Resolución 2535: adopta el Código Eléctrico Nacional, versión 1993. (Sustituye el Anejo A del Reglamento 4435)
Cite as Reglamento Núm. 5293, Art. 430-3-450
Exception No. 1: Control circuit transformers rated less than 50 VA and
that are an integral part of the motor controller and located within the
motor controller enclosure shall be permitted to be protected by primary
overcurrent devices, impedance limiting means, or other inherent protective means.
Exception No. 2: Where the control circuit transformer rated primary
current is less than 2 amperes, an overcurrent device rated or set at not
more than 500 percent of the rated primary current shall be permitted in
the primary circuit.
Exception No. 3: Where the transformer supplies a Class 1 powerlimited circuit [see Section 725-11(a)], Class 2, or Class 3 remote-control
circuit conforming with the requirements of Article 725. See Article 725,
Part C.
Exception No. 4: Where protection is provided by other approved
means.
70-412
NATIONAL ELECTRICAL CODE
Exception No. 5: Overcurrent protection shall be omitted where the
opening of the control circuit would create a hazard, as, for example, the
control circuit of a fire pump motor and the like.
430-73. Mechanical Protection of Conductor. Where damage to a motor
control circuit would constitute a hazard, all conductors of such a remote
motor control circuit that are outside the control device itself shall be
installed in a raceway or be otherwise suitably protected from physical
damage.
Where one side of the motor control circuit is grounded, the motor control circuit shall be so arranged that an accidental ground in the remotecontrol devices will (1) not start the motor, and (2) not bypass manually
operated shutdown devices or automatic safety shutdown devices.
430-74. Disconnection.
(a) General. Motor control circuits shall be so arranged that they will be
disconnected from all sources of supply when the disconnecting means is
in the open position. The disconnecting means shall be permitted to consist of two or more separate devices, one of which disconnects the motor
and the controller from the source(s) of power supply for the motor, and
the other(s), the motor control circuit(s) from its power supply. Where
separate devices are used, they shall be located immediately adjacent one
to each other.
Exception No. 1: Where more than twelve motor control circuit conductors are required to be disconnected, the disconnecting means shall be
permitted to be located other than immediately adjacent one to each other
where all of the following conditions are complied with:
a. Access to energized parts is limited to qualified persons in accordance with Part K of this article.
b. A warning sign is permanently located on the outside of each
equipment enclosure door or cover permitting access to the live parts in
the motor control circuit(s), warning that motor control circuit disconnecting means are remotely located and specifying the location and identification of each disconnect. Where energized parts are not in an equipment
enclosure as permitted by Sections 430-132 and 430-133, an additional
warning sign(s) shall be located where visible to persons who may be
working in the area of the energized parts.
Exception No. 2: Where the opening of one or more motor control circuit disconnect means may result in potentially unsafe conditions for personnel or property and the conditions of items a and b of Exception No. 1
above are complied with.
(b) Control Transformer in Controller Enclosure. Where a transformer
or other device is used to obtain a reduced voltage for the motor control
circuit and is located in the controller enclosure, such transformer or other
device shall be connected to the load side of the disconnecting means for
the motor control circuit.
ARTICLE 430 - MOTOR CIRCUITS, CONTROLLERS
70-413
G. Motor Controllers
430-81. General. Part G is intended to require suitable controllers for
all motors.
(a) Definition. For definition of "Controller," see Article 100. For the
purpose of this article, a controller is any switch or device normally used
to start and stop a motor by making and breaking the motor circuit current.
(b) Stationary Motor of 1/8 Horsepower or Less. For a stationary motor
rated at ¹/₈ horsepower or less that is normally left running and is so constructed that it cannot be damaged by overload or failure to start, such as
clock motors and the like, the branch-circuit protective device shall be
permitted to serve as the controller.
(c) Portable Motor of ¼ Horsepower or Less. For a portable motor
rated at ½ horsepower or less, the controller shall be permitted to be an
attachment plug and receptacle.
