Regl. 5293, art. 440-52(a)(3)-445
GENERATORS
Cite as Reglamento Núm. 5293, Art. 440-52(a)(3)-445
445-1. General. Generators and their associated wiring and equipment
shall also comply with the applicable provisions of Articles 230, 250, 700,
701, 702, and 705.
445-2. Location. Generators shall be of a type suitable for the locations
in which they are installed. They shall also meet the requirements for
motors in Section 430-14. Generators installed in hazardous (classified)
locations as described in Articles 500 through 503, or in other locations as
described in Articles 510 through 517, and in Articles 520, 530, and 665
shall also comply with the applicable provisions of those articles.
445-3. Marking. Each generator shall be provided with a nameplate giving the maker's name, the rated frequency, power factor, number of
phases if of alternating current, the rating in kilowatts or kilovolt amperes,
the normal volts and amperes corresponding to the rating, rated revolutions per minute, insulation system class and rated ambient temperature or
rated temperature rise, and time rating.
445-4. Overcurrent Protection.
(a) Constant-Voltage Generators. Constant-voltage generators, except
alternating-current generator exciters, shall be protected from overloads by
inherent design, circuit breakers, fuses, or other acceptable overcurrent
protective means suitable for the conditions of use.
(b) Two-Wire Generators. Two-wire, direct-current generators shall
be permitted to have overcurrent protection in one conductor only if the
overcurrent device is actuated by the entire current generated other
than the current in the shunt field. The overcurrent device shall not
open the shunt field.
(c) 65 Volts or Less. Generators operating at 65 volts or less and driven
by individual motors shall be considered as protected by the overcurrent
device protecting the motor if these devices will operate when the generators
are delivering not more than 150 percent of their full-load rated current.
(d) Balancer Sets. Two-wire, direct-current generators used in conjunction with balancer sets to obtain neutrals for 3-wire systems shall be
equipped with overcurrent devices that will disconnect the 3-wire system
in case of excessive unbalancing of voltages or currents.
(e) Three-Wire, Direct-Current Generators. Three-wire, direct-current
generators, whether compound or shunt wound, shall be equipped with
overcurrent devices, one in each armature lead, and so connected as to be
actuated by the entire current from the armature. Such overcurrent devices
shall consist either of a double-pole, double-coil circuit breaker, or of a
4-pole circuit breaker connected in the main and equalizer leads and
tripped by two overcurrent devices, one in each armature lead. Such protective devices shall be so interlocked that no one pole can be opened
without simultaneously disconnecting both leads of the armature from the
system.
Exception to (a) through (e): Where deemed by the authority having
jurisdiction, a generator is vital to the operation of an electrical system