Regl. 5293, art. 400-7-553
FLOATING BUILDINGS
Cite as Reglamento Núm. 5293, Art. 400-7-553
70-627
(FPN): For clearances of conductors over 600 volts, nominal, see National
Electrical Safety Code, ANSI C2-1990.
551-80. Underground Service, Feeder, Branch-Circuit and Recreational
Vehicle Site Feeder Circuit Conductors.
(a) General. All direct-burial conductors, including the equipment
grounding conductor if of aluminum, shall be insulated and identified for
the use. All conductors shall be continuous from equipment to equipment.
All splices and taps shall be made in approved junction boxes or by use of
material listed and identified for the purpose.
(b) Protection Against Physical Damage. Direct-buried conductors and
cables entering or leaving a trench shall be protected by rigid metal conduit, intermediate metal conduit, electrical metallic tubing with supplementary corrosion protection, rigid nonmetallic conduit, or other approved
raceways or enclosures. Where subject to physical damage, the conductors
or cables shall be protected by rigid metal conduit, intermediate conduit,
or Schedule 80 rigid nonmetallic conduit. All such protection shall extend
at least 18 inches (457 mm) into the trench from finished grade.
(FPN): See Section 300-5 and Article 339 for conductors or Type UF cable used
underground or in direct burial in earth.
551-81. Receptacles. A receptacle to supply electric power to a recreational vehicle shall be one of the configurations shown in Figure 551-46(c)
in the following ratings:
(a) 50-Ampere. 125/250 volts, 50-ampere, 3-pole, 4-wire, grounding type
for 120/240-volt systems.
(b) 30-Ampere. 125-volt, 30-ampere, 2-pole, 3-wire, grounding type for
120-volt systems.
(c) 20-Ampere. 125-volt, 20-ampere, 2-pole, 3-wire, grounding type for
120-volt systems.
(FPN): Complete details of these configurations can be found in American
National Standard Dimensions of Caps, Plugs and Receptacles, ANSI C73.17-1972;
ANSI C73.13-1972; and C73.12-1972.