430-82. Controller Design.
(a) Starting and Stopping. Each controller shall be capable of starting
and stopping the motor it controls and shall be capable of interrupting the
locked-rotor current of the motor.
(b) Autotransformer. An autotransformer starter shall provide an "off"
position, a running position, and at least one starting position. It shall be
so designed that it cannot rest in the starting position or in any position that
will render the overload device in the circuit inoperative.
(c) Rheostats. Rheostats shall be in compliance with the following:
(1) Motor-starting rheostats shall be so designed that the contact arm
cannot be left on intermediate segments. The point or plate on which the
arm rests when in the starting position shall have no electrical connection
with the resistor.
(2) Motor-starting rheostats for direct-current motors operated from a
constant voltage supply shall be equipped with automatic devices that will
interrupt the supply before the speed of the motor has fallen to less than
one-third its normal rate.
430-83. Ratings.
(a) Horsepower Rating at the Application Voltage. The controller
shall have a horsepower rating at the application voltage not lower than
the horsepower rating of the motor.
Exception No. 1: For a stationary motor rated at 2 horsepower or less,
and 300 volts or less, the controller shall be permitted to be a general-use
switch having an ampere rating not less than twice the full-load current
rating of the motor.
On ac circuits, general-use snap switches suitable only for use on ac
(not general-use ac-dc snap switches) shall be permitted to control a
motor rated at 2 horsepower or less, and 300 volts or less, having a
70-414
NATIONAL ELECTRICAL CODE
full-load current rating not more than 80 percent of the ampere rating of
the switch.
Exception No. 2: A branch-circuit inverse time circuit breaker rated in
amperes only shall be permitted as a controller. Where this circuit breaker
is also used for overload protection, it shall conform to the appropriate
provisions of this article governing overload protection.
Exception No. 3: The motor controller for a torque motor shall have a
continuous-duty, full-load current rating not less than the nameplate current rating of the motor. For a motor controller rated in horsepower but
not marked with the foregoing current rating, the equivalent current rating
shall be determined from the horsepower rating by using Table 430-147,
430-148, 430-149, or 430-150.
(b) Voltage Rating. A controller with a straight voltage rating, e.g.,
240V or 480V, shall be permitted to be applied in a circuit in which the
nominal voltage between any two conductors does not exceed the controller's voltage rating. A controller with a slash rating, e.g., 120/240V
or 480/277V, shall only be applied in a circuit in which the nominal voltage to ground from any conductor does not exceed the lower of the two
values of the controller's voltage rating and the nominal voltage
between any two conductors does not exceed the higher value of the
controller's voltage rating.
430-84. Need Not Open All Conductors. The controller shall not be
required to open all conductors to the motor.
Exception: Where the controller serves also as a disconnecting means,
it shall open all ungrounded conductors to the motor as provided in Section 430-111.
430-85. In Grounded Conductors. One pole of the controller shall be permitted to be placed in a permanently grounded conductor, provided the
controller is so designed that the pole in the grounded conductor cannot be
opened without simultaneously opening all conductors of the circuit.
430-87. Number of Motors Served by Each Controller. Each motor shall
be provided with an individual controller.
Exception: For motors rated 600 volts or less, a single controller rated
at not less than the sum of the horsepower ratings of all of the motors of
the group shall be permitted to serve the group of motors under any one of
the following conditions:
a. Where a number of motors drive several parts of a single machine
or piece of apparatus, such as metal and woodworking machines, cranes,
hoists, and similar apparatus.
b. Where a group of motors is under the protection of one overcurrent device as permitted in Section 430-53(a).
C. Where a group of motors is located in a single room within sight
from the controller location.
ARTICLE 430 - MOTOR CIRCUITS, CONTROLLERS
70-415
430-88. Adjustable-Speed Motors. Adjustable-speed motors that are
controlled by means of field regulation shall be so equipped and connected
that they cannot be started under weakened field.
Exception: Where the motor is designed for such starting.
