Regl. 5293, art. 384-32-710
This limit shall apply to any single unit in an installation of
Cite as Reglamento Núm. 5293, Art. 384-32-710
capacitors.
(b) Accidental Contact. Capacitors shall be enclosed, located, or
guarded so that persons cannot come into accidental contact or bring conducting materials into accidental contact with exposed energized parts,
terminals, or buses associated with them.
Exception: No additional guarding is required for enclosures accessible
only to authorized and qualified persons.
A. 600 Volts, Nominal, and Under
460-6. Discharge of Stored Energy. Capacitors shall be provided with a
means of discharging stored energy.
(a) Time of Discharge. The residual voltage of a capacitor shall be
reduced to 50 volts, nominal, or less, within 1 minute after the capacitor is
disconnected from the source of supply.
(b) Means of Discharge. The discharge circuit shall be either permanently connected to the terminals of the capacitor or capacitor bank, or
provided with automatic means of connecting it to the terminals of the
capacitor bank on removal of voltage from the line. Manual means of
switching or connecting the discharge circuit shall not be used.
460-8. Conductors.
(a) Ampacity. The ampacity of capacitor circuit conductors shall not be
less than 135 percent of the rated current of the capacitor. The ampacity of
conductors that connect a capacitor to the terminals of a motor or to motor
circuit conductors shall not be less than one third the ampacity of the
motor circuit conductors and in no case less than 135 percent of the rated
current of the capacitor.
(b) Overcurrent Protection.
(1) An overcurrent device shall be provided in each ungrounded conductor for each capacitor bank.
Exception: A separate overcurrent device shall not be required for a
capacitor connected on the load side of a motor overload protective
device.
(2) The rating or setting of the overcurrent device shall be as low as
practicable.
(c) Disconnecting Means.
(1) A disconnecting means shall be provided in each ungrounded conductor for each capacitor bank.
Exception: Where a capacitor is connected on the load side of a motor
overload protective device.
70-460
NATIONAL ELECTRICAL CODE
(2) The disconnecting means shall open all ungrounded conductors
simultaneously.
(3) The disconnecting means shall be permitted to disconnect the
capacitor from the line as a regular operating procedure.
(4) The rating of the disconnecting means shall not be less than 135
percent of the rated current of the capacitor.
460-9. Rating or Setting of Motor Overload Device. Where a motor
installation includes a capacitor connected on the load side of the motor
overload device, the rating or setting of the motor overload device shall be
based on the improved power factor of the motor circuit.
The effect of the capacitor shall be disregarded in determining the motor
circuit conductor rating in accordance with Section 430-22.
460-10. Grounding. Capacitor cases shall be grounded in accordance
with Article 250.
Exception: Where the capacitor units are supported on a structure that
is designed to operate at other than ground potential.
460-12. Marking. Each capacitor shall be provided with a nameplate giving the name of the manufacturer, rated voltage, frequency, kilovar or
amperes, number of phases, and, if filled with a combustible liquid, the
amount of liquid in gallons. Where filled with a nonflammable liquid, the
nameplate shall so state. The nameplate shall also indicate if a capacitor
has a discharge device inside the case.
B. Over 600 Volts, Nominal
460-24. Switching.
(a) Load Current. Group-operated switches shall be used for capacitor
switching and shall be capable of (1) carrying continuously not less than
135 percent of the rated current of the capacitor installation; (2) interrupting the maximum continuous load current of each capacitor, capacitor
bank, or capacitor installation that will be switched as a unit; (3) withstanding the maximum inrush current, including contributions from adjacent
capacitor installations; (4) carrying currents due to faults on capacitor side
of switch.
(b) Isolation.
(1) A means shall be installed to isolate from all sources of voltage each
capacitor, capacitor bank, or capacitor installation that will be removed from
service as a unit.
(2) The isolating means shall provide a visible gap in the electrical circuit adequate for the operating voltage.
(3) Isolating or disconnecting switches (with no interrupting rating)
shall be interlocked with the load-interrupting device or shall be provided
with prominently displayed caution signs in accordance with Section
710-22 to prevent switching load current.
ARTICLE 460 - CAPACITORS
70-461
(c) Additional Requirements for Series Capacitors. The proper switching sequence shall be assured by use of one of the following: (1) mechanically sequenced isolating and bypass switches; (2) interlocks; or (3) switching procedure prominently displayed at the switching location.
460-25. Overcurrent Protection.
(a) Provided to Detect and Interrupt Fault Current. A means shall be
provided to detect and interrupt fault current likely to cause dangerous
pressure within an individual capacitor.
(b) Single-Phase or Multiphase Devices. Single-phase or multiphase
devices shall be permitted for this purpose.
(c) Protected Individually or in Groups. Capacitors shall be permitted to
be protected individually or in groups.
(d) Protective Devices Rated or Adjusted. Protective devices for capacitors or capacitor equipment shall be rated or adjusted to operate within the
limits of the safe zone for individual capacitors.
Exception: If the protective devices are rated or adjusted to operate
within the limits for Zone 1 or Zone 2, the capacitors shall be enclosed or
isolated.
In no event shall the rating or adjustment of the protective devices
exceed the maximum limit of Zone 2.
(FPN): For definitions of the Safe Zone, Zone 1, and Zone 2, see Shunt Power
Capacitors, ANSI/IEEE 18-1980.
460-26. Identification. Each capacitor shall be provided with a permanent nameplate giving the maker's name, rated voltage, frequency, kilovar
or amperes, number of phases, and the amount of liquid in gallons identified as flammable, if such is the case.
460-27. Grounding. Capacitor neutrals and cases, if grounded, shall be
grounded in accordance with Article 250.
Exception: Where the capacitor units are supported on a structure that
is designed to operate at other than ground potential.
460-28. Means for Discharge.
(a) Means to Reduce the Residual Voltage. A means shall be provided
to reduce the residual voltage of a capacitor to 50 volts or less within 5
minutes after the capacitor is disconnected from the source of supply.
(b) Connection to Terminals. A discharge circuit shall be either permanently connected to the terminals of the capacitor or provided with automatic means of connecting it to the terminals of the capacitor bank after
disconnection of the capacitor from the source of supply. The windings of
motors, or transformers, or of other equipment directly connected to
capacitors without a switch or overcurrent device interposed shall meet the
requirements of (a) above.
70-462
NATIONAL ELECTRICAL CODE