Regl. 5293, art. 430-72(a)-725 dup2
REMOTE-CONTROL SIGNALING CIRCUITS
Cite as Reglamento Núm. 5293, Art. 430-72(a)-725 dup2
70-757
(2) To the power-supply conductors only, where the Class 1 circuit
conductors do not carry continuous loads in excess of 10 percent of the
ampacity of each conductor and where the number of power-supply conductors is more than three.
(c) Class 1 Circuit Conductors in Cable Trays. Where Class 1 circuit
conductors are installed in cable trays, they shall comply with the provisions of Sections 318-9 through 318-11.
725-18. Physical Protection. Where damage to remote-control circuits of
safety control equipment would introduce a hazard, as covered in Section
725-4, all conductors of such remote-control circuits shall be installed in
rigid metal conduit, intermediate metal conduit, rigid nonmetallic conduit,
electrical metallic tubing, Type MI cable, Type MC cable, or be otherwise
suitably protected from physical damage.
725-19. Circuits Extending Beyond One Building. Class 1 circuits that extend
aerially beyond one building shall also meet the requirements of Article 225.
725-20. Grounding. Class 1 circuits and equipment shall be grounded in
accordance with Article 250.
C. Class 2 and Class 3 Circuits
725-31. Power Limitations of Class 2 and Class 3 Circuits. As specified
in Table 725-31(a) for ac circuits and Table 725-31(b) for dc circuits, the
power for Class 2 and Class 3 circuits shall be either inherently limited
requiring no overcurrent protection or limited by a combination of a power
source and overcurrent protection.
Notes for Tables 725-31(a) and (b)
Note 1.
Vₘₐₓ: Maximum output voltage regardless of load with rated input applied.
Iₘₐₓ: Maximum output current under any noncapacitive load, including short circuit, and with overcurrent protection bypassed, if used. When a transformer limits
the output current, Iₘₐₓ limits apply after one minute of operation. Where a currentlimiting impedance, listed for the purpose, or as part of a listed product, is used in
combination with a nonpower-limited transformer or a stored energy source, e.g.,
storage battery, to limit the output current, Iₘₐₓ limits apply after 5 seconds.
VAₘₐₓ: Maximum volt-ampere output after one minute of operation regardless of
load and overcurrent protection bypassed, if used.
Current-limiting impedance shall not be bypassed when determining 1ₘₐₓ and VAₘₐₓ·
Note 2. For nonsinusoidal ac, Vₘₐₓ shall be not greater than 42.4 volts peak.
Where wet contact (immersion not included) is likely to occur, Class 3 wiring methods shall be used, or Vₘₐₓ shall be not greater than: 15 volts for sinusoidal ac: 21.2
volts peak for nonsinusoidal ac.
Note 3. If the power source is a transformer, (VA)ₘₐₓ is 350 or less where Vₘₐₓ
is 15 or less.
Note 4. A dry cell battery shall be considered an inherently limited power source,
provided the voltage is 30 volts or less and the capacity is equal to or less than that
available from series connected No. 6 carbon zinc cells.
Note 5: For dc interrupted at a rate of 10 to 200 Hz, Vₘₐₓ shall not be greater than
24.8 volts. Where wet contact (immersion not included) is likely to occur, Class 3
wiring methods shall be used, or Vₘₐₓ shall not be greater than: 30 volts for continuous dc; 12.4 volts for dc that is interrupted at a rate of 10 to 200 Hz.
Table 725-31(a). Power Source Limitations for Alternating Current Class 2 and Class 3 Circuits
70-758
Inherently Limited Power Source
Not Inherently Limited Power Source
(Overcurrent protection not required)
(Overcurrent protection required)
Circuit
Class 2
Class 3
Class 2
Class 3
Over
Over
Over
Circuit Voltage
0 through
Over 20 and
30 and
Over 30 and
0 through
Over 20 and
30 and
100 and
Vₘₐₓ (Volts) (Note 1)
20+
through 30+
through 150
through 100
20+
through 30+
through 100
through 150
Power Limitations
(VA) max (Volt-Amps)
250
-
-
-
-
250
250
N.A.
