For further information, see Purged and Pressurized Enclosures for Electrical Equipment, NFPA 496-1989 (ANSI), Flammable and
Combustible Liquids Code, NFPA 30-1990 (ANSI), Section 5-3.3, and American
Petroleum Institute, API RP 500-1991, Recommended Practice for Classification of
Locations for Electrical Installations at Petroleum Facilities, Section 4.6.
(FPN No. 3): It is important that the authority having jurisdiction be familiar
with such recorded industrial experience as well as with such standards of the
National Fire Protection Association as may be of use in the classification of various areas with respect to hazard.
70-466
NATIONAL ELECTRICAL CODE
(FPN No. 4): For further information, see Flammable and Combustible Liquids
Code, NFPA 30-1990; Drycleaning Plants, NFPA 32-1990; Manufacture of Organic
Coatings, NFPA 35-1987 (ANSI); Solvent Extraction Plants, NFPA 36-1988
(ANSI); Storage and Handling of Liquefied Petroleum Gases, NFPA 58-1992; Storage and Handling of Liquefied Petroleum Gases at Utility Gas Plants, NFPA
59-1992; Classification of Class I Hazardous (Classified) Locations for Electrical
Installations in Chemical Process Areas, NFPA 497A-1992 (ANSI); and Fire Protection in Wastewater Treatment and Collection Facilities, NFPA 820-1992 (ANSI).
(FPN No. 5): For protection against static electricity hazards, see Recommended Practice on Static Electricity, NFPA 77-1988 (ANSI).
(FPN No. 6): For electrical classification of laboratory areas, see Fire Protection for Laboratories Using Chemicals, NFPA 45-1991.
All conduit referred to herein shall be threaded with an NPT standard
conduit cutting die that provides ³/₄-inch taper per foot. Such conduit shall
be made up wrenchtight to minimize sparking when fault current flows
through the conduit system. Where it is impractical to make a threaded
joint tight, a bonding jumper shall be utilized.
500-3. Special Precaution. Articles 500 through 504 require equipment
construction and installation that will ensure safe performance under conditions of proper use and maintenance.
(FPN No. 1): It is important that inspection authorities and users exercise more
than ordinary care with regard to installation and maintenance.
(FPN No. 2): Low ambient conditions require special consideration. Explosionproof or dust-ignitionproof equipment may not be suitable for use at temperatures
lower than -25°C (-13°F) unless they are approved for low-temperature service.
However, at low ambient temperatures, flammable concentrations of vapors may
not exist in a location classified Class I, Division 1 at normal ambient temperature.
For purposes of testing, approval, and area classification, various air
mixtures (not oxygen-enriched) shall be grouped in accordance with Sections 500-3(a) and 500-3(b).
Exception: Equipment approved for a specific gas, vapor, or dust.
(FPN): This grouping is based on the characteristics of the materials. Facilities
have been made available for testing and approving equipment for use in the various
atmospheric groups.
(a) Class I Group Classifications. Class I groups shall be as follows:
(1) Group A. Atmospheres containing acetylene.
(2) Group B: Atmospheres containing hydrogen, fuel and combustible process gases containing more than 30 percent hydrogen by volume, or
gases or vapors of equivalent hazard such as butadiene, ethylene oxide,
propylene oxide, and acrolein.
Exception No. 1: Group D equipment shall be permitted to be used for
atmospheres containing butadiene if such equipment is isolated in accordance with Section 501-5(a) by sealing all conduit ¹/₂-inch size or larger.
Exception No. 2: Group C equipment shall be permitted to be used for
atmospheres containing ethylene oxide, propylene oxide, and acrolein if
such equipment is isolated in accordance with Section 501-5(a) by sealing
all conduit ¹/₂-inch size or larger.
(3) Group C: Atmospheres such as ethyl ether, ethylene, or gases or
vapors of equivalent hazard.
