Regl. 5293, art. 520-44(a)-250
Resolución 2535: adopta el Código Eléctrico Nacional, versión 1993. (Sustituye el Anejo A del Reglamento 4435)
Cite as Reglamento Núm. 5293, Art. 520-44(a)-250
(FPN): See Section 250-21 for objectionable current over grounding conductors.
Exception No. 1: The main bonding jumper shall not be required at the
distribution panelboard in or on buildings housing livestock or poultry
where all the following conditions are met:
a. All buildings and premises wiring are under the same ownership.
b. An equipment grounding conductor is run with the supply conductors and is of the same size as the largest supply conductor, if of the same
material, or is adjusted in size in accordance with the equivalent size columns of Table 250-95 if of different materials.
c. Service disconnecting means is provided at the distribution point
for supply to those buildings.
d. The equipment grounding conductor is bonded to the grounded
circuit conductor at the service equipment or the source of a separately
derived system.
e. A grounding electrode is provided and connected to the equipment
grounding conductor in the distribution panelboard.
Exception No. 2: A metal interior water piping system or other interior
metal or metallic piping system of an agricultural building to which electrical equipment requiring grounding is not attached or in electrical contact shall be permitted to be bonded to the service equipment enclosure,
the grounded conductor at the service, or to the equipment grounding terminal bar in a panelboard that serves the building by means of an impedance device listed for the purpose, provided that all the following conditions are complied with:
a. The device shall have the short-circuit withstand rating identified
where other than the minimum of 10,000 amperes.
b. The bonding conductor shall be an insulated copper conductor not
smaller than No. 8 and shall be installed without splice other than where
connected to the impedance device.
C. The bonding conductor shall be installed in a raceway suitable for
the conditions.
d. The bonding conductor shall be connected to the metal piping system or other metal by means of a listed pressure connector suitable for the
conditions or by exothermic welding.
(b) Concrete Embedded Elements. Wire mesh or other conductive elements where provided in the concrete floor of animal confinement areas to
provide an equipotential plane shall be bonded to the building grounding
electrode system. The bonding conductor shall be copper, insulated, covered or bare, and not smaller than No. 8. The means of bonding to wire
70-588
NATIONAL ELECTRICAL CODE
mesh or conductive elements shall be by pressure connectors or clamps of
brass, copper, copper alloy, or an equally substantial approved means.
Equipotential Plane: An equipotential plane is an area where a wire
mesh or other conductive elements are embedded in concrete, bonded to
all adjacent conductive equipment, structures, or surfaces, and connected
to the electrical grounding system to prevent a difference in voltage from
developing within the plane.
(FPN): If a wire mesh or other conductive grid is embedded in a concrete floor
or platform, and, if this grid is bonded to the electrical system grounding bus, livestock making contact between the concrete floor or platform and the equipment or
metal structure will be less likely to be exposed to a level of voltage that may alter
animal behavior or productivity.
(c) Separate Equipment Grounding Conductor. In agricultural buildings
as described in Sections 547-1(a) and (b), noncurrent-carrying metal parts
of equipment, raceways, and other enclosures, where required to be
grounded, shall be grounded by a copper equipment grounding conductor
installed between the equipment and the building disconnecting means. If
installed underground, the equipment grounding conductor shall be insulated or covered.
(FPN): Grounding electrode system resistances lower than required by Article
250, Part H, may reduce potential differences in livestock facilities.
(d) Water Pumps and Metal Well Casings. The frame of the motor of any
water pump shall be grounded as required for Section 430-142. Where a submersible pump is used in metal well casing, the well casing shall be bonded
to the pump circuit equipment grounding conductor, or to the equipment
grounding bus of the panelboard supplying the submersible pump.