Regl. 5293, art. 410-67(c)-353

MULTIOUTLET ASSEMBLY

Last amended: 1993Length: 137 wordsOfficial source

Cite as Reglamento Núm. 5293, Art. 410-67(c)-353

353-1. Other Articles. A multioutlet assembly shall comply with applicable provisions of Article 300. (FPN): See definition in Article 100. 353-2. Use. The use of a multioutlet assembly shall be permitted in dry locations. It shall not be installed (1) where concealed, except that it shall be permissible to surround the back and sides of a metal multioutlet assembly by the building finish or recess a nonmetallic multioutlet assembly in a baseboard; (2) where subject to severe physical damage; (3) where the voltage is 300 volts or more between conductors unless the assembly is of metal having a thickness of not less than .040 inch (1.02 mm); (4) where subject to corrosive vapors; (5) in hoistways; nor (6) in any hazardous (classified) locations except Class I, Division 2 locations as permitted in the exception to Section 501-4(b).