Regl. 5293, art. 422-27
Resolución 2535: adopta el Código Eléctrico Nacional, versión 1993. (Sustituye el Anejo A del Reglamento 4435)
Cite as Reglamento Núm. 5293, Art. 422-27
(FPN No. 2): For appliances employing unit switches, see Section 422-25.
422-22. Disconnection of Cord- and Plug-Connected Appliances.
(a) Separable Connector or an Attachment Plug and Receptacle. For
cord- and plug-connected appliances, an accessible separable connector or
an accessible plug and receptacle shall be permitted to serve as the disconnecting means. Other cord- and plug-connected appliances shall be provided with disconnecting means in accordance with Section 422-21.
(b) Connection at the Rear Base of a Range. For cord- and plugconnected household electric ranges, an attachment plug and receptacle
connection at the rear base of a range, if it is accessible from the front by
removal of a drawer, shall be considered as meeting the intent of Section
422-22(a).
(c) Rating. The rating of a receptacle or of a separable connector shall
not be less than the rating of any appliance connected thereto.
Exception: Demand factors authorized elsewhere in this Code shall be
permitted to be applied.
(d) Requirements for Attachment Plugs and Connectors. Attachment
plugs and connectors shall conform to the following:
(1) Live Parts. They shall be so constructed and installed as to guard
against inadvertent contact with live parts.
(2) Interrupting Capacity. They shall be capable of interrupting their
rated current without hazard to the operator.
ARTICLE 422 - APPLIANCES
70-357
(3) Interchangeability. They shall be so designed that they will not fit
into receptacles of lesser rating.
422-23. Polarity in Cord- and Plug-Connected Appliances. If the appliance is provided with a manually operated, line-connected, single-pole
switch for appliance on-off operation, an Edison-base lampholder, or a 15-
or 20-ampere receptacle, the attachment plug shall be of the polarized or
grounding type.
(FPN): For polarity of Edison-base lampholders, see Section 410-42(a).
422-24. Cord- and Plug-Connected Appliances Subject to Immersion.
Cord- and plug-connected portable freestanding hydromassage units and
hand-held hair dryers shall be constructed to provide protection for personnel against electrocution when immersed while in the "on" or "off"
position.
422-25. Unit Switch(es) as Disconnecting Means. A unit switch(es) with
a marked "off" position that is a part of an appliance and disconnects all
ungrounded conductors shall be permitted as the disconnecting means
required by this article where other means for disconnection are provided
in the following types of occupancies:
(a) Multifamily Dwellings. In multifamily dwellings, the other disconnecting means shall be within the dwelling unit, or on the same floor as the
dwelling unit in which the appliance is installed, and shall be permitted to
control lamps and other appliances.
(b) Two-Family Dwellings. In two-family dwellings, the other disconnecting means shall be permitted either inside or outside of the dwelling
unit in which the appliance is installed. In this case, an individual switch or
circuit breaker for the dwelling unit shall be permitted and shall also be
permitted to control lamps and other appliances.
(c) One-Family Dwellings. In one-family dwellings, the service disconnecting means shall be permitted to be the other disconnecting means.
(d) Other Occupancies. In other occupancies, the branch-circuit switch
or circuit breaker, where readily accessible for servicing of the appliance,
shall be permitted as the other disconnecting means.
422-26. Switch and Circuit Breaker to Be Indicating. Switches and circuit
breakers used as disconnecting means shall be of the indicating type.
422-27. Disconnecting Means for Motor-Driven Appliances. If a switch
or circuit breaker serves as the disconnecting means for a permanently
connected motor-driven appliance of more than 1/8 horsepower, it shall
be located within sight from the motor controller and shall comply with
Part I of Article 430.
Exception: A switch or circuit breaker that serves as the other disconnecting means as required in Section 422-25(a), (b), (c), or (d) shall be permitted to be out of sight from the motor controller of an appliance provided with a unit switch(es) with a marked "off" position and that
disconnects all ungrounded conductors.
70-358
NATIONAL ELECTRICAL CODE
422-28. Overcurrent Protection.
(a) Appliances. Appliances shall be protected against overcurrent in
accordance with (b) through (f) below and Sections 422-4 and 422-5.
Exception: Motors of motor-operated appliances shall be provided with
overload protection in accordance with Part C of Article 430. Hermetic
refrigerant motor-compressors in air-conditioning or refrigerating equipment shall be provided with overload protection in accordance with Part F
I
of Article 440. Where appliance overcurrent protective devices that are
separate from the appliance are required, data for selection of these
devices shall be marked on the appliance. The minimum marking shall be
that specified in Sections 430-7 and 440-4.
(b) Household-type Appliance with Surface Heating Elements. A
household-type appliance with surface heating elements having a maximum demand of more than 60 amperes computed in accordance with Table
220-19 shall have its power supply subdivided into two or more circuits,
each of which is provided with overcurrent protection rated at not over 50
amperes.
