Regl. 5293, art. 430-250
Resolución 2535: adopta el Código Eléctrico Nacional, versión 1993. (Sustituye el Anejo A del Reglamento 4435)
Cite as Reglamento Núm. 5293, Art. 430-250
(FPN): See Section 430-12(e) for grounding connection means required at motor
terminal housings.
(b) Separation of Junction Box from Motor. The junction box required
I
by (a) above shall be permitted to be separated from the motor by not more
than 6 feet (1.83 m), provided the leads to the motor are Typc AC cable or
armored cord or are stranded leads enclosed in liquidtight flexible metal
conduit, flexible metal conduit, intermediate metal conduit, rigid metal
conduit, or electrical metallic tubing not smaller than ³/₈-inch electrical
trade size, the armor or raceway being connected both to the motor and to
ARTICLE 430 - MOTOR CIRCUITS, CONTROLLERS
70-425
the box. Where stranded leads are used, protected as specified above, they
shall not be larger than No. 10 and shall comply with other requirements
of this Code for conductors to be used in raceways.
Liquidtight flexible nonmetallic conduit and rigid nonmetallic conduit
shall be permitted to enclose the leads to the motor provided the required
grounding conductor is connected to both the motor and to the box.
(c) Grounding of Controller Mounted Devices. Instrument transformer
secondaries and exposed noncurrent-carrying metal or other conductive
parts or cases of instrument transformers, meters, instruments, and relays
shall be grounded as specified in Sections 250-121 through 250-125.
M. Tables
Table 430-147. Full-Load Current in Amperes,
Direct-Current Motors
The following values of full-load currents* are for motors running at base speed.
Armature Voltage Rating*
HP
90V
120V
180V
240V
500V
550V
¹/₄
4.0
3.1
2.0
1.6
¹/₃
5.2
4.1
2.6
2.0
½
6.8
5.4
3.4
2.7
3/4
9.6
7.6
4.8
3.8
1
12.2
9.5
6.1
4.7
1½
13.2
8.3
6.6
2
17
10.8
8.5
3
25
16
12.2
5
40
27
20
7½
58
29
13.6
12.2
10
76
38
18
16
15
55
27
24
20
72
34
31
25
89
43
38
30
106
51
46
40
140
67
61
50
173
83
75
60
206
99
90
75
255
123
111
100
341
164
148
125
425
205
185
150
506
246
222
200
675
330
294
*These are average direct-current quantities.
70-426
NATIONAL ELECTRICAL CODE
Table 430-148. Full-Load Currents in Amperes
Single-Phase Alternating-Current Motors
The following values of full-load currents are for motors running at usual
speeds and motors with normal torque characteristics. Motors built for especially
low speeds or high torques may have higher full-load currents, and multispeed
motors will have full-load current varying with speed, in which case the namplate
current ratings shall be used.
The voltages listed are rated motor voltages. The currents listed shall be permitted for system voltage ranges of 110 to 120 and 220 to 240.
HP
115V
200V
208V
230V
1/6
4.4
2.5
2.4
2.2
¼
5.8
3.3
3.2
2.9
½
7.2
4.1
4.0
3.6
½
9.8
5.6
5.4
4.9
3/4
13.8
7.9
7.6
6.9
1
16
9.2
8.8
8
1½
20
11.5
11
10
2
24
13.8
13.2
12
3
34
19.6
18.7
17
5
56
32.2
30.8
28
7½
80
46
44
40
10
100
57.5
55
50
ARTICLE 430 - MOTOR CIRCUITS, CONTROLLERS
70-427
Table 430-149. Full-Load Current
Two-Phase Alternating-Current Motors (4-Wire)
The following values of full-load current are for motors running at speeds usual
for belted motors and motors with normal torque characteristics. Motors built for
especially low speeds or high torques may require more running current, and
multispeed motors will have full-load current varying with speed, in which case
the nameplate current rating shall be used. Current in the common conductor of
a 2-phase, 3-wire system will be 1.41 times the value given.
The voltages listed are rated motor voltages. The currents listed shall be permitted for system voltage ranges of 110 to 120, 220 to 240, 440 to 480, and 550-
600 volts.
