Regl. 5293, art. 430-23-620 dup2
ELEVATORS, DUMBWAITERS
Cite as Reglamento Núm. 5293, Art. 430-23-620 dup2
70-653
Exception: Higher voltages shall be permitted for frequencies of 25-
through 60-hertz alternating current or for direct current, provided the
current in the system cannot, under any conditions, exceed 8 milliamperes
for alternating current or 30 milliamperes for direct current.
(b) 600 Volts. Driving machine motors, machine brakes, and motorgenerator sets.
Exception: Higher voltages shall be permitted for driving motors of
motor-generator sets.
620-3. Live Parts Enclosed. All live parts of electric apparatus in the
hoistways, at the landings, or in or on the cars of elevators and dumbwaiters or in the wellways or the landings of escalators or moving walks, or in
the runways and machinery spaces of wheelchair lifts and stairway chair
lifts shall be enclosed to protect against accidental contact.
B. Conductors
620-11. Insulation of Conductors. The insulation of conductors installed
in connection with elevators, dumbwaiters, escalators, moving walks,
wheelchair lifts, and stairway chair lifts shall comply with (a) through (d)
below.
(a) Hoistway Door Interlock Wiring. The conductors to the hoistway
door interlocks from the hoistway riser shall be flame-retardant and suitable for a temperature of not less than 200°C (392°F). Conductors shall be
Type SF or equivalent.
(b) Traveling Cables. Traveling cables used as flexible connections
between the elevator or dumbwaiter car and the raceway shall be of the
types of elevator cable listed in Table 400-4 or other approved types.
(c) Other Wiring. All conductors in raceways; in or on the cars of elevators and dumbwaiters; in the wellways of escalators and moving walks;
in the runways and machinery spaces of wheelchair lifts and stairway chair
lifts; and in the machine room of elevators, dumbwaiters, escalators, and
moving walks shall have flame-retardant insulation.
(d) Insulation. All conductors shall have an insulation voltage rating
equal to at least the maximum nominal circuit voltage rating of any conductor within the enclosure, cable, or raceway.
Conductors shall be Type MTW, TF, TFF, TFN, TFFN, THHN,
THW, THWN, TW, XHHW, hoistway cable, or any other conductor with
insulation designated as flame-retardant. Shielded conductors shall be permitted, provided such conductors are insulated for the maximum voltage
found in the cable or raceway system.
620-12. Minimum Size of Conductors. The minimum size of conductors
used for elevator, dumbwaiter, escalator, moving walk, wheelchair lift, and
stairway chair lift wiring, other than conductors that form an integral part
of control equipment, shall be as follows:
70-654
NATIONAL ELECTRICAL CODE
(a) Traveling Cables.
(1) For lighting circuits: No. 14.
Exception: No. 20 or larger conductors shall be permitted in parallel,
provided the ampacity is equivalent to at least that of No. 14 wire.
(2) Operating control and signaling circuits: No. 20.
(b) Other Wiring. All operating control and signaling circuits: No. 24.
620-13. Motor Circuit Conductors. Conductors supplying elevator,
dumbwaiter, escalator, moving walk, wheelchair lift, and stairway chair
lift motors shall have an ampacity in accordance with (a) and (b) below
based on the nameplate current rating of the motors. With generator
field control, the ampacity shall be based on the nameplate current rating of the driving motor of the motor-generator set that supplies power
to the elevator motor.
(FPN): The heating of conductors depends on root-mean-square current values, which, with generator field control, are reflected by the nameplate current
rating of the motor-generator set driving motor rather than by the rating of the
elevator motor, which represents actual but short-time and intermittent full-load
current values.
(a) Conductors Supplying Single Motor. Conductors supplying a single
motor shall have an ampacity in conformance with Section 430-22 and
Table 430-22(a), Exception.
(b) Conductors Supplying Several Motors. Conductors supplying two
or more motors shall have an ampacity of not less than 125 percent of the
nameplate current rating of the highest rated motor in the group plus the
sum of the nameplate current ratings of the remainder of the motors in the
group.
620-14. Adjustable Speed Drive Systems. Conductors supplying elevators, dumbwaiters, escalators, moving walks, wheelchair lifts, or stairway
chair lifts shall have an ampacity in accordance with the following:
(a) Drive Power Transformer Integral with the Power Conversion
Equipment. Conductor ampacity shall be based on the nameplate current
rating of the power conversion equipment.
(b) Drive Power Transformer Not Integral with the Power Conversion
Equipment. Conductor ampacity shall be based on the nameplate current
rating of the drive power transformer and all other connected loads, or the
nameplate current rating of the power conversion equipment reflected to
the primary side of the transformer, plus all other connected loads, whichever is the larger.
