Regl. 5293, art. 430-23
Resolución 2535: adopta el Código Eléctrico Nacional, versión 1993. (Sustituye el Anejo A del Reglamento 4435)
Cite as Reglamento Núm. 5293, Art. 430-23
(b) Secondary Resistor Conductors. Where the secondary resistor is
separate from the controller, the minimum size of the conductors between
controller and resistor shall be calculated by multiplying the motor secondary current by the appropriate factor from Table 610-14(b) and selecting a
wire from Table 610-14(a).
70-646
NATIONAL ELECTRICAL CODE
Table 610-14(a). Ampacities of Insulated Copper Conductors
Used with Short-Time Rated Crane and Hoist Motors.
Based on Ambient Temperature of 30°C (86°F).
Up to Four Conductors in Raceway or Cable*
Up to 3 ac** or 4 dc*Conductors in Raceway or Cable.
Maximum
Maximum
Operating
75°C (167°F)
90°C (194°F)
125°C (257°F)
Operating
Temp.
Temp.
Size
Types MTW, RH,
Types TA, TBS, SA,
Types FEP, FEPB,
Size
AWG
RHW, THW, THWN,
SIS, PFA, FEP,
PFA, PFAH, SA,
AWG
(kcmil)
XHHW, USE, ZW
FEPB, RHH, THHN,
TFE, Z, ZW
(kcmil)
XHHW, Z, zw
60 Min
30 Min
60 Min
30 Min
60 Min
30 Min
16
10
12
16
14
25
26
31
32
38
40
14
12
30
33
36
40
45
50
12
10
40
43
49
52
60
65
10
8
55
60
63
69
73
80
8
6
76
86
83
94
101
119
6
5
85
95
95
106
115
134
5
4
100
117
111
130
133
157
4
3
120
141
131
153
153
183
3
2
137
160
148
173
178
214
2
1
143
175
158
192
210
253
1
1/0
190
233
211
259
253
304
1/0
2/0
222
267
245
294
303
369
2/0
3/0
280
341
305
372
370
452
3/0
4/0
300
369
319
399
451
555
4/0
250
364
420
400
461
510
635
250
300
455
582
497
636
587
737
300
350
486
646
542
716
663
837
350
400
538
688
593
760
742
941
400
450
600
765
660
836
818
1042
450
500
660
847
726
914
896
1143
500
AMPACITY CORRECTION FACTORS
Ambient
For ambient temperatures other than 30°C (86°F), multiply the ampacities
Ambient
Temp. °C
shown above by the appropriate factor shown below.
Temp. °F
21-25
1.05
1.05
1.04
1.04
1.02
1.02
70-77
26-30
1.00
1.00
1.00
1.00
1.00
1.00
79-86
31-35
.94
.94
.96
.96
.97
.97
88-95
36-40
.88
.88
.91
.91
.95
.95
97-104
41-45
.82
.82
.87
.87
.92
.92
106-113
46-50
.75
.75
.82
.82
.89
.89
115-122
51-55
.67
.67
.76
.76
.86
.86
124-131
56-60
.58
.58
.71
.71
.83
.83
133-140
61-70
.33
.33
.58
.58
.76
.76
142-158
71-80
.41
.41
.69
.69
160-176
81-90
.61
.61
177-194
91-100
.51
.51
195-212
101-120
.40
.40
213-248
Other insulations shown in Table 310-13 and approved for the temperature and location
shall be permitted to be substituted for those shown in Table 610-14(a). The allowable
ampacities of conductors used with 15-minute motors shall be the 30-minute ratings
increased by 12%.
* For 5 to 8 simultaneously energized power conductors in raceway or cable, the ampacity of each power conductor shall be reduced to a value of 80% of that shown in the table.
** For 4 to 6 simultaneously energized 125°C (257°F) ac power conductors in raceway or
cable, the ampacity of each power conductor shall be reduced to a value of 80% of that
shown in the table.
