FIXED ELECTRIC SPACE HEATING EQUIPMENT 70-361

Last amended: 1993Length: 136 wordsOfficial source

Cite as Reglamento Núm. 5293, Art. 422-27-424 dup2

tactor, thermostat, relay, or similar device, listed for continuous operation at 100 percent of its rating, shall be permitted to supply its full-rated load as provided in Section 210-22(c), Exception. The size of the branch-circuit conductors and overcurrent protective devices supplying fixed electric space heating equipment including a hermetic refrigerant motor-compressor with or without resistance units shall be computed in accordance with Sections 440-34 and 440-35. The provisions of this section shall not apply to conductors that form an integral part of approved fixed electric space heating equipment. B. Installation 424-9. General. All fixed electric space heating equipment shall be installed in an approved manner. Permanently installed electric baseboard heaters equipped with factoryinstalled receptacle outlets, or outlets provided as a separate listed assembly, shall be permitted in lieu of a receptacle outlet(s) that is required by