(Note 1)
(Note 3)
Current Limitations
max (Amps)
8.0
8.0
0.005
150/V max
1000/V
max
1000/V, max
1000/V
1.0
max
(Note 1)
Maximum Over-
-
-
-
-
5.0
100/V max
100/V max
1.0
current Protection
(Amps)
VA
Power Source
Maximum Nameplate Ratings
(Volt-Amps)
5.0 X Vₘₐₓ
100
0.005 X V. max
100
5.0 X Vₘₐₓ
100
NATIONAL ELECTRICAL CODE
100
100
Current
5.0
(Amps)
100/V max
0.005
100/V max
5.0
100/V. max
100/V max
100/V max
Supply Conductors
and Cables
See Section 725-37
Circuit Conductors
and Cables
See Sections 725-49 through 725-53
t Voltage ranges shown are for sinusoidal ac in indoor locations or where wet contact is not likely to occur. For nonsinusoidal or wet contact conditions, see Note 2.
Table 725-31(b). Power Source Limitations for Direct Current Class 2 and Class 3 Circuits
Inherently Limited Power Source (Note 4)
Not Inherently Limited Power Source
(Overcurrent protection not required)
(Overcurrent protection required)
Circuit
Class 2
Class 3
Class 2
Class 3
Over 20
Over 30,
Over 60
Over 60
Over 20
Over 60
Over 100
Circuit Voltage
0 through
and through
and through
and through
and through
0 through
and through
and through
and through
Vₘₐₓ (Volts) (Note 1)
20++
30++
60++
150
100
20++
60++
100
150
Power Limitations
(VA)
250
max
-
-
250
250
N.A.
-
-
-
(Volts-Amps)
(Note 3)
(Note 1)
Current Limitations
max (Amps)
8.0
8.0
150/V max
0.005
150/V max
1000/V max
1000/V max
1000/V max
1.0
(Note 1)
Maximum Overcurrent Protection
-
-
5.0
-
-
-
100/V max
100/V max
1.0
(Amps)
VA
5.0 X Vₘₐₓ
100
100
0.005 X Vₘₐₓ
100
5.0 X Vₘₐₓ
100
100
100
Power Source
Maximum Nameplate Ratings
(Volt-Amps)
ARTICLE 725 REMOTE-CONTROL, SIGNALING CIRCUITS
Current
5.0
100/V max
100/v max
0.005
100/V max
5.0
100/V max
100/v max
100/V max
(Amps)
Supply Conductors
See Section 725-37
and Cables
Circuit Conductors
See Sections 725-49 through 725-53
and Cables
tt Voltage ranges shown are for continuous dc in indoor locations or where wet contact is not likely to occur. For interrupted dc or wet contact
70-759
conditions, see Note 5.
70-760
NATIONAL ELECTRICAL CODE
725-32. Interconnection of Power Supplies. Class 2 or Class 3 power
supplies shall not be paralleled or otherwise interconnected unless listed
for such interconnection.
725-34. Marking. A Class 2 or Class 3 power supply unit shall be durably
marked where plainly visible to indicate the class of supply and its electrical rating.
725-35. Overcurrent Protection. Where overcurrent protection is
required, the overcurrent-protective devices shall not be interchangeable
with devices of higher ratings. The overcurrent device shall be permitted
as an integral part of the power supply.
725-36. Location of Overcurrent Devices. Overcurrent devices, where
required, shall be located at the point where the conductor to be protected
receives its supply.
725-37. Wiring Methods on Supply Side. Conductors and equipment on
the supply side of overcurrent protection, transformers, or current-limiting
devices shall be installed in accordance with the appropriate requirements
of Chapter 3. Transformers or other devices supplied from electric light or
power circuits shall be protected by an overcurrent device rated not over
20 amperes.
Exception: The input leads of a transformer or other power source
supplying Class 2 and Class 3 circuits shall be permitted to be smaller
than No. 14, but not smaller than No. 18 if they are not over 12 inches
(305 mm) long and if they have insulation that complies with Section
725-16(b).
725-38. Wiring Methods and Materials on Load Side. Conductors on the
load side of overcurrent protection, transformers, and current-limiting
devices shall be insulated at not less than the requirements of Section
725-50 and shall be installed in accordance with Section 725-52.