ARTICLE 610 - CRANES AND HOISTS
70-647
Table 610-14(b). Secondary Conductor Rating Factors
Time in Seconds
Ampacity of Wire
in Percent of Full-Load
On
Off
Secondary Current
5
75
35
10
70
45
15
75
55
15
45
65
15
30
75
15
15
85
Continuous Duty
110
(c) Minimum Size. Conductors external to motors and controls shall not
be smaller than No. 16.
Exception No. 1: No. 18 wire in multiple conductor cord shall be permitted for control circuits at not over 7 amperes.
Exception No. 2: Wires not smaller than No. 20 shall be permitted for
electronic circuits.
(d) Contact Conductors. Contact wires shall have an ampacity not less
than that required by Table 610-14(a) for 75°C (167°F) wire, and in no case
shall they be smaller than the following:
Distance Between
End Strain Insulators or
Clamp-type Intermediate Supports
Size of Wire
0-30 feet
No. 6
30-60 feet
No. 4
Over 60 feet
No. 2
For SI units: one foot = 0.3048 meter.
(e) Calculation of Motor Load.
(1) For one motor, use 100 percent of motor nameplate full-load
ampere rating.
(2) For multiple motors on a single crane or hoist, the minimum
ampacity of the power supply conductors shall be the nameplate full-load
I
ampere rating of the largest motor or group of motors for any single crane
motion, plus 50 percent of the nameplate full-load ampere rating of the next
largest motor or group of motors, using that column of Table 610-14(a) that
applies to the longest time-rated motor.
(3) For multiple cranes and/or hoists supplied by a common conductor
system, compute the motor minimum ampacity for each crane as defined
in Section 610-14(e), add them together, and multiply the sum by the
appropriate demand factor from Table 610-14(e).
70-648
NATIONAL ELECTRICAL CODE
Table 610-14(e). Demand Factors
Number of
Cranes of Hoists
Demand Factor
2
0.95
3
0.91
4
0.87
5
0.84
6
0.81
7
0.78
(f) Other Loads. Additional loads, such as heating, lighting, and air conditioning, shall be provided for by application of the appropriate sections
of this Code.
(g) Nameplate. Each crane, monorail, or hoist shall be provided with a
visible nameplate marked with the maker's name, the rating in volts, frequency, number of phases, and circuit amperes as calculated in Sections
610-14(e) and (f).
610-15. Common Return. Where a crane or hoist is operated by more
than one motor, a common-return conductor of proper ampacity shall be
permitted.
C. Contact Conductors
610-21. Installation of Contact Conductors. Contact conductors shall
comply with (a) through (h) below.
(a) Locating or Guarding Contact Conductors. Runway contact conductors shall be guarded, and bridge contact conductors shall be located or
guarded in a manner that persons cannot inadvertently touch energized
current-carrying parts.
(b) Contact Wires. Wires that are used as contact conductors shall be
secured at the ends by means of approved strain insulators and shall be so
mounted on approved insulators that the extreme limit of displacement of
the wire will not bring the latter within less than 1½ inches (38 mm) from
the surface wired over.
(c) Supports Along Runways. Main contact conductors carried along
runways shall be supported on insulating supports placed at intervals not
exceeding 20 feet (6.1 m).
Exception: Supports for grounded rail conductors as provided in (f)
below shall not be required to be of the insulating type.
Such conductors shall be separated not less than 6 inches (152 mm) other
than for monorail hoists where a spacing of not less than 3 inches (76 mm)
shall be permitted. Where necessary, intervals between insulating supports
shall be permitted to be increased up to 40 feet (12.2 m), the separation
between conductors being increased proportionately.
ARTICLE 610 - CRANES AND HOISTS
70-649
(d) Supports on Bridges. Bridge wire contact conductors shall be kept at
least 2½ inches (64 mm) apart, and, where the span exceeds 80 feet (24.4 m),
insulating saddles shall be placed at intervals not exceeding 50 feet (15.2 m).
