Regl. 5293, art. 410-67(c)-362 dup2
METAL AND NONMETALLIC WIREWAYS
Cite as Reglamento Núm. 5293, Art. 410-67(c)-362 dup2
70-269
Exception No. 2: As provided in Section 520-5, the thirty-conductor limitation shall not apply to theaters and similar locations.
Exception No. 3: As provided in Section 620-32, the 20-percent fill limitation shall not apply to elevators and dumbwaiters.
(FPN): For conductor cross-sectional area, see Tables 5, 5A, 6, and 8 and the
applicable Notes to Tables at the beginning of Chapter 9.
362-6. Deflected Insulated Conductors. Where insulated conductors are
deflected within a wireway, either at the ends or where conduits, fittings,
or other raceways or cables enter or leave the wireway, or where the
direction of the wireway is deflected greater than 30 degrees, dimensions
corresponding to Section 373-6 shall apply.
362-7. Splices and Taps. Splices and taps shall be permitted within a
wireway provided they are accessible. The conductors, including splices
and taps, shall not fill the wireway to more than 75 percent of its area at
that point.
362-8. Supports. Wireways shall be supported at intervals not to exceed
5 feet (1.52 m), or for individual lengths longer than 5 feet (1.52 m) at each
end or joint, unless listed for other support intervals. In no case shall the
distance between supports exceed 10 feet (3.05 m).
Exception: Vertical runs of wireways shall be securely supported at
intervals not exceeding 15 feet (4.57 m) and shall have not more than one
joint between supports. Adjoining wireway sections shall be securely fastened together to provide a rigid joint.
362-9. Extension Through Walls. Unbroken lengths of wireway shall be
permitted to pass transversely through walls if in unbroken lengths where
passing through.
362-10. Dead Ends. Dead ends of wireways shall be closed.
362-11. Extensions from Wireways. Extensions from wireways shall be
made with cord pendants or any wiring method in Chapter 3 that includes
a means for equipment grounding. Where a separate equipment grounding
conductor is employed, connection of the equipment grounding conductors
in the wiring method to the wireway shall comply with Sections 250-113
and 250-118. Where rigid nonmetallic conduit, electrical nonmetallic tubing, or liquidtight flexible nonmetallic conduit is used, connection of the
equipment grounding conductor in the nonmetallic raceway to a metal
wireway shall comply with Sections 250-113 and 250-118.
362-12. Marking. Wireways shall be marked so that their manufacturer's
name or trademark will be visible after installation.
362-13. Grounding. Grounding shall be according to the provisions of