Regl. 5293, art. 384-32-501 dup2
CLASS 1 LOCATIONS
Cite as Reglamento Núm. 5293, Art. 384-32-501 dup2
70-475
SNM cable with approved termination fittings shall be the wiring method
employed. Type PLTC, MI, MC, MV, TC, or SNM cable shall be permitted to be installed in cable tray systems and shall be installed in a manner
to avoid tensile stress at the termination fittings. Boxes, fittings, and joints
shall not be required to be explosionproof except as required by Sections
501-3(b)(1), 501-6(b)(1), and 501-14(b)(1). Where provision must be made
for limited flexibility, as at motor terminals, flexible metal fittings, flexible
metal conduit with approved fittings, liquidtight flexible metal conduit with
approved fittings, liquidtight flexible nonmetallic conduit with approved
fittings, or flexible cord approved for extra-hard usage and provided with
approved bushed fittings shall be used. An additional conductor for
grounding shall be included in the flexible cord.
(FPN): See Section 501-16(b) for grounding requirements where flexible conduit
is used.
Exception: Wiring in nonincendive circuits shall be permitted using any
of the methods suitable for wiring in ordinary locations.
501-5. Sealing and Drainage. Seals in conduit and cable systems shall
comply with (a) through (f) below. Sealing compound shall be of a type
approved for the conditions and use. Sealing compound shall be used in
Type MI cable termination fittings to exclude moisture and other fluids
from the cable insulation.
(FPN No. 1): Seals are provided in conduit and cable systems to minimize the
passage of gases and vapors and prevent the passage of flames from one portion of
the electrical installation to another through the conduit. Such communication
through Type MI cable is inherently prevented by construction of the cable. Unless
specifically designed and tested for the purpose, conduit and cable seals are not
intended to prevent the passage of liquids, gases, or vapors at a continuous pressure
differential across the seal. Even at differences in pressure across the seal equivalent to a few inches of water, there may be a slow passage of gas or vapor through
a seal, and through conductors passing through the seal. See Section 501-5(e)(2).
Temperature extremes and highly corrosive liquids and vapors can affect the ability
of seals to perform their intended function. See Section 501-5(c)(2).
(FPN No. 2): Gas or vapor leakage and propagation of flames may occur
through the interstices between the strands of standard stranded conductors larger
than No. 2. Special conductor constructions, e.g., compacted strands or sealing of
the individual strands, are means of reducing leakage and preventing the propagation of flames.
(a) Conduit Seals, Class I, Division 1. In Class I, Division: 1 locations,
conduit seals shall be located as follows:
(1) In each conduit run entering an enclosure for switches, circuit
breakers, fuses, relays, resistors, or other apparatus that may produce
arcs, sparks, or high temperatures. Seals shall be installed within 18 inches
(457 mm) from such enclosures. Explosionproof unions, couplings, reducers, elbows, capped elbows, and conduit bodies similar to "L," "T," and
"Cross" types shall be the only enclosures or fittings permitted between
the sealing fitting and the enclosure. The conduit bodies shall not be larger
than the largest trade size of the conduits.
Exception: Conduit 1½ inches and smaller entering an explosionproof
enclosure for switches, circuit breakers, fuses, relays, or other apparatus
that may produce arcs or sparks shall not be required to be sealed if the
current-interrupting contacts are:
70-476
NATIONAL ELECTRICAL CODE
a. Enclosed within a chamber hermetically sealed against the
entrance of gases or vapors, or
b. Immersed in oil in accordance with Section 501-6(b)(1)(2).
(2) In each conduit of 2-inch size or larger entering the enclosure or
fitting housing terminals, splices, or taps and within 18 inches (457 mm) of
such enclosure or fitting.
(FPN): See Section 500-3(c)(2).
(3) Where two or more enclosures for which seals are required under
(a)(1) and (a)(2) above are connected by nipples or by runs of conduit not
more than 36 inches (914 mm) long, a single seal in each such nipple connection or run of conduit shall be considered sufficient if located not more
than 18 inches (457 mm) from either enclosure.