(c) Infrared Lamp Commercial and Industrial Heating Appliances.
Infrared lamp commercial and industrial heating appliances shall have
overcurrent protection not exceeding 50 amperes.
(d) Open-Coil or Exposed Sheathed-Coil Types of Surface Heating Elements in Commercial-type Heating Appliances. Open-coil or exposed
sheathed-coil types of surface heating elements in commercial-type heating
appliances shall be protected by overcurrent protective devices rated at not
over 50 amperes.
(e) Single Nonmotor-Operated Appliance. If the branch circuit supplies
a single nonmotor-operated appliance, the rating of overcurrent protection
shall (1) not exceed that marked on the appliance; (2) if the overcurrent
protection rating is not marked and the appliance is rated over 13.3
amperes, not exceed 150 percent of the appliance rated current; or (3) if the
overcurrent protection rating is not marked and the appliance is rated 13.3
amperes or less, not exceed 20 amperes.
Exception: Where 150 percent of appliance rating does not correspond
to a standard overcurrent device ampere rating, the next higher standard
rating shall be permitted.
(f) Electric Heating Appliances Employing Resistance-type Heating Elements Rated More than 48 Amperes. Electric heating appliances employing resistance-type heating elements rated more than 48 amperes shall have
the heating elements subdivided. Each subdivided load shall not exceed 48
amperes and shall be protected at not more than 60 amperes.
These supplementary overcurrent protective devices shall be (1) factoryinstalled within or on the heater enclosure or provided as a separate assembly by the heater manufacturer; (2) accessible, but need not be readily
accessible; and (3) suitable for branch-circuit protection.
The main conductors supplying these overcurrent protective devices
shall be considered branch-circuit conductors.
ARTICLE 422 - APPLIANCES
70-359
Exception No. 1: Household-type appliances with surface heating elements as covered in Section 422-28(b) and commercial-type heating appliances as covered in Section 422-28(d).
Exception No. 2: Commercial kitchen and cooking appliances using
sheathed-type heating elements not covered in Section 422-28(d) shall be
permitted to be subdivided into circuits not exceeding 120 amperes and
protected at not more than 150 amperes where one of the following is met:
a. Elements are integral with and enclosed within a cooking surface;
b. Elements are completely contained within an enclosure identified
as suitable for this use; or
c. Elements are contained within an ASME rated and stamped
vessel.
Exception No. 3: Water heaters and steam boilers employing
resistance-type immersion electric heating elements contained in an
ASME rated and stamped vessel shall be permitted to be subdivided
into circuits not exceeding 120 amperes and protected at not more than
150 amperes.
E. Marking of Appliances
422-29. Cord- and Plug-Connected Pipe Heating Assemblies. Cord- and
plug-connected pipe heating assemblies intended to prevent freezing of
piping shall be listed.
422-30. Nameplate.
(a) Nameplate Marking. Each electric appliance shall be provided with
a nameplate giving the identifying name and the rating in volts and
amperes, or in volts and watts. If the appliance is to be used on a specific
frequency or frequencies, it shall be so marked.
Where motor overload protection external to the appliance is required,
the appliance shall be so marked.
(FPN): See Section 422-28(a), Exception for overcurrent protection requirements.
(b) To Be Visible. Marking shall be located so as to be visible or easily
accessible after installation.
422-31. Marking of Heating Elements. All heating elements that are rated
over one ampere, replaceable in the field, and a part of an appliance shall
be legibly marked with the ratings in volts and amperes, or in volts and
watts, or with the manufacturer's part number.
422-32. Appliances Consisting of Motors and Other Loads. Appliances
shall be marked in accordance with (a) or (b) below.
(a) Marking. In addition to the marking required in Section 422-30, the
marking on an appliance consisting of a motor with other load(s) or motors
with or without other load(s) shall specify the minimum supply circuit conductor ampacity and the maximum rating of the circuit overcurrent protective device.
70-360
NATIONAL ELECTRICAL CODE
Exception No. 1: Appliances factory-equipped with cords and attachment plugs, complying with Section 422-30.
Exception No. 2: An appliance where both the minimum supply circuit
conductor ampacity and maximum rating of the circuit overcurrent protective device are not more than 15 amperes and complies with Section 422-30.
(b) Alternate Marking Method. An alternate marking method shall be
permitted to specify the rating of the largest motor in volts and amperes,
and the additional load(s) in volts and amperes, or volts and watts in addition to the marking required in Section 422-30.
Exception No. 1: Appliances factory-equipped with cords and attachment plugs, complying with Section 422-30.
Exception No. 2: The ampere rating of a motor ¹/₈ horsepower or less
or a nonmotor load 1 ampere or less shall be permitted to be omitted
unless such loads constitute the principal load.