ARTICLE 500 - HAZARDOUS (CLASSIFIED) LOCATIONS
70-467
(4) Group D: Atmospheres such as acetone, ammonia, benzene,
butane, cyclopropane, ethanol, gasoline, hexane, methanol, methane, natural gas, naphtha, propane, or gases or vapors of equivalent hazard.
Exception: For atmospheres containing ammonia, the authority having
jurisdiction for enforcement of this Code shall be permitted to reclassify
the location to a less hazardous location or a nonhazardous location.
(FPN No. 1): For additional information on the properties and group classification
of Class I materials, see Classification of Gases, Vapors, and Dusts for Electrical
Equipment in Hazardous (Classified) Locations, NFPA 497M-1991, and Fire Hazard
Properties of Flammable Liquids, Gases, and Volatile Solids, NFPA 325M-1991.
(FPN No. 2): The explosion characteristics of air mixtures of gases or vapors
vary with the specific material involved. For Class I locations, Groups A, B, C, and
D, the classification involves determinations of maximum explosion pressure and
maximum safe clearance between parts of a clamped joint in an enclosure. It is necessary, therefore, that equipment be approved not only for class but also for the
specific group of the gas or vapor that will be present.
(FPN No. 3): Certain chemical atmospheres may have characteristics that
require safeguards beyond those required for any of the above groups. Carbon disulfide is one of these chemicals because of its low ignition temperature [100°C
(212°F)] and the small joint clearance permitted to arrest its flame.
(FPN No. 4): For classification of areas involving ammonia atmosphere, see
Safety Code for Mechanical Refrigeration, ANSI/ASHRAE 15-1978, and Safety
Requirements for the Storage and Handling of Anhydrous Ammonia, ANSI/CGA
G2.1-1981.
(b) Class II Group Classifications. Class II groups shall be as follows:
(1)x Group E: Atmospheres containing combustible metal dusts,
including aluminum, magnesium, and their commercial alloys, or other
combustible dusts whose particle size, abrasiveness, and conductivity
present similar hazards in the use of electrical equipment.
(FPN): Certain metal dusts may have characteristics that require safeguards
beyond those required for atmospheres containing the dusts of aluminum, magnesium, and their commercial alloys. For example, zirconium, thorium, and uranium
dusts have extremely low ignition temperatures [as low as 20°C (68°F)] and minimum ignition energies lower than any material classified in any of the Class I or
Class II Groups.
(2)* Group F: Atmospheres containing combustible carbonaceous
dusts, including carbon black, charcoal, coal, or coke dusts that have more
than 8 percent total entrapped voltatiles, or dusts that have been sensitized
by other materials so that they present an explosion hazard.
(FPN): See ASTM D 3175-89, Standard Test Method for Volatile Material in
the Analysis Sample for Coal and Coke.
(3) Group G: Atmospheres containing combustible dusts not included
in Group E or F, including flour, grain, wood, plastic, and chemicals.
(FPN No. 1): For additional information on group classification of Class II
materials, see Classification of Gases, Vapors, and Dusts for Electrical Equipment
in Hazardous (Classified) Locations, NFPA 497M-1991.
(FPN No. 2): The explosion characteristics of air mixtures of dust vary with the
materials involved. For Class II locations, Groups E, F, and G, the classification
involves the tightness of the joints of assembly and shaft openings to prevent the
entrance of dust in the dust-ignitionproof enclosure, the blanketing effect of layers
of dust on the equipment that may cause overheating, and the ignition temperature
70-468
NATIONAL ELECTRICAL CODE
of the dust. It is necessary, therefore, that equipment be approved not only for the
class, but also for the specific group of dust that will be present.
(FPN No. 3): Certain dusts may require additional precautions due to chemical
phenomena that can result in the generation of ignitible gases. See National Electrical Safety Code, ANSI C2-1990, Section 127A-Coal Handling Areas.