(4) In each conduit run leaving the Class I, Division 1 location. The
sealing fitting shall be permitted on either side of the boundary of such
location but shall be so designed and installed to minimize the amount of
gas or vapor that may have entered the conduit system within the Division
1 location from being communicated to the conduit beyond the seal. There
shall be no union, coupling, box, or fitting in the conduit between the
sealing fitting and the point at which the conduit leaves the Division 1
location.
Exception: Metal conduit containing no unions, couplings, boxes, or
fittings that passes completely through a Class I, Division 1 location with
no fittings less than 12 inches (305 mm) beyond each boundary shall not be
required to be sealed if the termination points of the unbroken conduit are
in unclassified locations.
(b) Conduit Seals, Class I, Division 2. In Class I, Division 2 locations,
conduit seals shall be located as follows:
(1) For connections to explosionproof enclosures that are required to
be approved for Class I locations, seals shall be provided in accordance
with (a)(1), (a)(2), and (a)(3) above. All portions of the conduit run or
nipple between the seal and such enclosure shall comply with Section
501-4(a).
(2) In each conduit run passing from a Class I, Division 2 location into
an unclassified location. The sealing fitting shall be permitted on either side
of the boundary of such location but shall be so designed and installed to
minimize the amount of gas or vapor that may have entered the conduit
system within the Division 2 location from being communicated to the
conduit beyond the seal. Rigid metal conduit or threaded steel intermediate metal conduit shall be used between the sealing fitting and the point at
which the conduit leaves the Division 2 location, and a threaded connection shall be used at the sealing fitting. There shall be no union, coupling,
box, or fitting in the conduit between the sealing fitting and the point at
which the conduit leaves the Division 2 location.
Exception No. 1: Metal conduit containing no unions, couplings, boxes,
or fittings that passes completely through a Class I, Division 2 location
with no fittings less than 12 inches (305 mm) beyond each boundary shall
not be required to be sealed if the cermination points of the unbroken conduit are in unclassified locations.
ARTICLE 501 - CLASS I LOCATIONS
70-477
Exception No. 2: Conduit systems terminating at an outdoor unclassified location where a wiring method transition is made to cable tray, cablebus, ventilated busway, Type MI cable, or open wiring shall not be
required to be sealed where passing from the Class I, Division 2 location
into the unclassified area. The conduits shall not terminate at an enclosure
containing an ignition source.
(c) Class I, Divisions 1 and 2. Where required, seals in Class I, Division
1 and 2 locations shall comply with the following:
(1) Fittings. Enclosures for connections or equipment shall be provided with an approved integral means for sealing, or sealing fittings
approved for Class I locations shall be used. Sealing fittings shall be
accessible.
(2) Compound. Sealing compound shall be approved and shall provide a seal against passage of gas or vapors through the seal fitting, shall
not be affected by the surrounding atmosphere or liquids, and shall not
have a melting point of less than 93°C (200°F).
(3) Thickness of Compounds. In a completed seal, the minimum
thickness of the sealing compound shall not be less than the trade size of
the conduit and, in no case, less than 5/₈ inch (16 mm).
(4) Splices and Taps. Splices and taps shall not be made in fittings
intended only for sealing with compound, nor shall other fittings in which
splices or taps are made be filled with compound.
(5) Assemblies. In an assembly where equipment that may produce
arcs, sparks, or high temperatures is located in a compartment separate
from the compartment containing splices or taps, and an integral seal is
provided where conductors pass from one compartment to the other, the
entire assembly shall be approved for Class I locations. Seals in conduit
connections to the compartment containing splices or taps shall be provided in Class I, Division 1 locations where required by (a)(2) above.
(d) Cable Seals, Class I, Division 1. In Class I, Division 1 locations,
each multiconductor cable in conduit shall be considered as a single conductor if the cable is incapable of transmitting gases or vapors through the
cable core. These cables shall be sealed in accordance with (a) above.
Cables with a gas/vapor-tight continuous sheath capable of transmitting
gases or vapors through the cable core shall be sealed in the Division 1
location after removing the jacket and any other coverings so that the sealing compound will surround each individual insulated conductor and the
outer jacket.
