Regl. 5293, art. 422-27-424 dup2
FIXED ELECTRIC SPACE HEATING EQUIPMENT 70-361
Cite as Reglamento Núm. 5293, Art. 422-27-424 dup2
tactor, thermostat, relay, or similar device, listed for continuous operation
at 100 percent of its rating, shall be permitted to supply its full-rated load
as provided in Section 210-22(c), Exception.
The size of the branch-circuit conductors and overcurrent protective
devices supplying fixed electric space heating equipment including a hermetic refrigerant motor-compressor with or without resistance units shall
be computed in accordance with Sections 440-34 and 440-35.
The provisions of this section shall not apply to conductors that form an
integral part of approved fixed electric space heating equipment.
B. Installation
424-9. General. All fixed electric space heating equipment shall be
installed in an approved manner.
Permanently installed electric baseboard heaters equipped with factoryinstalled receptacle outlets, or outlets provided as a separate listed assembly, shall be permitted in lieu of a receptacle outlet(s) that is required by