Regl. 5293, art. 501-5-514 dup2
GASOLINE DISPENSING
Cite as Reglamento Núm. 5293, Art. 501-5-514 dup2
AND SERVICE STATIONS
514-1. Definition. A gasoline dispensing and service station is a location
where gasoline or other volatile flammable liquids or liquefied flammable
gases are transferred to the fuel. tanks (including auxiliary fuel tanks) of
self-propelled vehicles or approved containers.
Other areas used as lubritoriums, service rooms, repair rooms, offices,
salesrooms, compressor rooms, and similar locations shall comply with
Articles 510 and 511 with respect to electric wiring and equipment.
Where the authority having jurisdiction can satisfactorily determine that
flammable liquids having a flash point below 38°C (100°F), such as gasoline,
will not be handled, such location shall not be required to be classified.
(FPN No. 1): For further information regarding safeguards for gasoline dispensing and service stations, see Automotive and Marine Service Station Code, NFPA
30A-1990.
(FPN No. 2): For information on classified areas pertaining to LP-Gas Systems
other than residential or commercial, see Storage and Handling of Liquefied Petroleum Gases, NFPA 58-1992 and Storage and Handling of Liquefied Petroleum Gases
at Utility Gas Plants, NFPA 59-1992.
(FPN No. 3): See Section 555-9 for gasoline dispensing stations in marinas and
boatyards.
514-2.* Class I Locations. Table 514-2 shall be applied where Class I liquids are stored, handled, or dispensed and shall be used to delineate and
classify service stations. A Class I location shall not extend beyond an
unpierced wall, roof, or other solid partition.
514-3. Wiring and Equipment Within Class I Locations. All electric
equipment and wiring within Class I locations defined in Section 514-2 shall
comply with the applicable provisions of Article 501.
70-510
NATIONAL ELECTRICAL CODE
Exception: As permitted in Section 514-8.
(FPN): For special requirements for conductor insulation, see Section 501-13.
514-4. Wiring and Equipment Above Class I Locations. Wiring and
equipment above the Class I locations defined in Section 514-2 shall comply with Sections 511-6 and 511-7.
514-5. Circuit Disconnects.
(a) General. Each circuit leading to or through dispensing equipment,
including equipment for remote pumping systems, shall be provided with a
switch or other acceptable means to disconnect simultaneously from the
source of supply all conductors of the circuit, including the grounded conductor, if any.
Single-pole breakers utilizing handle ties shall not be permitted.
(b) Attended Self-Service Stations.* Emergency controls as specified in
(a) above shall be installed at a location acceptable to the authority having
jurisdiction, but controls shall not be more than 100 feet (30 m) from
dispensers.
(c) Unattended Self-Service Stations.* Emergency controls as specified
in (a) above shall be installed at a location acceptable to the authority having jurisdiction, but the controls shall be more than 20 feet (7 m) but less
than 100 feet (30 m) from the dispensers. Additional emergency controls
shall be installed on each group of dispensers or the outdoor equipment
used to control the dispensers. Emergency controls shall shut off all power
to all dispensing equipment at the station. Controls shall be manually reset
only in a manner approved by the authority having jurisdiction.
(FPN): For additional information, see Sections 9-4.5 and 9-5.3 of Automotive
and Marine Service Station Code, NFPA 30A-1990.
514-6. Sealing.
(a) At Dispenser. An approved seal shall be provided in each conduit
run entering or leaving a dispenser or any cavities or enclosures in direct
communication therewith. The sealing fitting shall be the first fitting after
the conduit emerges from the earth or concrete.
(b) At Boundary. Additional seals shall be provided in accordance with