725-42. Circuit Conductors Extending Beyond One Building. Where
Class 2 or Class 3 circuit conductors that extend beyond one building and
are so run as to be subject to accidental contact with electric light or power
conductors operating at over 300 volts to ground, or are exposed to lightning on interbuilding circuits on the same premises, the requirements of the
following shall also apply:
(1) Sections 800-10, 800-12, 800-13, 800-30, 800-31, 800-32, 800-33, and
800-40 for other than coaxial conductors, and
(2) Sections 820-10, 820-33, and 820-40 for coaxial conductors.
725-43. Grounding. Class 2 and Class 3 circuits and equipment shall be
grounded in accordance with Article 250.
ARTICLE 725 - REMOTE-CONTROL, SIGNALING CIRCUITS
70-761
725-49. Fire Resistance of Cables Within Buildings. Single- and multiconductor cables of Class 2 and Class 3 circuits, including PLTC cables,
installed as wiring within buildings shall be listed as resistant to the spread
of fire in accordance with Sections 725-50 and 725-51.
725-50. Listing, Marking, and Installation of Class 2, Class 3, and PLTC
Cables.
(a) Class 2 and Class 3 Cables. Class 2 and Class 3 cables installed as
wiring within buildings shall be listed as being suitable for the purpose,
marked in accordance with Table 725-50, and installed in accordance
with Section 725-38. The cable voltage ratings shall not be marked on
the cable.
(FPN): Voltage markings on cables may be misinterpreted to suggest that the
cables may be suitable for Class 1, electric light and power applications.
Exception No. 1: Voltage markings shall be permitted where the cable
has multiple listings and voltage marking is required for one or more of the
listings.
Exception No. 2: Cable substitutions as provided for in Section 725-53(g)
shall be considered as suitable for the purpose and shall be permitted.
(b) PLTC. PLTC shall be marked in accordance with Section 310-11 and
Table 725-50 and shall be listed as being suitable for use in cable trays.
Table 725-50. Cable Markings
Cable
Marking
Type
Reference
CL3P
Class 3 Plenum Cable
725-51(a) and 725-53(a)
CL2P
Class 2 Plenum Cable
725-51(a) and 725-53(a)
CL3R
Class 3 Riser Cable
725-51(b) and 725-53(b)
CL2R
Class 2 Riser Cable
725-51(b) and 725-53(b)
PLTC
Power-Limited Tray Cable
725-51(e) and
725-53(c) and (d)
CL3
Class 3 Cable
725-51(c), 725-53(b), Exception
No. 2, and 725-53(e)
CL2
Class 2 Cable
725-51(c), 725-53(b), Exception
No. 2, and 725-53(e)
CL3X
Class 3 Cable, Limited Use
725-51(d), 725-53(b), Exception
No. 2, and 725-53(e), Exception
Nos. 1, 2, and 3
CL2X
Class 2 Cable, Limited Use
725-51(d), 725-53(b), Exception
No. 2, and 725-53(e), Exception
Nos. 1, 2, and 3
70-762
NATIONAL ELECTRICAL CODE
(FPN No. 1): Class 2 and Class 3 Cable types are listed in descending order of
fire resistance rating, and Class 3 cables are listed above Class 2 cables, since Class
3 cables may substitute for Class 2 cables.
(FPN No. 2): See the referenced sections for permitted uses.
725-51. Additional Listing Requirements. Class 2 and Class 3 cables
shall be listed in accordance with (a) through (f) below, and, where single
conductors are used for Class 3 circuits, with (g) below:
(a) Types CL2P and CL3P. Types CL2P and CL3P plenum cables shall
be listed as being suitable for use in ducts, plenums, and other space used
for environmental air and shall also be listed as having adequate fireresistant and low-smoke-producing characteristics.
(FPN): One method of defining low-smoke-producing cable is by establishing an
acceptable value of the smoke produced when tested in accordance with Test for
Fire and Smoke Characteristics of Wires and Cables, NFPA 262-1990 (ANSI) to a
maximum peak optical density of 0.5 and a maxiumum average optical density of
0.15. Similarly, one method of defining fire-resistant cables is by establishing maximum allowable flame travel distance of 5 feet (1.52 m) when tested in accordance
with the same test.
