Regl. 5293, art. 501-5-514
GASOLINE DISPENSING, SERVICE STATIONS 70-509
Cite as Reglamento Núm. 5293, Art. 501-5-514
manently affixed warning sign to read: "WARNING - KEEP 5 FEET
CLEAR OF AIRCRAFT ENGINES AND FUEL TANK AREAS."
(b) Cords and Connectors. Flexible cords for mobile equipment shall
be suitable for the type of service and approved for extra-hard usage and
shall include an equipment grounding conductor. Attachment plugs and
receptacles shall be approved for the location in which they are installed
and shall provide for connection of the equipment grounding conductor.
(c) Restricted Use. Equipment that is not identified as suitable for Class
I, Division 2 locations shall not be operated in locations where maintenance operations likely to release flammable liquids or vapors are in
progress.
513-12. Grounding. All metal raceways, metal-jacketed cables, and all
noncurrent-carrying metal portions of fixed or portable equipment, regardless of voltage, shall be grounded as provided in Article 250.