(e) Supports for Rigid Conductors. Conductors along runways and
crane bridges, that are of the rigid type specified in Section 610-13, Exception
No. 2 and not contained within an approved enclosed assembly, shall be carried on insulating supports spaced at intervals of not more than eighty times
the vertical dimension of the conductor, but in no case greater than 15 feet
(4.57 m), and spaced apart sufficiently to give a clear electrical separation of
conductors or adjacent collectors of not less than 1 inch (25.4 mm).
(f) Track as Circuit Conductor. Monorail, tramrail, or crane-runway
tracks shall be permitted as a conductor of current for one phase of a
3-phase, alternating-current system furnishing power to the carrier, crane,
or trolley, provided all of the following conditions are met:
(1) The conductors supplying the other two phases of the power supply are insulated.
(2) The power for all phases is obtained from an insulating transformer.
(3) The voltage does not exceed 300 volts.
(4) The rail serving as a conductor is effectively-grounded at the transformer and also shall be permitted to be grounded by the fittings used for
the suspension or attachment of the rail to a building or structure.
(g) Electrical Continuity of Contact Conductors. All sections of contact
conductors shall be mechanically joined to provide a continuous electrical
connection.
(h) Not to Supply Other Equipment. Contact conductors shall not be
used as feeders for any equipment other than the crane or cranes that they
are primarily designed to serve.
610-22. Collectors. Collectors shall be so designed as to reduce to a minimum sparking between them and the contact conductor; and, where operated in rooms used for the storage of easily ignitible combustible fibers and
materials, they shall comply with Section 503-13.
D. Disconnecting Means
610-31. Runway Conductor Disconnecting Means. A disconnecting
means having a continuous ampere rating not less than that computed in
Sections 610-14(e) and (f) shall be provided between the runway contact
conductors and the power supply. Such disconnecting means shall consist
shall: of a motor circuit switch or circuit breaker. This disconnecting means
(1) Be readily accessible and operable from the ground or floor level.
(2) Be arranged to be locked in the open position.
(3) Open all ungrounded conductors simultaneously.
(4) Be placed within view of the crane or hoist and the runway contact
conductors.
70-650
NATIONAL ELECTRICAL CODE
610-32. Disconnecting Means for Cranes and Monorail Hoists. A motor
circuit switch or circuit breaker arranged to be locked in the open position
shall be provided in the leads from the runway contact conductors or other
power supply on all cranes and monorail hoists.
Exception: Where a monorail hoist or hand-propelled crane bridge
installation meets all of the following, the disconnect shall be permitted to
be omitted.
a. The unit is floor controlled.
b. The unit is within view of the power supply disconnecting means.
c. No fixed work platform has been provided for servicing the unit.
Where the disconnecting means is not readily accessible from the crane
or monorail hoist operating station, means shall be provided at the operating station to open the power circuit to all motors of the crane or monorail
hoist.
610-33. Rating of Disconnecting Means. The continuous ampere rating
of the switch or circuit breaker required by Section 610-32 shall not be less
than 50 percent of the combined short-time ampere rating of the motors,
nor less than 75 percent of the sum of the short-time ampere rating of the
motors required for any single motion.
E. Overcurrent Protection
610-41. Feeders, Runway Conductors. The runway supply conductors
and main contact conductors of a crane or monorail shall be protected by
an overcurrent device(s) that shall not be greater than the largest rating or
setting of any branch-circuit protective device, plus the sum of the nameplate ratings of all the other loads with application of the demand factors
from Table 610-14(e).
610-42. Branch-Circuit Short-Circuit and Ground-Fault Protection.
Branch circuits shall be protected as follows:
(a) Fuse or Circuit Breaker Rating. Crane, hoist, and monorail hoist
motor branch circuits shall be protected by fuses or inverse-time circuit
breakers having a rating in accordance with Table 430-152. Taps to control
circuits shall be permitted to be taken from the load side of a branch-circuit
protective device, provided each tap and piece of equipment is properly
protected.
Exception No. 1: When two or more motors operate a single motion,
the sum of their nameplate current ratings shall be considered as a single
motor current in the above calculations.