(c) Approval for Class and Properties. Equipment shall be approved
not only for the class of location but also for the explosive, combustible,
or ignitible properties of the specific gas, vapor, dust, fiber, or flyings that
will be present. In addition, Class I equipment shall not have any exposed
surface that operates at a temperature in excess of the ignition temperature
of the specific gas or vapor. Class II equipment shall not have an external
temperature higher than that specified in Section 500-3(f). Class III equipment shall not exceed the maximum surface temperatures specified in Section 503-1.
Equipment that has been approved for a Division 1 location shall be permitted in a Division 2 location of the same class and group.
Where specifically permitted in Articles 501 through 503, generalpurpose equipment or equipment in general-purpose enclosures shall be
permitted to be installed in Division 2 locations if the equipment does not
constitute a source of ignition under normal operating conditions.
Unless otherwise specified, normal operating conditions for motors shall
be assumed to be rated full-load steady conditions.
Where flammable gases or combustible dusts are or may be present at
the same time, the simultaneous presence of both shall be considered when
determining the safe operating temperature of the electrical equipment.
(FPN): The characteristics of various atmospheric mixtures of gases, vapors,
and dusts depend on the specific material involved.
(d) Marking. Approved equipment shall be marked to show the Class,
Group, and operating temperature or temperature range referenced to a
40°C ambient.
The temperature range, if provided, shall be indicated in identification
numbers, as shown in Table 500-3(d).
Identification numbers marked on equipment nameplates shall be in
accordance with Table 500-3(d).
Equipment that is approved for Class I and Class II shall be marked with
the maximum safe operating temperature, as determined by simultaneous
exposure to the combinations of Class I and Class II conditions.
Exception No. 1: Equipment of the nonheat-producing type, such as
junction boxes, conduit, and fittings and equipment of the heat-producing
type having a maximum temperature not more than 100°C (212°F) shall not
be required to have a marked operating temperature or temperature
range.
Exception No. 2: Fixed lighting fixtures marked for use in Class I, Division 2 or Class II, Division 2 locations only shall not be required to be
marked to indicate the group.
Exception No. 3: Fixed general-purpose equipment in Class I locations,
other than fixed lighting fixtures, that is acceptable for use in Class I,
Division 2 locations shall not be required to be marked with the Class,
Group, Division, or operating temperature.
ARTICLE 500 - HAZARDOUS (CLASSIFIED) LOCATIONS
70-469
Exception No. 4: Fixed dusttight equipment other than fixed lighting
fixtures that are acceptable for use in Class II, Division 2 and Class III
locations shall not be required to be marked with the Class, Group, Division, or operating temperature.
Table 500-3(d). Identification Numbers
I
Maximum
Temperature
Identification
Degrees C
Degrees F
Number
450
842
T1
300
572
T2
280
536
T2A
260
500
T2B
230
446
T2C
215
419
T2D
200
392
T3
180
356
T3A
165
329
T3B
160
320
T3C
135
275
T4
120
248
T4A
100
212
T5
85
185
T6
(FPN): Since there is no consistent relationship between explosion properties and ignition
temperature, the two are independent requirements.
(e) Class I Temperature. The temperature marking specified in (d) above
shall not exceed the ignition temperature of the specific gas or vapor to be
encountered.
(FPN): For information regarding ignition temperatures of gases and vapors, see
Classification of Gases, Vapors, and Dusts for Electrical Equipment in Hazardous
(Classified) Locations, NFPA 497M-1991, and Fire Hazard Properties of Flammable
Liquids, Gases, and Volatile Solids, NFPA 325M-1991.
Formerly, the temperature limit of each group was assumed to be the
lowest ignition temperature of any material in the group, i.e., 280°C (536°F)
for Group D and 180°C (356°F) for Group C.
(FPN): To avoid revising this limit as new gases are added (see hexane in Group
D and acetaldehyde in Group C), temperature will be specified in future markings.
