Regl. 5293, art. 400-22
Resolución 2535: adopta el Código Eléctrico Nacional, versión 1993. (Sustituye el Anejo A del Reglamento 4435)
Cite as Reglamento Núm. 5293, Art. 400-22
(d) Grounded Conductors of Different Systems. Where conductors of
different systems are installed in the same raceway, box, auxiliary gutter,
or other type of enclosure, one system grounded conductor, if required,
shall have an outer covering conforming to Section 200-6(a) or (b). Each
other system grounded conductor, if required, shall have an outer covering
of white with an identifiable colored stripe (not green) running along the
insulation, or other and different means of identification as allowed by