(b) Types CL2R and CL3R. Types CL2R and CL3R riser cables shall be
listed as being suitable for use in a vertical run in a shaft or from floor to
floor and shall also be listed as having fire-resistant characteristics capable
of preventing the carrying of fire from floor to floor.
(FPN): One method of defining fire-resistant characteristics capable of preventing the carrying of fire from floor to floor is that the cables pass the requirements of
Test for Flame Propagation Height of Electrical and Optical-Fiber Cable Installed
Vertically in Shafts, ANSI/UL 1666-1986.
(c) Types CL2 and CL3. Types CL2 and CL3 cables shall be listed as
being suitable for general-purpose use, with the exception of risers, ducts,
plenums, and other space used for environmental air, and shall also be
listed as being resistant to the spread of fire.
(FPN): One method of defining resistant to spread of fire is that the cables do
not spread fire to the top of the tray in the "Vertical Tray Flame Test" in Reference
Standard for Electrical Wires, Cables and Flexible Cords, ANSI/UL 1581-1985.
Another method of defining resistant to the spread of fire is for the damage (char
length) not to exceed 4 feet 11 inches (1.5 m) when performing the CSA "Vertical
Flame Test - Cables in Cable Trays," as described in Test Methods for Electrical
Wires and Cables, CSA C22.2 No. 0.3-M-1985.
(d) Types CL2X and CL3X. Types CL2X and CL3X limited use cables
shall be listed as being suitable for use in dwellings and for use in raceway
and shall also be listed as being flame-retardant.
(FPN): One method of determining that cable is flame-retardant is by testing the
cable to the "VW-1 (Vertical-Wire) Flame Test" in the Reference Standard for
Electrical Wires, Cables and Flexible Cords, ANSI/UL 1581-1985.
(e) Type PLTC. Type PLTC nonmetallic-sheathed, power-limited tray
cable shall be a factory assembly of two or more insulated conductors
under a nonmetallic jacket. The insulated conductors shall be Nos. 22
through 12. The conductor material shall be copper (solid or stranded).
ARTICLE 725 - REMOTE-CONTROL, SIGNALING CIRCUITS
70-763
Insulation on conductors shall be suitable for 300 volts. The cable core
shall be either (1) two or more parallel conductors; (2) one or more group
assemblies of twisted or parallel conductors; or (3) a combination thereof.
A metallic shield or a metallized foil shield with drain wire(s) shall be permitted to be applied either over the cable core, over groups of conductors,
or both. The cable shall be listed as being resistant to the spread of fire.
The outer jacket shall be a sunlight- and moisture-resistant nonmetallic
material.
Exception: Where a smooth metallic sheath, welded and corrugated
metallic sheath, or interlocking tape armor is applied over the nonmetallic
jacket, an overall nonmetallic jacket shall not be required. On metallicsheathed cable without an overall nonmetallic jacket, the information
required in Section 310-11 shall be located on the nonmetallic jacket under
the sheath.
(FPN): One method of defining resistant to spread of fire is that the cables
do not spread fire to the top of the tray in the "Vertical Tray Flame Test" in the
Reference Standard for Electrical Wires, Cables and Flexible Cords, ANSI/UL
1581-1985.
Another method of defining resistant to the spread of fire is for the damage (char
length) not to exceed 4 feet, 11 inches (1.5 m) when performing the CSA "Vertical
Flame Test - Cables in Cable Trays," as described in Test Methods for Electrical
Wires and Cables, CSA C22.2 No. 0.3-M-1985.
(f) Voltage Rating. Class 3 cables shall have a voltage rating of not less
than 300 volts.
(g) Single Conductors. Class 3 single conductors shall not be smaller
than No. 18 and shall be insulated in accordance with Section 725-16(b).
725-52. Installation of Conductors and Equipment. Conductors and
equipment on the load side of overcurrent protection, transformers, and
current-limiting devices shall comply with (a) and (b) below.
(a) Separation from Electric Light, Power, Class 1, and Nonpower-
Limited Fire Protective Signaling Circuit Conductors.
(1) Open Conductors. Conductors of Class 2 and Class 3 circuits shall
be separated by at least 2 inches (50.8 mm) from conductors of any electric
light, power, Class 1, or nonpower-limited fire protective signaling circuits.