(FPN): Diagram 620-14 is for information only.
620-15. Feeder Demand Factor. Feeder conductors of less ampacity than
required by Sections 620-13 and 620-14 shall be permitted subject to the
requirements of Section 430-26 and Table 620-15.
ARTICLE 620 - ELEVATORS, DUMBWAITERS
70-655
To supply
To supply
620-14(a)
620-14(b)
Common feeder
Feeder demand
factor
Sec. 620-15
Disconnecting means
Part F
Overcurrent
protection
Part G
Short-circuit and
Art. 430
ground-fault
Part D
protection
Branch circuit
conductors to
Sec. 620-14
external transformer
External transformer
Art. 450
Branch circuit
Sec. 620-14
conductors to
controller
Sec. 620-13
Controller
cabinet
Sec. 620-14
rating
Motor conductors
Sec. 620-13(a)
Part G
Motor
Thermal protection
Art. 430
Parts A and c
M
M
(FPN): Diagram 620-14
70-656
NATIONAL ELECTRICAL CODE
Table 620-15. Feeder Demand Factors for Elevators
Number of Elevators
on a Single Feeder
DF
1
1.00
2
.95
3
.90
4
.85
5
.82
6
.79
7
.77
8
.75
9
.73
10 or more
.72
(FPN): Demand Factors (DF) are based on 50 percent duty cycle (i.e., half time on and
half time off).
C. Wiring
620-21. Wiring Methods. Conductors located in hoistways, in escalator
and moving walk wellways, in wheelchair lifts, stairway chair lift runways,
and machinery spaces, in or on cars, and in machine and control rooms,
not including the traveling cables connecting the car and hoistway wiring,
shall be installed in rigid metal conduit, intermediate metal conduit, electrical metallic tubing, rigid nonmetallic conduit, or wireways, or shall be
Type MC, MI, or AC cable.
Exception No. 1: Flexible metal conduit or liquidtight flexible metal conduit shall be permitted in hoistways and in escalator and moving walk wellways between risers and limit switches, interlocks, operating buttons, and
similar devices. Cables used in Class 2 power-limited circuits (30 volts RMS
or less or 42 VDC or less) shall be permitted to be installed between risers
and signal fixtures and operating devices and within escalators and moving
walkways and wheelchair lifts, and stairway chair lift runways and machinery spaces provided the cables are supported and protected from physical
abuse and are of a jacketed and flame-retardant type.
(FPN): Signal fixtures include audible and visual equipment such as chimes,
gongs, lights, and displays that convey information to the elevator user.
Exception No. 2: Flexible metal conduit or liquidtight flexible metal conduit not exceeding 6 feet (1.83 m) in length shall be permitted on cars where
so located as to be free from oil and if securely fastened in place.
Exception No. 3: Hard-service cords and junior hard-service cords conforming to the requirements of Article 400 (Table 400-4) shall be permitted
as flexible connections between the fixed wiring on the car and devices on
the car doors or gates. Hard-service cords only shall be permitted as flexible connections for the top-of-car operating device or the car-top work
light. Devices or fixtures shall be grounded by means of an equipment
grounding conductor run with the circuit conductors. Cables with smaller
conductors and other types and thicknesses of insulation and jackets shall
be permitted as flexible connections between the fixed wiring on the car
and devices on the car doors or gates, if listed for this use.
ARTICLE 620 - ELEVATORS, DUMBWAITERS
70-657
Exception No. 4: Flexible metal conduit or liquidtight flexible metal
conduit, not exceeding 6 feet (1.83 m) in length, shall be permitted between
control panels and machine motors, machine brakes, motor-generator
sets, disconnecting means, and pumping unit motors and valves. Conductors shall also be permitted to be grouped together and taped or corded
without being installed in a raceway. Such cable groups shall be supported
at intervals not over 3 feet (914 mm) and so located as to be free from
physical damage.
Exception No. 5: Flexible metal conduit or liquidtight flexible metal
conduit, of ³/₈-inch nominal trade size, shall be permitted in lengths not in
excess of 6 feet (1.83 m).
Exception No. 6: Flexible metal conduit, conforming to Article 350, or
liquidtight flexible metal conduit, or hard-service cords conforming to the
requirements of Article 400 (Table 400-4) shall be permitted as flexible
connections on escalators, moving walk or elevator control panels and
disconnecting means where the entire control panel and disconnecting
means are arranged for removal from machine spaces as permitted in