430-89. Speed Limitation. Machines of the following types shall be provided with speed limiting devices or other speed limiting means:
(a) Separately Excited DC Motors. Separately excited direct-current
motors.
(b) Series Motors. Series motors.
(c) Motor-Generators and Converters. Motor-generators and converters that can be driven at excessive speed from the direct-current end, as by
a reversal of current or decrease in load.
Exception No. 1: Where the inherent characteristics of the machines,
the system, or the load and the mechanical connection thereto are such as
to safely limit the speed.
Exception No. 2: Where the machine is always under the manual control of a qualified operator.
430-90. Combination Fuseholder and Switch as Controller. The rating of
a combination fuseholder and switch used as a motor controller shall be
such that the fuseholder will accommodate the size of the fuse specified in
Part C of this article for motor overload protection.
Exception: Where fuses having time delay appropriate for the starting
characteristics of the motor are used, fuseholders of smaller size than
specified in Part C of this article shall be permitted.
430-91. Motor Controller Enclosure Types. Table 430-91 provides the
basis for selecting enclosures for use in specific nonhazardous locations.
The enclosures are not intended to protect against conditions such as condensation, icing, corrosion, or contamination that may occur within the
enclosure or enter via the conduit or unsealed openings. These internal
conditions require special consideration by the installer and user.
H. Motor Control Centers
430-92. General. Part H covers motor control centers installed for the
control of motors, lighting, and power circuits.
A motor control center is an assembly of one or more enclosed sections having a common power bus and principally containing motor
control units.
430-94. Overcurrent Protection. Motor control centers shall be provided
with overcurrent protection in accordance with Article 240 based on the
rating of the common power bus. This protection shall be provided by
either (1) an upstream overcurrent-protective device or (2) a main
overcurrent-protective device located within the motor control center.
70-416
NATIONAL ELECTRICAL CODE
Table 430-91. Motor Controller Enclosure Selection Table
For Outdoor Use
Provides a Degree of Protection
Enclosure Type Number t
Against the Following
Environmental Conditions
3 3 R 3 S 4 4X 6 6P
Incidental contact with the
enclosed equipment
X
X
X
X
X
X
X
Rain, snow, and sleet
X
X
X
X
X
X
X
Sleet*
-
X
Windblown dust
X
-
X
X
X
X
X
Hosedown
-
X
X
X
X
Corrosive agents
-
-
-
X
-
X
Occasional temporary submersion
-
-
-
-
-
X
X
Occasional prolonged submersion
-
-
-
-
-
-
X
*Mechanism shall be operable when ice covered.
For Indoor Use
Provides a Degree of Protection
Enclosure Type Number t
Against the Following
Environmental Conditions
1 2 4 4 X 5 6 6P 12 12K 13
Incidental contact with the
enclosed equipment
X
X
X
X
X
X
X
X
X
X
Falling dirt
X
X
X
X
X
X
X
X
X
X
Falling liquids and light splashing
-
X
X
X
X
X
X
X
X
X
Circulating dust, lint, fibers,
and flyings
-
-
X
X
-
X
X
X
X
X
Settling airborne dust, lint, fibers,
and flyings
-
-
X
X
X
X
X
X
X
X
Hosedown and splasing water
-
-
X
X
-
X
X
-
-
Oil and coolant seepage
-
-
-
X
X
X
Oil or coolant spraying and
splashing
-
-
-
X
Corrosive agents
-
-
X
-
X
---
-
Occasional temporary submersion
|
-
X
X
-
|
-
Occasional prolonged submersion
-
-
X
tEnclosure type number shall be marked on the motor controller enclosure.
430-95. Service-Entrance Equipment. Where used as service equipment,
each motor control center shall be provided with a single main disconnecting means to disconnect all ungrounded service conductors.
Exception: A second service disconnect shall be permitted to supply
additional equipment.
Where a grounded (neutral) conductor is provided, the motor control
center shall be provided with a main bonding jumper, sized in accordance
with Section 250-79(d), within one of the sections for connecting the
grounded (neutral) conductor, on its supply side, to the motor control center equipment ground bus.