Exception No. 1: Where either (1) all of the electric light, power, Class
1, and nonpower-limited fire protective signaling circuit conductors, or
(2) all of the Class 2 and Class 3 circuit conductors are in raceway or in
metal-sheathed, metal-clad, nonmetallic-sheathed, or Type UF cables.
Exception No. 2: Where the conductors are permanently separated
from the conductors of the other circuits by a continuous and firmly fixed
nonconductor, such as porcelain tubes or flexible tubing, in addition to the
insulation on the wire.
(2) In Cable, Cable Trays, Enclosures, and Raceways. Conductors of
Class 2 and Class 3 circuits shall not be placed in any cable, cable tray,
compartment, enclosure, outlet box, raceway, or similar fitting with conductors of electric light, power, Class 1, and nonpower-limited fire protective signaling circuits.
70-764
NATIONAL ELECTRICAL CODE
Exception No. 1: Where the conductors of the different circuits are separated by a barrier. In enclosures, Class 2 or Class 3 circuits shall be permitted to be installed in a raceway within the enclosure to separate them
from Class 1, electric light and power circuits.
Exception No. 2: Conductors in compartments, enclosures, outlet
boxes, or similar fittings, where electric light, power, Class 1, or
nonpower-limited fire protective signaling circuit conductors are introduced solely to connect to the equipment connected to Class 2 or Class 3
circuits to which the other conductors in the enclosure are connected. The
electric light, power, Class 1, and nonpower-limited fire protective signaling circuit conductors shall be routed within the enclosure to maintain a
minimum 0.25-inch (6.35-mm) separation from the conductors of Class 2
and Class 3 circuits.
Exception No. 3: Underground conductors in a manhole where one of
the following conditions is met:
a. The electric light, power, Class 1, and nonpower-limited fire protective signaling circuit conductors are in a metal-enclosed cable or Type
UF cable;
b. The conductors are permanently and effectively separated from
the conductors of the other circuits by a continuous and firmly fixed nonconductor, such as flexible tubing, in addition to the insulation or covering
on the wire;
c. The conductors are permanently and effectively separated from
conductors of the other circuits and securely fastened to racks, insulators,
or other approved supports.
Exception No. 4: As permitted by Section 780-6(a) and installed in
accordance with Article 780.
(3) In Hoistways. Class 2 or Class 3 circuit conductors shall be
installed in rigid metal conduit, rigid nonmetallic conduit, intermediate
metal conduit, or electrical metallic tubing in hoistways.
Exception: As provided for in Section 620-21, Exception Nos. 1 and 2
for elevators and similar equipment.
(4) In Shafts. Class 2 or Class 3 circuit conductors shall be separated
by not less than 2 inches (50.8 mm) from electric light, power, Class 1, or
nonpower-limited fire protective signaling circuit conductors run in the
same shaft.
Raceway. (b) Conductors of Different Circuits in Same Cable, Enclosure, or
(1) Two or More Class 2 Circuits. Conductors of two or more Class 2
circuits shall be permitted within the same cable, enclosure, or raceway,
provided all conductors in the cable, enclosure, or raceway are insulated
for the maximum voltage of any conductor.
(2) Two or More Class 3 Circuits. Conductors of two or more Class 3
circuits shall be permitted within the same cable, enclosure, or raceway.
(3) Class 2 Circuits with Class 3 Circuits. Conductors of one or more
Class 2 circuits shall be permitted within the same cable, enclosure, or
ARTICLE 725 - REMOTE-CONTROL, SIGNALING CIRCUITS
70-765
raceway with conductors of Class 3 circuits, provided that the insulation of
the Class 2 circuit conductors in the cable, enclosure, or raceway is at least
that required for Class 3 circuits.
(4) Class 2 or Class 3 Circuits with Other Circuits. Jacketed cables of
Class 2 or Class 3 circuits shall be permitted in the same enclosure or raceway with jacketed cables of any of the following:
a. Power-limited fire protective signaling systems in compliance
with Article 760.
b. Nonconductive and conductive optical fiber cables in compliance with Article 770.
c. Communications circuits in compliance with Article 800.
d. Community antenna television and radio distribution systems in
compliance with Article 820.
