Regl. 5293, art. 501-5-512
GASOLINE DISPENSING, SERVICE STATIONS
Cite as Reglamento Núm. 5293, Art. 501-5-512
70-511
Table 514-2.* Class I Locations - Service Stations
Class I,
Group D
Location
Division
Extent of Classified Location
Underground Tank
Fill Opening
1
Any pit, box, or space below
grade level, any part of which is
within the Division 1 or 2 classified location.
2
Up to 18 inches above grade level
within a horizontal radius of 10
feet from a loose fill connection
and within a horizontal radius of 5
feet from a tight fill connection.
Vent - Discharging
1
Within 3 feet of open end of vent,
Upward
extending in all directions.
2
Space between 3 feet and 5 feet of
open end of vent, extending in all
directions.
Dispensing Device
(except overhead type)*
Pits
1
Any pit, box, or space below
grade level, any part of which is
within the Division 1 or 2 classified location.
Dispenser
(FPN): Space classification inside
the dispenser enclosure is covered
in Power Operated Dispensing
Devices for Petroleum Products,
ANSI/UL 87-1987.
2
Within 18 inches horizontally in
all directions extending to grade
from (1) the dispenser enclosure
or (2) that portion of the dispenser
enclosure containing liquid handling components.
(FPN): Space classification inside
the dispenser enclosure is covered
in Power Operated Dispensing
Devices for Petroleum Products,
ANSI/UL 87-1987.
Outdoor
2
Up to 18 inches above grade level
within 20 feet horizontally of any
edge of enclosure.
Indoor
with Mechanical
2
Up to 18 inches above grade or
Ventilation
floor level within 20 feet horizontally of any edge of enclosure.
with Gravity Ventilation
2
Up to 18 inches above grade or
floor level within 25 feet horizontally of any edge of enclosure.
70-512
NATIONAL ELECTRICAL CODE
Table 514-2. Class I Locations - Service Stations (cont.)
Class I,
Group D
Location
Division
Extent of Classified Location
Dispensing Device
Overhead Type*
1
The space within the dispenser
enclosure, and all electrical equipment integral with the dispensing
hose or nozzle.
2
A space extending 18 inches horizontally in all directions beyond the
enclosure and extending to grade.
2
Up to 18 inches above grade level
within 20 feet horizontally measured from a point vertically
below the edge of any dispenser
enclosure.
Remote Pump - Outdoor
1
Any pit, box, or space below
grade level if any part is within a
horizontal distance of 10 feet from
any edge of pump.
2
Within 3 feet of any edge of
pump, extending in all directions.
Also up to 18 inches above grade
level within 10 feet horizontally
from any edge of pump.
Remote Pump - Indoor
1
Entire space within any pit.
2
Within 5 feet of any edge of
pump, extending in all directions.
Also up to 3 feet above grade
level within 25 feet horizontally
from any edge of pump.
Lubrication or Service Room -
1
Any pit within any unventilated
with Dispensing
space.
2
Any pit with ventilation.
2
Space up to 18 inches above floor
or grade level and 3 feet horizontally from a lubrication pit.
Dispenser for Class I Liquids
2
Within 3 feet of any fill or dispensing point, extending in all directions.
Lubrication or Service Room -
2
Entire area within any pit used for
without Dispensing
lubrication or similar services
where Class I liquids may be
released.
2
Area up to 18 inches above any
such pit, and extending a distance
of 3 ft horizontally from any edge
of the pit.
2
Entire unventilated area within any
pit, below-grade area, or subfloor
area.