Regl. 5293, art. 410-67(c)-351 dup3
LIQUIDTIGHT FLEXIBLE CONDUIT
Cite as Reglamento Núm. 5293, Art. 410-67(c)-351 dup3
70-259
(2) Where protection of the contained conductors is required from
vapors, liquids, or solids;
(3) For outdoor locations where listed and marked as suitable for the
purpose.
(FPN): For marking requirements, see Section 110-21.
(4) For direct burial where listed and marked for the purpose.
(b) Not Permitted. Liquidtight flexible nonmetallic conduit shall not be
used:
(1) Where subject to physical damage;
(2) Where any combination of ambient and conductor temperatures is
in excess of that for which the liquidtight flexible nonmetallic conduit is
approved;
(3) In lengths longer than 6 feet (1.83 m).
Exception: Where longer length is essential for a required degree of
flexibility.
(4) Where voltage of the contained conductors is in excess of 600
volts, nominal.
Exception: As permitted in Section 600-31(a), Exception for electric
signs over 600 volts.
351-24. Size. The sizes of liquidtight flexible nonmetallic conduit shall be
electrical trade sizes ½ inch to 4 inch inclusive.
Exception No. 1: ³/₈-inch size for enclosing the leads of motors as permitted in Section 430-145(b).
Exception No. 2: ³/₈-inch trade size shall be permitted in lengths not in
excess of 6 feet (1.83 m) as a part of a listed assembly, for tap connections
to lighting fixtures as required in Section 410-67(c), or for utilization equipment. See Table 350-3 for conduit fill.
Exception No. 3: ³/₈-inch trade size for electric sign conductors on insulators in accordance with Section 600-31(a).
351-25. Number of Conductors. The number of conductors permitted in
a single conduit shall be in accordance with the percentage fill specified in
Table 1, Chapter 9.
351-26. Fittings. Liquidtight flexible nonmetallic conduit shall be used
only with terminal fittings identified for such use. Angle connectors shall
not be used for concealed raceway installations.
351-28. Equipment Grounding. Where an equipment grounding conductor is required for the circuits installed in liquidtight flexible nonmetallic
conduit, it shall be permitted to be installed on the inside or outside of the
conduit. Where installed on the outside, the length of the equipment
grounding conductor shall not exceed 6 feet (1.83 m) and shall be routed
with the raceway or enclosure. Fittings and boxes shall be bonded or
grounded in accordance with Article 250.
70-260
NATIONAL ELECTRICAL CODE
351-29. Splices and Taps. Splices and taps shall be made only in junction boxes, outlet boxes, device boxes, or conduit bodies. See Article 370.
351-30. Bends - Number in One Run. There shall not be more than the
equivalent of four quarter bends (360 degrees total) between pull points,
e.g., conduit bodies and boxes.