Regl. 5293, art. 440-52(a)(3)-450 dup3
TRANSFORMERS AND TRANSFORMER VAULTS 70-445
Cite as Reglamento Núm. 5293, Art. 440-52(a)(3)-450 dup3
Where fuses are used, their continuous current rating shall not exceed
250 percent of the rated primary current of the transformer. Where circuit breakers or electronically-actuated fuses are used, they shall be
set at not more than 300 percent of the rated primary current of the
transformer.
Table 450-3(a)(1).
Transformers Over 600 Volts
Maximum Rating or Setting for Overcurrent Device
Primary
Secondary
Over 600 Volts
Over 600 Volts
600 Volts or Below
Transformer
Circuit
Circuit
Circuit Breaker
Rated
Breaker
Fuse
Breaker
Fuse
Setting or
Impedance
Setting
Rating
Setting
Rating
Fuse Rating
Not more than 6%
600%
300%
300%
250%
125%
More than 6% and
not more than 10%
400%
300%
250%
225%
125%
Exception No. 1: Where the required fuse rating or circuit breaker setting does not correspond to a standard rating or setting, the next higher
standard rating or setting shall be permitted.
Exception No. 2: An individual overcurrent device shall not be required
where the primary circuit overcurrent device provides the protection specified in this section.
Exception No. 3: As provided in (a)(2)b below:
b. Primary and Secondary. A transformer over 600 volts, nominal,
having an overcurrent device on the secondary side rated or set to open
at not more than the values noted in Table 450-3(a)(2)b, or a transformer
equipped with a coordinated thermal overload protection by the manufacturer, shall not be required to have an individual overcurrent device
in the primary connection, provided the primary feeder overcurrent
device is rated or set to open at not more than the values noted in Table
450-3(a)(2)b.
Table 450-3(a)(2)b.
Transformers Over 600 Volts in Supervised Locations
Maximum Rating or Setting for Overcurrent Device
Primary
Secondary
Over 600 Volts
Over 600 Volts
600 Volts or Below
Transformer
Circuit
Circuit
Circuit Breaker
Rated
Breaker
Fuse
Breaker
Fuse
Setting or
Impedance
Setting
Rating
Setting
Rating
Fuse Rating
Not more than 6%
600%
300%
300%
250%
250%
More than 6% and
not more than 10%
400%
300%
250%
225%
250%
70-446
NATIONAL ELECTRICAL CODE
(b) Transformers 600 Volts, Nominal, or Less. Overcurrent protection
of transformers rated 600 volts, nominal, or less, shall comply with (1) or
(2) below.
(1) Primary. Each transformer 600 volts, nominal, or less, shall be
protected by an individual overcurrent device on the primary side, rated
or set at not more than 125 percent of the rated primary current of the
transformer.
Exception No. 1: Where the rated primary current of a transformer is 9
amperes or more and 125 percent of this current does not correspond to a
standard rating of a fuse or nonadjustable circuit breaker, the next higher
standard rating described in Section 240-6 shall be permitted. Where the
rated primary current is less than 9 amperes, an overcurrent device rated or
set at not more than 167 percent of the primary current shall be permitted.
Where the rated primary current is less than 2 amperes, an overcurrent
device rated or set at not more than 300 percent shall be permitted.
Exception No. 2: An individual overcurrent device shall not be required
where the primary circuit overcurrent device provides the protection specified in this section.
Exception No. 3: As provided in (b)(2) below.
(2) Primary and Secondary. A transformer 600 volts, nominal, or less,
having an overcurrent device on the secondary side rated or set at not
more than 125 percent of the rated secondary current of the transformer
shall not be required to have an individual overcurrent device on the primary side if the primary feeder overcurrent device is rated or set at'a current value not more than 250 percent of the rated primary current of the
transformer.
A transformer 600 volts, nominal, or less, equipped with coordinated
thermal overload protection by the manufacturer and arranged to interrupt
the primary current, shall not be required to have an individual overcurrent
device on the primary side if the primary feeder overcurrent device is rated
or set at a current value not more than six times the rated current of the
transformer for transformers having not more than 6 percent impedance,
and not more than four times the rated current of the transformer for
transformers having more than 6 percent but not more than 10 percent
impedance.
Exception: Where the rated secondary current of a transformer is
9 amperes or more and 125 percent of this current does not correspond to
a standard rating of a fuse or nonadjustable circuit breaker, the next
higher standard rating described in Section 240-6 shall be permitted.
Where the rated secondary current is less than 9 amperes, an overcurrent device rated or set at not more than 167 percent of the rated secondary current shall be permitted.
(c) Voltage Transformers. Voltage transformers installed indoors or
enclosed shall be protected with primary fuses.