Regl. 5293, art. 400-7-553 dup2
FLOATING BUILDINGS
Cite as Reglamento Núm. 5293, Art. 400-7-553 dup2
A. General
553-1. Scope. This article covers wiring, services, feeders, and grounding for floating buildings.
553-2. Definition.
Floating Building. A building unit as defined in Article 100 that floats
on water, is moored in a permanent location, and has a premises wiring
system served through connection by permanent wiring to an electricity
supply system not located on the premises.
70-628
NATIONAL ELECTRICAL CODE
553-3. Application of Other Articles. Wiring for floating buildings shall
comply with the applicable provisions of other articles of this Code, except
as modified by this article.
B. Services and Feeders
553-4. Location of Service Equipment. The service equipment for a
floating building shall be located adjacent to, but not in or on, the building.
553-5. Service Conductors. One set of service conductors shall be permitted to serve more than one set of service equipment.
553-6. Feeder Conductors. Each floating building shall be supplied by a
single set of feeder conductors from its service equipment.
Exception: Where the floating building has multiple occupancy, each
occupant shall be permitted to be supplied by a single set of feeder conductors extended from the occupant's service equipment to the occupant's
panelboard.
553-7. Installation of Services and Feeders.
(a) Flexibility. Flexibility of the wiring system shall be maintained
between floating buildings and the supply conductors. All wiring shall be
so installed that motion of the water surface and changes in the water level
will not result in unsafe conditions.
(b) Wiring Methods. Liquidtight flexible metal conduit or liquidtight
flexible nonmetallic conduit with approved fittings shall be permitted for
feeders and where flexible connections are required for services. Extrahard usage portable power cable listed for both wet locations and sunlight
resistance shall be permitted for a feeder to a floating building where flexibility is required.
(FPN): See Sections 555-1 and 555-6.
C. Grounding
553-8. General Requirements. Grounding of both electrical and nonelectrical parts in a floating building shall be through connection to a grounding
bus in the building panelboard. The grounding bus shall be grounded
through a green-colored insulated equipment grounding conductor run with
the feeder conductors and connected to a grounding terminal in the service
equipment. The grounding terminal in the service equipment shall be
grounded by connection through a green insulated grounding electrode
conductor to a grounding electrode on shore.
553-9. Insulated Neutral. The grounded circuit conductor (neutral) shall
be a white insulated conductor. The neutral conductor shall be connected
to the equipment grounding terminal in the service equipment, and, except
for that connection, it shall be insulated from the equipment grounding
conductors, equipment enclosures, and all other grounded parts. The neutral circuit terminals in the panelboard and in ranges, clothes dryers,
counter-mounted cooking units, and the like shall be insulated from the
enclosures.