Regl. 5293, art. 520-44(a)-545 dup2
MANUFACTURED BUILDING
Cite as Reglamento Núm. 5293, Art. 520-44(a)-545 dup2
A. General
545-1. Scope. This article covers requirements for a manufactured building and building components as herein defined.
545-2. Other Articles. Wherever the requirements of other articles of this
Code and Article 545 differ, the requirements of Article 545 shall apply.
545-3. Definitions.
Manufactured Building: "Manufactured Building" means any building
that is of closed construction and is made or assembled in manufacturing
70-584
NATIONAL ELECTRICAL CODE
facilities on or off the building site for installation, or assembly and installation on the building site, other than mobile homes or recreational
vehicles.
Building Component: "Building Component" means any subsystem,
subassembly, or other system designed for use in or integral with or as part
of a structure, which can include structural, electrical, mechanical, plumbing,
and fire protection systems, and other systems affecting health and safety.
Building System: "Building System" means plans, specifications, and
documentation for a system of manufactured building or for a type or a
system of building components, which can include structural, electrical,
mechanical, plumbing, and fire protection systems, and other systems
affecting health and safety, and including such variations thereof as are
specifically permitted by regulation, and which variations are submitted as
part of the building system or amendment thereto.
Closed Construction: "Closed Construction" means any building,
building component, assembly, or system manufactured in such a manner
that all concealed parts of processes of manufacture cannot be inspected
before installation at the building site without disassembly, damage, or
destruction.
545-4. Wiring Methods.
(a) Methods Permitted. All raceway and cable wiring methods included
in this Code and such other wiring systems specifically intended and listed
for use in manufactured buildings shall be permitted with listed fittings and
with fittings listed and identified for manufactured buildings.
(b) Securing Cables. In closed construction, cables shall be permitted
to be secured only at cabinets, boxes, or fittings where No. 10 or smaller
conductors are used and protection against physical damage is provided as
required by Section 300-4.
545-5. Service-Entrance Conductors. Service-entrance conductors shall
meet the requirements of Article 230. Provisions shall be made to route the
service-entrance conductors from the service equipment to the point of
attachment of the service.
(FPN): See Section 310-10 for temperature limitation of conductors.
545-6. Installation of Service-Entrance Conductors. Service-entrance
conductors shall be installed after erection at the building site.
Exception: Where point of attachment is known prior to manufacture.
545-7. Service Equipment Location. Service equipment shall be installed
in accordance with Section 230-70(a).
545-8. Protection of Conductors and Equipment. Protection shall be
provided for exposed conductors and equipment during processes of manufacturing, packaging, in transit, and erection at the building site.