Regl. 5293, art. 501-6(b)-20
0, receptacles, attachment plugs, connectors, and similar devices
Cite as Reglamento Núm. 5293, Art. 501-6(b)-20
shall be of the grounding type, and the grounded conductor of the flexible
cord shall be connected to the screw shell of any lampholder or to the
grounded terminal of any utilization equipment supplied. Approved means
shall be provided for maintaining continuity of the grounding conductor
between the fixed wiring system and the noncurrent-carrying metal
portions of pendant fixtures, portable lamps, and portable utilization
equipment.
513-5. Equipment Not Within Class I Locations.
(a) Arcing Equipment. In locations other than those described in Section 513-2, equipment that is less than 10 feet (3.05 m) above wings and
engine enclosures of aircraft and that may produce arcs, sparks, or particles of hot metal, such as lamps and lampholders for fixed lighting, cutouts,
switches, receptacles, charging panels, generators, motors, or other equipment having make-and-break or sliding contacts, shall be of the totally
enclosed type or so constructed as to prevent escape of sparks or hot metal
particles.
Exception: Equipment in areas described in Section 513-2(d) shall be
permitted to be of the general-purpose type.
(b) Lampholders. Lampholders of metal-shell, fiber-lined types shall
not be used for fixed incandescent lighting.
(c) Portable Lighting Equipment. Portable lighting equipment that are
used within a hangar shall be approved for the location in which they are
used.
(d) Portable Equipment. Portable utilization equipment that is or may
be used within a hangar shall be of a type suitable for use in Class I, Division 2 locations.
513-6. Stanchions, Rostrums, and Docks.
(a) In Class I Location. Electric wiring, outlets, and equipment (including lamps) on or attached to stanchions, rostrums, or docks that are
located or likely to be located in a Class I location as defined in Section
513-2(c) shall comply with the requirements for Class I, Division 2
locations.
(b) Not in Class I Location. Where stanchions, rostrums, or docks are
not located or likely to be located in a Class I location as defined in Section 513-2(c), wiring and equipment shall comply with Sections 513-4 and
513-5, except that such wiring and equipment not more than 18 inches (457
mm) above the floor in any position shall comply with (a) above. Receptacles and attachment plugs shall be of a locking type that will not readily
disconnect.
70-508
NATIONAL ELECTRICAL CODE
(c) Mobile Type. Mobile stanchions with electric equipment complying
with (b) above shall carry at least one permanently affixed warning sign to
read: "WARNING - KEEP 5 FEET CLEAR OF AIRCRAFT
ENGINES AND FUEL TANK AREAS."
513-7. Sealing. Approved seals shall be provided in accordance with