Regl. 5293, art. 410-67(c)-250
Resolución 2535: adopta el Código Eléctrico Nacional, versión 1993. (Sustituye el Anejo A del Reglamento 4435)
Cite as Reglamento Núm. 5293, Art. 410-67(c)-250
70-270
NATIONAL ELECTRICAL CODE
B. Nonmetallic Wireways
362-14. Definition. Nonmetallic wireways are flame-retardant, nonmetallic troughs with removable covers for housing and protecting electric wires
and cables in which conductors are laid in place after the wireway has been
installed as a complete system.
362-15. Uses Permitted. The use of nonmetallic wireways shall be permitted:
(1) Only for exposed work.
Exception: Nonmetallic wireways shall be permitted in concealed
spaces in accordance with Section 640-4, Exception, item C.
(2) Where subject to corrosive vapors.
(3) In wet locations where listed for the purpose.
(FPN): Extreme cold may cause nonmetallic wireways to become brittle and,
therefore, more susceptible to damage from physical contact.
362-16. Uses Not Permitted. Nonmetallic wireways shall not be used:
(1) Where subject to physical damage.
(2) In any hazardous (classified) location.
Exception: As permitted in Section 504-20.
(3) Where exposed to sunlight unless listed and marked as suitable for
the purpose.
(4) Where subject to ambient temperatures other than those for which
nonmetallic wireway is listed.
362-17. Other Articles. Installations of nonmetallic wireways shall comply with the applicable provisions of Article 300. Where equipment grounding is required by Article 250, a separate equipment grounding conductor
shall be installed in the nonmetallic wireway.
362-18. Size of Conductors. No conductor larger than that for which the
nonmetallic wireway is designed shall be installed in any nonmetallic wireway.
362-19. Number of Conductors. The sum of cross-sectional areas of all
contained conductors at any cross section of the nonmetallic wireway shall
not exceed 20 percent of the interior cross-sectional area of the nonmetallic wireway. Conductors for signaling circuits or controller conductors
between a motor and its starter and used only for starting duty shall not be
considered as current-carrying conductors.
The derating factors specified in Article 310, Note 8(a) of Notes to
Ampacity Tables of 0 to 2000 Volts shall be applicable to the currentcarrying conductors at the 20 percent fill specified above.
(FPN): For conductor cross-sectional area, see Tables 5, 5A, 6, and 8 and the
applicable Notes to Tables at the beginning of Chapter 9.
362-20. Deflected Insulated Conductors. Where insulated conductors
are deflected within a nonmetallic wireway, either at the ends or where