Exception No. 2: Two or more motors shall be permitted to be connected to the same branch circuit if no tap conductor to an individual
motor has an ampacity less than one-third that of the branch circuit and if
each motor is protected from overload according to Section 610-43.
(b) Taps to Brake Coils. Taps to brake coils do not require separate
overcurrent protection.
ARTICLE 610 - CRANES AND HOISTS
70-651
610-43. Motor and Branch-Circuit Overload Protection. Each motor,
motor control, and branch-circuit conductor shall be protected from overload by one of the following means:
(1) A single motor shall be considered as protected where the branchcircuit overcurrent device meets the rating requirements of Section 610-42.
(2) Overload relay elements in each ungrounded circuit conductor,
with all relay elements protected from short circuit by the branch-circuit
protection.
(3) Thermal sensing device(s), sensitive to motor temperature or to
temperature and current that are thermally in contact with the motor winding(s). A hoist or trolley is considered to be protected if the sensing device
is connected in the hoist's upper limit switch circuit so as to prevent further hoisting during an overload condition of either motor.
Exception No. 1: If the motor is manually controlled, with spring return
controls, the overload protective device shall not be required to protect the
motor against stalled rotor conditions.
Exception No. 2: Where two or more motors drive a single trolley,
truck, or bridge and are controlled as a unit by a single set of overload
devices with a rating equal to the sum of their rated full-load currents. A
hoist or trolley shall be considered to be protected if the sensing device is
connected in the hoist's upper limit switch circuit so as to prevent further
hoisting during an overtemperature condition of either motor.
Exception No. 3: Hoists and monorail hoists and their trolleys that are
not used as part of an overhead traveling crane shall not require individual motor overload protection, provided the largest motor does not exceed
7½ horsepower and all motors are under manual control of the operator.
F. Control
610-51. Separate Controllers. Each motor shall be provided with an individual controller.
Exception No. 1: Where two or more motors drive a single hoist, carriage, truck, or bridge, they shall be permitted to be controlled by a single
controller.
Exception No. 2: One controller shall be permitted to be switched
between motors, provided:
a. The controller shall have a horsepower rating that shall not be
lower than the horsepower rating of the largest motor.
b. Only one motor is operated at one time.
610-53. Overcurrent Protection. Conductors of control circuits shall be
protected against overcurrent. Control circuits shall be considered as protected by overcurrent devices that are rated or set at not more than 300
percent of the ampacity of the control conductors.
Exception No. 1: Taps to control transformers shall be considered as
protected where the secondary circuit is protected by a device rated or set
at not more than 200 percent of the rated secondary current of the transformer and not more than 200 percent of the ampacity of the control circuit conductors.
70-652
NATIONAL ELECTRICAL CODE
Exception No. 2: Such conductors shall be considered as being properly
protected by the branch-circuit overcurrent devices where the opening of
the control circuit would create a hazard, as for example, the control circuit of a hot metal crane.
610-55. Limit Switch. A limit switch or other device shall be provided to
prevent the load block from passing the safe upper limit of travel of all
hoisting mechanisms.
610-57. Clearance. The dimension of the working space in the direction
of access to live parts that are likely to require examination, adjustment,
servicing, or maintenance while energized shall be a minimum of 2½ feet
(762 mm). Where controls are enclosed in cabinets, the door(s) shall either
open at least 90 degrees or be removable.
G. Grounding
610-61. Grounding. All exposed noncurrent-carrying metal parts of
cranes, monorail hoists, hoists, and accessories including pendant controls
shall be metallically joined together into a continuous electrical conductor
so that the entire crane or hoist will be grounded in accordance with Article 250. Moving parts, other than removable accessories or attachments,
having metal-to-metal bearing surfaces shall be considered to be electrically connected to each other through the bearing surfaces for grounding
purposes. The trolley frame and bridge frame shall be considered as electrically grounded through the bridge and trolley wheels and its respective
tracks unless local conditions, such as paint or other insulating material,
prevent reliable metal-to-metal contact. In this case, a separate bonding
conductor shall be provided.