(c) Support of Conductors. Raceways shall not be used as a means of
support for Class 2 or Class 3 circuit conductors.
Exception: Except as permitted by Section 300-11(b), Exception No. 2.
725-53. Applications of Listed Class 2, Class 3, and PLTC Cables. Class
2, Class 3, and PLTC cables shall comply with (a) through (g) below.
(a) Plenum. Cables installed in ducts, plenums, and other spaces used
for environmental air shall be Type CL2P or CL3P.
Exception: Listed wires and cables installed in compliance with Section
300-22.
(b) Riser. Cables installed in vertical runs and penetrating more than
one floor, or cables installed in vertical runs in a shaft, shall be Type CL2R
or CL3R. Floor penetrations requiring Type CL2R or CL3R shall contain
only cables suitable for riser or plenum use.
Exception No. 1: Other cables as covered in Table 725-53 and other
listed wiring methods as covered in Chapter 3, where these are installed in
metal raceways or located in a fireproof shaft having firestops at each
floor.
Exception No. 2: Types CL2, CL3, CL2X, and CL3X cable in one- and
two-family dwellings.
(FPN): See Section 300-21 for firestop requirements for floor penetrations.
(c) Cable Trays. Cables installed in cable trays shall be Type PLTC.
Exception: Conductors in PLTC cables used for Class 2 thermocouple
circuits shall be permitted to be any of the materials used for thermocouple extension wire.
(d) Hazardous (Classified) Locations. Cables installed in hazardous
(classified) locations shall be Type PLTC. Where the use of PLTC cable is
permitted in Section 501-4(b), the cable shall be installed in cable trays, in
raceways, supported by messenger wire, or directly buried where the cable
is listed for this use.
70-766
NATIONAL ELECTRICAL CODE
Exception. Exception No. 1: For Class 2 circuits as permitted by Section 501-4(b),
Exception No. 2: Conductors in PLTC cables used for Class 2 thermocouple circuits shall be permitted to be any of the materials used for thermocouple extension wire.
(e) Other Wiring Within Buildings. Cables installed in building locations
other than the locations covered in (a) through (d) above shall be Type CL2
or CL3.
Exception No. 1: Type CL2X or CL3X where installed in a raceway, or
other wiring methods as covered in Chapter 3.
Exception No. 2: In nonconcealed spaces where the exposed length of
cable does not exceed 10 feet (3.05 m).
Exception No. 3: Listed Type CL2X, Class 2 cables less than 0.25 inch
(6.4 mm) in diameter and listed Type CL3X, Class 3 cables less than
0.25 inch (6.4 mm) in diameter installed in one- or two-family or multifamily dwellings.
(f) Cross-Connect Arrays. Type CL2 or CL3 wire or cable shall be
used.
(g) Cable Substitutions. The substitutions for Class 2 and Class 3
permitted. cables listed in Table 725-53 and illustrated in Figure 725-53 shall be
Table 725-53. Cable Substitutions
Cable Type
Permitted Substitutions
CL3P
MPP, CMP, FPLP
CL2P
MPP, CMP, FPLP, CL3P
CL3R
MPP, CMP, FPLP, CL3P,
MPR, CMR, FPLR
CL2R
MPP, CMP, FPLP, CL3P, CL2P,
MPR, CMR, FPLR, CL3R
CL3
MPP, CMP, FPLP, CL3P,
MPR, CMR, FPLR, CL3R,
MPG, MP, CMG, CM, FPL, PLTC
CL2
MPP, CMP, FPLP, CL3P, CL2P,
MPR, CMR, FPLR, CL3R, CL2R
MPG, MP, CMG, CM, FPL, PLTC, CL3
CL3X
MPP, CMP, FPLP, CL3P,
MPR, CMR, FPLR, CL3R,
MPG, MP, CMG, CM, FPL, PLTC, CL3,
CMX
CL2X
MPP, CMP, FPLP, CL3P, CL2P,
MPR, CMR, FPLR, CL3R, CL2R,
MPG, MP, CMG, CM, FPL, PLTC, CL3,
CL2, CMX, CL3X
(FPN): For information on FPLP, FPLR, and FPL cables, see Section 760-50. For information on MPP, MPR, MPG, MP, CMP, CMR, CMG, and CM cables, see Section 800-50.