ARTICLE 430 - MOTOR CIRCUITS, CONTROLLERS
70-417
430-96. Grounding. Multisection motor control centers shall be bonded
together with an equipment grounding conductor or an equivalent grounding bus sized in accordance with Table 250-95. Equipment grounding conductors shall terminate on this grounding bus or to a grounding termination
point provided in a single-section motor control center.
430-97. Busbars and Conductors.
(a) Support and Arrangement. Busbars shall be protected from physical
damage and be held firmly in place. Other than for required interconnections and control wiring, only those conductors that are intended for termination in a vertical section shall be located in that section.
Exception: Conductors shall be permitted to travel horizontally through
vertical sections where such conductors are isolated from the busbars by a
barrier.
(b) Phase Arrangement. The phase arrangement on 3-phase buses shall
be A, B, C from front to back, top to bottom, or left to right, as viewed
from the front of the motor control center.
Exception: Rear-mounted units connected to a vertical bus that is common to front-mounted units shall be permitted to have a C, B, A phase
arrangement where properly identified.
(c) Minimum Wire Bending Space. The minimum wire bending space at
the motor control center terminals and minimum gutter space shall be as
required in Article 373.
(d) Spacings. Spacings between motor control center bus terminals and
other bare metal parts shall not be less than specified in Table 430-97.
Table 430-97. Minimum Spacing Between Bare Metal Parts
Opposite Polarity
Opposite Polarity
Where Mounted on
Where Held
Live Parts
the Same Surface
Free in Air
to Ground
Not over 125 volts, nominal
3/4 inch
1/2 inch
½ inch
Not over 250 volts, nominal
1½ inch
3/4 inch
½ inch
Not over 600 volts, nominal
2 inches
1 inch
1 inch
For SI units: one inch = 25.4 millimeters.
(e) Barriers. Barriers shall be placed in all service-entrance motor control centers to isolate service busbars and terminals from the remainder of
the motor control center.
430-98. Marking.
(a) Motor Control Centers. Motor control centers shall be marked
according to Section 110-21, and such marking shall be plainly visible after
installation. Marking shall also include common power bus current rating
and motor control center short-circuit rating.
70-418
NATIONAL ELECTRICAL CODE
(b) Motor Control Units. Motor control units in a motor control center
shall comply with Section 430-8.
I. Disconnecting Means
430-101. General. Part I is intended to require disconnecting means
capable of disconnecting motors and controllers from the circuit.
(FPN No. 1): See Diagram 430-1.
(FPN No. 2): See Section 110-22 for identification of disconnecting means.
430-102. Location.
(a) Controller. A disconnecting means shall be located in sight from the
controller location and shall disconnect the controller.
Exception No. 1: For motor circuits over 600 volts, nominal, a controller disconnecting means capable of being locked in the open position shall
be permitted to be out of sight of the controller, provided the controller is
marked with a warning label giving the location of the disconnecting
means.
Exception No. 2: A single disconnecting means shall be permitted to be
located adjacent to a group of coordinated controllers mounted adjacent
one to each other on a multimotor continuous process machine.
(b) Motor. A disconnecting means shall be located in sight from the
motor location and the driven machinery location.
Exception: Where the disconnecting means provided in accordance
with Section 430-102(a) is capable of being locked in the open position.
430-103. Operation. The disconnecting means shall open all ungrounded
supply conductors and shall be so designed that no pole can be operated
independently. The disconnecting means shall be permitted in the same
enclosure with the controller.
(FPN): See Section 430-113 for equipment receiving energy from more than one
source.
430-104. To Be Indicating. The disconnecting means shall plainly indicate whether it is in the open ("off") or closed ("on") position.
430-105. Grounded Conductors. One pole of the disconnecting means
shall be permitted to disconnect a permanently grounded conductor, provided the disconnecting means is so designed that the pole in the grounded
conductor cannot be opened without simultaneously disconnecting all conductors of the circuit.