The ignition temperature for which equipment was approved prior to this
requirement shall be assumed to be as follows:
Group A - 280°C (536°F)
Group C - 180°C (356°F)
Group B - 280°C (536°F)
Group D - 280°C (536°F)
70-470
NATIONAL ELECTRICAL CODE
(f) Class II Temperature. The temperature marking specified in (d)
above shall be less than the ignition temperature of the specific dust to be
encountered. For organic dusts that may dehydrate or carbonize, the temperature marking shall not exceed the lower of either the ignition temperature or 165°C (329°F). See Classification of Gases, Vapors, and Dusts for
Electrical Equipment in Hazardous (Classified) Locations, NFPA 497M-
1991, for minimum ignition temperatures of specific dusts.
The ignition temperature for which equipment was approved prior to this
requirement shall be assumed to be as shown in Table 500-3(f).
Table 500-3(f)
Equipment (such as Motors or Power
Transformers) that May Be Overloaded
Equipment that
is Not Subject
to Overloading
Normal Operation
Abnormal Operation
Class II
Degrees
Degrees
Degrees
Degrees
Degrees
Degrees
Group
C
F
C
F
C
F
E
200
392
200
392
200
392
F
200
392
150
302
200
392
G
165
329
120
248
165
329
500-4. Specific Occupancies. Articles 510 through 517 cover garages,
aircraft hangars, gasoline dispensing and service stations, bulk storage
plants, spray application, dipping and coating processes, and health care
facilities.
500-5. Class I Locations. Class I locations are those in which flammable
gases or vapors are or may be present in the air in quantities sufficient to
produce explosive or ignitible mixtures. Class I locations shall include
those specified in (a) and (b) below.
(a) Class I, Division 1. A Class I, Division 1 location is a location (1) in
which ignitible concentrations of flammable gases or vapors can exist
under normal operating conditions; or (2) in which ignitible concentrations
of such gases or vapors may exist frequently because of repair or maintenance operations or because of leakage; or (3) in which breakdown or
faulty operation of equipment or processes might release ignitible concentrations of flammable gases or vapors, and might also cause simultaneous
failure of electric equipment.
(FPN): This classification usually includes locations where volatile flammable
liquids or liquefied flammable gases are transferred from one container to another;
interiors of spray booths and areas in the vicinity of spraying and painting operations
where volatile flammable solvents are used; locations containing open tanks or vats
of volatile flammable liquids; drying rooms or compartments for the evaporation of
flammable solvents; locations containing fat and oil extraction equipment using volatile flammable solvents; portions of cleaning and dyeing plants where flammable
liquids are used; gas generator rooms and other portions of gas manufacturing
ARTICLE 500 - HAZARDOUS (CLASSIFIED) LOCATIONS
70-471
plants where flammable gas may escape; inadequately ventilated pump rooms for
flammable gas or for volatile flammable liquids; the interiors of refrigerators and
freezers in which volatile flammmable materials are stored in open, lightly stoppered, or easily ruptured containers; and all other locations where ignitible concentrations of flammable vapors or gases are likely to occur in the course of normal
operations.
(b) Class I, Division 2. A Class I, Division 2 location is a location (1) in
which volatile flammable liquids or flammable gases are handled, processed, or used, but in which the liquids, vapors, or gases will normally be
confined within closed containers or closed systems from which they can
escape only in case of accidental rupture or breakdown of such containers
or systems, or in case of abnormal operation of equipment; or (2) in which
ignitible concentrations of gases or vapors are normally prevented by positive mechanical ventilation, and which might become hazardous through
failure or abnormal operation of the ventilating equipment; or (3) that is
adjacent to a Class I, Division 1 location, and to which ignitible concentrations of gases or vapors might occasionally be communicated unless such
communication is prevented by adequate positive-pressure ventilation
from a source of clean air, and effective safeguards against ventilation failure are provided.
(FPN No. 1): This classification usually includes locations where volatile flammable liquids or flammable gases or vapors are used but that, in the judgment of the
authority having jurisdiction, would become hazardous only in case of an accident
or of some unusual operating condition. The quantity of flammable material that
might escape in case of accident, the adequacy of ventilating equipment, the total
area involved, and the record of the industry or business with respect to explosions
or fires are all factors that merit consideration in determining the classification and
extent of each location.