Induction Type
Squirrel-Cage and Wound-Rotor
Amperes
HP
115V
230V
460V
575V
2300V
½
4
2
1
.8
3/4
4.8
2.4
1.2
1.0
1
6.4
3.2
1.6
1.3
1½
9
4.5
2.3
1.8
2
11.8
5.9
3
2.4
3
8.3
4.2
3.3
5
13.2
6.6
5.3
7½
19
9
8
10
24
12
10
15
36
18
14
20
47
23
19
25
59
29
24
30
69
35
28
40
90
45
36
50
113
56
45
60
133
67
53
14
75
166
83
66
18
100
218
109
87
23
125
270
135
108
28
150
312
156
125
32
200
416
208
167
43
70-428
NATIONAL ELECTRICAL CODE
Table 430-150. Full-Load Current*
Three-Phase Alternating-Current Motors
Induction Type
Synchronous Type
Squirrel-Cage and Wound-Rotor
Unity Power Factort
Amperes
Amperes
HP
115V
200V
208V
230V
460V
575V
2300V
230V
460V
575V
2300V
½
4
2.3
2.2
2
1
.8
3/4
5.6
3.2
3.1
2.8
1.4
1.1
1
7.2
4.1
4.0
3.6
1.8
1.4
1½
10.4
6.0
5.7
5.2
2.6
2.1
2
13.6
7.8
7.5
6.8
3.4
2.7
3
11.0
10.6
9.6
4.8
3.9
5
17.5
16.7
15.2
7.6
6.1
7½
25.3
24.2
22
11
9
10
32.2
30.8
28
14
11
15
48.3
46.2
42
21
17
20
62.1
59.4
54
27
22
25
78.2
74.8
68
34
27
53
26
21
30
92
88
80
40
32
63
32
26
40
119.6
114.4
104
52
41
83
41
33
50
149.5
143.0
130
65
52
104
52
42
60
177.1
169.4
154
77
62
16
123
61
49
12
75
220.8
211.2
192
96
77
20
155
78
62
15
100
285.2
272.8
248
124
99
26
202
101
81
20
125
358.8
343.2
312
156
125
31
253
126
101
25
150
414
396.0
360
180
144
37
302
151
121
30
200
552
528.0
480
240
192
49
400
201
161
40
*These values of full-load current are for motors running at speeds usual for belted motors
and motors with normal torque characteristics. Motors built for especially low speeds or
high torques may require more runnning current, and multispeed motors will have full-load
current varying with speed, in which case the nameplate current rating shall be used.
+For 90 and 80 percent power factor, the above figures shall be multipled by 1.1 and 1.25
respectively.
The voltages listed are rated motor voltages. The currents listed shall be permitted for
system voltage ranges of 110 to 120, 220 to 240, 440 to 480, and 550 to 600 volts.
ARTICLE 430 - MOTOR CIRCUITS, CONTROLLERS
70-429
Table 430-151. Conversion Table of Locked-Rotor Currents
for Selection of Disconnecting Means and Controllers
as Determined from Horsepower and Voltage Rating
For use only with Sections 430-110, 440-12, 440-41, and 455-8(c).
Motor Locked-Rotor Current Amperes*
Single Phase
Two or Three Phase
Max. HP
115V
230V
115V
200V
230V
460V
575V
Rating
58.8
29.4
24
18.8
12
6
4.8
1/2
82.8
41.4
33.6
19.3
16.8
8.4
6.6
3/4
96
48
43.2
24.8
21.6
10.8
8.4
1
120
60
62
35.9
31.2
15.6
12.6
1½
144
72
81
46.9
40.8
20.4
16.2
2
204
102
-
66
58
26.8
23.4
3
336
168
-
105
91
45.6
36.6
5
480
240
-
152
132
66
54
7½
600
300
-
193
168
84
66
10
-
-
-
290
252
126
102
15
-
-
-
373
324
162
132
20
-
-
-
469
408
204
162
25
-
-
-
552
480
240
192
30
-
-
-
718
624
312
246
40
-
-
-
897
780
390
312
50
-
-
-
1063
924
462
372
60
-
-
-
1325
1152
576
462
75
-
-
-
1711
1488
744
594
100
-
-
-
2153
1872
936
750
125
-
-
-
2484
2160
1080
864
150
-
-
-
3312
2880
1440
1152
200
*These values of motor locked-rotor current are approximately six times the full-load current values given in Tables 430-148 and 430-150.
70-430
NATIONAL ELECTRICAL CODE
430-152. Maximum Rating or Setting of Motor Branch-Circuit
Short-Circuit and Ground-Fault Protective Devices
Percent of Full-Load Current
Dual
Element
Instan-
Nontime
(Timetaneous
Inverse
Delay
Delay)
Trip
Time
Type of Motor
Fuse
Fuse
Breaker
Breaker*
Single-phase, all types
No code letter
300
175
700
250
All ac single-phase and
polyphase squirrel-cage and synchronous motorst with fullvoltage, resistor or reactor starting:
No code letter
300
175
700
250
Code letters F to V
300
175
700
250
Code letters B to E
250
175
700
200
Code letter A
150
150
700
150
All ac squirrel-cage and synchronous motorst with autotransformer starting:
Not more than 30 amps
No code letter
250
175
700
200
More than 30 amps
No code letter
200
175
700
200
Code letters F to V
250
175
700
200
Code letters B to E
200
175
700
200
Code letter A
150
150
700
150
High reactance squirrel-cage
Not more than 30 amps
No code letter
250
175
700
250
More than 30 amps
No code letter
200
175
700
200
Wound-rotor -
No code letter
150
150
700
150
Direct-current (constant voltage)
No more than 50 hp
No code letter
150
150
250
150
More than 50 hp
No code letter
150
150
175
150
For explanation of code letter marking, see Table 430-7(b).
For certain exceptions to the values specified, see Sections 430-52 through 430-54.
*The values given in the last column also cover the ratings of nonadjustable inverse time
types of circuit breakers that may be modified as in Section 430-52.
+Synchronous motors of the low-torque, low-speed type (usually 450 rpm or lower), such
as are used to drive reciprocating compressors, pumps, etc., that start unloaded, do not
require a fuse rating or circuit-breaker setting in excess of 200 percent of full-load current.