430-106. Service Switch as Disconnecting Means. Where an installation
consists of a single motor, the service switch shall be permitted to serve as
the disconnecting means if it complies with this article and is within sight
from the controller location.
430-107. Readily Accessible. One of the disconnecting means shall be
readily accessible.
ARTICLE 430 - MOTOR CIRCUITS, CONTROLLERS
70-419
430-108. Every Switch. Every disconnecting means in the motor
branch circuit between the point of attachment to the feeder and the
point of connection to the motor shall comply with the requirements of
Sections 430-109 and 430-110.
430-109. Type. The disconnecting means shall be one of the following
types: a motor-circuit switch rated in horsepower, a circuit breaker, or a
molded-case switch, and shall be a listed device.
Exception No. 1: For stationary motors of 1/8 horsepower or less, the
branch-circuit overcurrent device shall be permitted to serve as the disconnecting means.
Exception No. 2: For stationary motors rated at 2 horsepower or less
and 300 volts or less, the disconnecting means shall be permitted to be a
general-use switch having an ampere rating not less than twice the fullload current rating of the motor.
On ac circuits, general-use snap switches suitable only for use on ac
(not general-use ac-dc snap switches) shall be permitted to disconnect a
motor rated 2 horsepower or less and 300 volts or less having a full-load
current rating not more than 80 percent of the ampere rating of the switch.
Exception No. 3: For motors of over 2 horsepower to and including 100
horsepower, the separate disconnecting means required for a motor with
an autotransformer-type controller shall be permitted to be a general-use
switch where all of the following provisions are met:
a. The motor drives a generator that is provided with overload protection.
b. The controller (1) is capable of interrupting the locked-rotor current of the motor; (2) is provided with a no-voltage release; and (3) is provided with running overload protection not exceeding 125 percent of the
motor full-load current rating.
c. Separate fuses or an inverse time circuit breaker rated or set at not
more than 150 percent of the motor full-load current are provided in the
motor branch circuit.
Exception No. 4: For stationary motors rated at more than 40 horsepower direct current or 100 horsepower alternating current, the disconnecting means shall be permitted to be a general-use or isolating switch
where plainly marked "Do not operate under load."
Exception No. 5: For a cord- and plug-connected motor, a horsepowerrated attachment plug and receptacle having ratings no less than the
motor ratings shall be permitted to serve as the disconnecting means. A
horsepower-rated attachment plug and receptacle shall not be required for
a cord- and plug-connected appliance in accordance with Section 422-22,
a room air conditioner in accordance with Section 440-63, or a portable
motor rated 1/3 horsepower or less.
Exception No. 6: For torque motors, the disconnecting means shall be
permitted to be a general-use switch.
Exception No. 7: An instantaneous trip circuit breaker that is part of a
listed combination motor controller shall be permitted to serve as a disconnecting means.
70-420
NATIONAL ELECTRICAL CODE
430-110. Ampere Rating and Interrupting Capacity.
(a) General. The disconnecting means for motor circuits rated 600 volts,
nominal, or less, shall have an ampere rating of at least 115 percent of the
full-load current rating of the motor.
(b) For Torque Motors. Disconnecting means for a torque motor shall
have an ampere rating of at least 115 percent of the motor nameplate
current.
(c) For Combination Loads. Where two or more motors are used
together or where one or more motors are used in combination with other
loads, such as resistance heaters, and where the combined load may be
simultaneous on a single disconnecting means, the ampere and horsepower
ratings of the combined load shall be determined as follows:
(1) The rating of the disconnecting means shall be determined from the
summation of all currents, including resistance loads, at the full-load condition and also at the locked-rotor condition. The combined full-load current and the combined locked-rotor current so obtained shall be considered
as a single motor for the purpose of this requirement as follows:
The full-load current equivalent to the horsepower rating of each motor
shall be selected from Table 430-148, 430-149, or 430-150. These full-load
currents shall be added to the rating in amperes of other loads to obtain an
equivalent full-load current for the combined load.