(FPN No. 2): Piping without valves, checks, meters, and similar devices would
not ordinarily introduce a hazardous condition even though used for flammable liquids or gases. Locations used for the storage of flammable liquids or of liquefied or
compressed gases in sealed containers would not normally be considered hazardous
unless subject to other hazardous conditions also.
Electrical conduits and their associated enclosures separated from process fluids by a single seal or barrier shall be classed as a Division 2 location if the outside of the conduit and enclosures is an unclassified location.
500-6. Class II Locations. Class II locations are those that are hazardous
because of the presence of combustible dust. Class II locations shall
include those specified in (a) and (b) below.
(a) Class II, Division 1. A Class II, Division 1 location is a location (1)
in which combustible dust is in the air under normal operating conditions
in quantities sufficient to produce explosive or ignitible mixtures; or (2)
where mechanical failure or abnormal operation of machinery or equipment might cause such explosive or ignitible mixtures to be produced, and
might also provide a source of ignition through simultaneous failure of
electric equipment, operation of protection devices, or from other causes;
or (3) in which combustible dusts of an electrically conductive nature may
be present in hazardous quantities.
(FPN): Combustible dusts that are electrically nonconductive include dusts produced in the handling and processing of grain and grain products, pulverized sugar
and cocoa, dried egg and milk powders, pulverized spices, starch and pastes, potato
70-472
NATIONAL ELECTRICAL CODE
and woodflour, oil meal from beans and seed, dried hay, and other organic materials that may produce combustible dusts when processed or handled. Only Group E
dusts are considered to be electrically conductive for classification purposes. Dusts
containing magnesium or aluminum are particularly hazardous, and the use of
extreme precaution will be necessary to avoid ignition and explosion.
(b) Class II, Division 2. A Class II, Division 2 location is a location
where combustible dust is not normally in the air in quantities sufficient to
produce explosive or ignitible mixtures, and dust accumulations are normally insufficient to interfere with the normal operation of electrical equipment or other apparatus, but combustible dust may be in suspension in the
air as a result of infrequent malfunctioning of handling or processing equipment and where combustible dust accumulations on, in, or in the vicinity
of the electrical equipment may be sufficient to interfere with the safe dissipation of heat from electrical equipment or may be ignitible by abnormal
operation or failure of electrical equipment.
(FPN No. 1): The quantity of combustible dust that may be present and the
adequacy of dust removal systems are factors that merit consideration in determining the classification and may result in an unclassified area.
(FPN No. 2): Where products such as seed are handled in a manner that
produces low quantities of dust, the amount of dust deposited may not warrant
classification.
500-7. Class III Locations. Class III locations are those that are hazardous because of the presence of easily ignitible fibers or flyings, but in which
such fibers or flyings are not likely to be in suspension in the air in quantities sufficient to produce ignitible mixtures. Class III locations shall include
those specified in (a) and (b) below.
(a) Class III, Division 1. A Class III, Division 1 location is a location in
which easily ignitible fibers or materials producing combustible flyings are
handled, manufactured, or used.
(FPN No. 1): Such locations usually include some parts of rayon, cotton, and
other textile mills; combustible fiber manufacturing and processing plants; cotton
gins and cotton-seed mills; flax-processing plants; clothing manufacturing plants;
woodworking plants; and establishments and industries involving similar hazardous
processes or conditions.
(FPN No. 2): Easily ignitible fibers and flyings include rayon, cotton (including
cotton linters and cotton waste), sisal or henequen, istle, jute, hemp, tow, cocoa
fiber, oakum, baled waste kapok, Spanish moss, excelsior, and other materials of
similar nature.
(b) Class III, Division 2. A Class III, Division 2 location is a location in
which easily ignitible fibers are stored or handled.
Exception: In process of manufacture.