Exception: Multiconductor cables with a gas/vapor-tight continuous
sheath capable of transmitting gases or vapors through the cable core
shall be permitted to be considered as a single conductor by sealing the
cable in the conduit within 18 inches (457 mm) of the enclosure and the
cable end within the enclosure by an approved means to prevent the
entrance of gases or vapors or propagation of flame into the cable core,
or by other approved methods.
(e) Cable Seals, Class I, Division 2. In Class I, Division 2 locations,
cable seals shall be located as follows:
70-478
NATIONAL ELECTRICAL CODE
(1) Cables entering enclosures that are required to be approved for
Class I locations shall be sealed at the point of entrance. The sealing fitting
shall comply with (b)(1) above. Multiconductor cables with a gas/vaportight continuous sheath capable of transmitting gases or vapors through the
cable core shall be sealed in an approved fitting in the Division 2 location
after removing the jacket and any other coverings so that the sealing compound will surround each individual insulated conductor in such a manner
as to minimize the passage of gases and vapors. Multiconductor cables in
conduit shall be sealed as described in (d) above.
(2) Cables with a gas/vapor-tight continuous sheath and that will not
transmit gases or vapors through the cable core in excess of the quantity
permitted for seal fittings shall not be required to be sealed except as
required in (e)(1) above. The minimum length of such cable run shall
not be less than that length that limits gas or vapor flow through the cable
core to the rate permitted for seal fittings [0.007 cubic feet per hour
(198 cubic centimeters per hour) of air at a pressure of 6 inches of water
(1493 pascals)].
(FPN No. 1): See Outlet Boxes and Fittings for Use in Hazardous Locations,
ANSI/UL 886-1985.
(FPN No. 2): The cable core does not include the interstices of the conductor
strands.
(3) Cables with a gas/vapor-tight continuous sheath capable of transmitting gases or vapors through the cable core shall not be required to be
sealed except as required in (e)(1) above, unless the cable is attached to
process equipment or devices that may cause a pressure in excess of
6 inches (1493 pascals) of water to be exerted at a cable end, in which case
a seal, barrier, or other means shall be provided to prevent migration of
flammables into an unclassified area.
Exception: Cables with an unbroken gas/vapor-tight continuous sheath
shall be permitted to pass through a Class I, Division 2 location without
seals.
(4) Cables that do not have gas/vapor-tight continuous sheath shall be
sealed at the boundary of the Division 2 and unclassified location in such a
manner as to minimize the passage of gases or vapors into an unclassified
location.
(FPN): The sheath mentioned in (d) and (e) above may be either metal or a nonmetallic material.
(f) Drainage.
(1) Control Equipment. Where there is a probability that liquid or
other condensed vapor may be trapped within enclosures for control
equipment or at any point in the raceway system, approved means shall be
provided to prevent accumulation or to permit periodic draining of such
liquid or condensed vapor.
(2) Motors and Generators. Where the authority having jurisdiction
judges that there is a probability that liquid or condensed vapor may accumulate within motors or generators, joints and conduit systems shall be
arranged to minimize entrance of liquid. If means to prevent accumulation
or to permit periodic draining are judged necessary, such means shall be
provided at the time of manufacture and shall be considered an integral
part of the machine.
ARTICLE 501 - CLASS I LOCATIONS
70-479
(3) Canned Pumps, Process or Service Connections, Etc. For canned
pumps, process or service connections for flow, pressure, or analysis measurement, etc., that depend upon a single compression seal, diaphragm, or
tube to prevent flammable or combustible fluids from entering the electrical conduit system, an additional approved seal, barrier, or other means
shall be provided to prevent the flammable or combustible fluid from entering the conduit system beyond the additional devices or means, if the primary seal fails.
The additional approved seal or barrier and the interconnecting enclosure shall meet the temperature and pressure conditions to which they will
be subjected upon failure of the primary seal, unless other approved means
are provided to accomplish the purpose above.
Drains, vents, or other devices shall be provided so that primary seal
leakage will be obvious.
(FPN): See also the last paragraph of Section 500-5(b) and Fine Print Notes to