The locked-rotor current equivalent to the horsepower rating of each
motor shall be selected from Table 430-151. The locked-rotor currents shall
be added to the rating in amperes of other loads to obtain an equivalent
locked-rotor current for the combined load. Where two or more motors or
other loads cannot be started simultaneously, appropriate combinations of
locked-rotor and full-load current shall be permitted to be used to determine the equivalent locked-rotor current for the simultaneous combined
loads.
Exception: Where part of the concurrent load is resistance load, and
where the disconnecting means is a switch rated in horsepower and
amperes, the switch used shall be permitted to have a horsepower rating
not less than the combined load of the motor(s), if the ampere rating of the
switch is not less than the locked-rotor current of the motor(s) plus the
resistance load.
(2) The ampere rating of the disconnecting means shall not be less than
115 percent of the summation of all currents at the full-load condition
determined in accordance with (c)(1) above.
(3) For small motors not covered by Tables 430-147, 430-148, 430-149,
or 430-150, the locked-rotor current shall be assumed to be six times the
full-load current.
430-111. Switch or Circuit Breaker as Both Controller and Disconnecting
Means. A switch or circuit breaker complying with Section 430-83 shall
be permitted to serve as both controller and disconnecting means if it
opens all ungrounded conductors to the motor, if it is protected by an
overcurrent device (which shall be permitted to be the branch-circuit fuses)
that opens all ungrounded conductors to the switch or circuit breaker, and
if it is of one of the types specified in (a), (b), or (c) below:
ARTICLE 430 - MOTOR CIRCUITS, CONTROLLERS
70-421
(a) Air-Break Switch. An air-break switch, operable directly by applying
the hand to a lever or handle.
(b) Inverse Time Circuit Breaker. An inverse time circuit breaker operable directly by applying the hand to a lever or handle.
(c) Oil Switch. An oil switch used on a circuit whose rating does not
exceed 600 volts or 100 amperes, or by special permission on a circuit
exceeding this capacity where under expert supervision.
The oil switch or circuit breaker specified above shall be permitted to be
both power and manually operable.
The overcurrent device protecting the controller shall be permitted to be
part of the controller assembly or shall be permitted to be separate.
An autotransformer-type controller shall be provided with a separate
disconnecting means.
430-112. Motors Served by Single Disconnecting Means. Each motor
shall be provided with an individual disconnecting means.
Exception: A single disconnecting means shall be permitted to serve
a group of motors under any one of the conditions of a, b, and c below.
The single disconnecting means shall be rated in accordance with Section 430-110(c):
a. Where a number of motors drive several parts of a single machine
or piece of apparatus, such as metal and woodworking machines, cranes,
and hoists.
b. Where a group of motors is under the protection of one set of
branch-circuit protective devices as permitted by Section 430-53(a).
c. Where a group of motors is in a single room within sight from the
location of the disconnecting means.
430-113. Energy from More than One Source. Motor and motor-operated
equipment receiving electrical energy from more than one source shall be
provided with disconnecting means from each source of electrical energy
immediately adjacent to the equipment served. Each source shall be permitted to have a separate disconnecting means.
Exception No. 1: Where a motor receives electrical energy from more
than one source, the disconnecting means for the main power supply to the
motor shall not be required to be immediately adjacent to the motor, provided the controller disconnecting means is capable of being locked in the
open position.
Exception No. 2: A separate disconnecting means shall not be required
for a Class 2 remote-control circuit conforming with Article 725, rated not
more than 30 volts, and that is isolated and ungrounded.
J. Over 600 Volts, Nominal
430-121. General. Part J recognizes the additional hazard due to the use
of higher voltages. It adds to or amends the other provisions of this article.
Other requirements for circuits and equipment operating at over 600 volts,
nominal, are in Article 710.
70-422
NATIONAL ELECTRICAL CODE
430-122. Marking on Controllers. In addition to the marking required by