Regl. 5293, art. 400-7-605

OFFICE FURNISHINGS

Last amended: 1993Length: 198 wordsOfficial source

Cite as Reglamento Núm. 5293, Art. 400-7-605

(Consisting of Lighting Accessories and Wired Partitions) 605-1. Scope. This article covers electrical equipment, lighting accessories, and wiring systems used to connect, or contained within, or installed on relocatable wired partitions. 605-2. General. Wiring systems shall be identified as suitable for providing power for lighting accessories and appliances in wired partitions. These partitions shall not extend from floor to ceiling. Exception: Where permitted by the authority having jurisdiction, these relocatable wired partitions shall be permitted to extend to the ceiling but shall not penetrate the ceiling. (a) Use. These assemblies shall be installed and used only as provided for by this article. (b) Other Articles. Except as modified by the requirements of this article, all other articles of this Code shall apply. (c) Hazardous (Classified) Locations. Where used in hazardous (classified) locations, these assemblies shall conform with Articles 500 through 517 in addition to this article. 605-3. Wireways. All conductors and connections shall be contained within wiring channels of metal or other material identified as suitable for the conditions of use. Wiring channels shall be free of projections or other conditions that may damage conductor insulation. (FPN): Conductors as used in this section do not include flexible cord.