Regl. 5293, art. 520-44(a)-550 dup5
MOBILE HOMES AND MOBILE HOME PARKS 70-599
Cite as Reglamento Núm. 5293, Art. 520-44(a)-550 dup5
(b) Continuity and Operational Tests and Polarity Checks. Each mobile
home shall be subjected to:
(1) An electrical continuity test to ensure that all exposed electrically
conductive parts are properly bonded;
(2) An electrical operational test to demonstrate that all equipment,
except water heaters and electric furnaces, is connected and in working
order; and
(3) Electrical polarity checks of permanently wired equipment and
receptacle outlets to determine that connections have been properly made.
550-13. Calculations. The following method shall be employed in computing the supply-cord and distribution-panelboard load for each feeder
assembly for each mobile home in lieu of the procedure shown in Article
220 and shall be based on a 3-wire, 120/240-volt supply with 120-volt loads
balanced between the two legs of the 3-wire system.
(a) Lighting and Small Appliance Load:
Lighting Volt-Amperes: Length times width of mobile home floor (outside
dimensions) times 3 volt-amperes per square foot; e.g.,
Length X width X 3 =
lighting volt-amperes.
Small Appliance Volt-Amperes: Number of circuits times 1,500 volt-amperes
for each 20-ampere appliance receptacle circuit (see definition of "Appliance, Portable" with note) including 1,500 volt-amperes for laundry circuit; e.g.,
Number of circuits X 1,500 =
small appliance volt-amperes.
Total: Lighting volt-amperes plus small appliance =
total volt-amperes.
First 3,000 total volt-amperes at 100 percent plus remainder at 35 percent
II
volt-amperes to be divided by 240 volts to obtain current (amperes)
per leg.
(b) Total Load for Determining Power Supply. Total load for determining power supply is the summation of:
(1) Lighting and small appliance load as calculated in Section 550-13(a).
(2) Nameplate amperes for motors and heater loads (exhaust fans, air
conditioners, electric, gas, or oil heating).
Omit smaller of the heating and cooling loads, except include blower
motor if used as air-conditioner evaporator motor. Where an air conditioner is not installed and a 40-ampere power-supply cord is provided,
allow 15 amperes per leg for air conditioning.
(3) 25 percent of current of largest motor in (2).
(4) Total of nameplate amperes for: disposal, dishwasher, water
heater, clothes dryer, wall-mounted oven, cooking units.
Where number of these appliances exceeds three, use 75 percent of
total.
(5) Derive amperes for freestanding range (as distinguished from separate ovens and cooking units) by dividing the following values by 240 volts.
70-600
NATIONAL ELECTRICAL CODE
Nameplate Rating
Use
0 thru 10,000 watts
80 percent of rating
Over 10,000 thru 12,500 watts
8,000 volt-amperes
Over 12,500 thru 13,500 watts
8,400 volt-amperes
Over 13,500 thru 14,500 watta
8,800 volt-amperes
Over 14,500 thru 15,500 watts
9,200 volt-amperes
Over 15,500 thru 16,500 watts
9,600 volt-amperes
Over 16,500 thru 17,500 watts
10,000 volt-amperes
(6) If outlets or circuits are provided for other than factory-installed
appliances, include the anticipated load.
See following Example for illustration of application of this calculation.
Example
A mobile home floor is 70 feet X 10 feet and has two small appliance circuits, a
1000-volt-ampere, 240-volt heater, a 200-volt-ampere, 120-volt exhaust fan, a
400-volt-ampere, 120-volt dishwasher, and a 7000-volt-ampere electric range.
Lighting and small appliance load
Lighting 70 X 10 X 3 VA/sq ft =
2100 volt-amperes
Small appliance 1500 X 2=
3000 volt-amperes
Laundry 1500 X 1=
1500 volt-amperes
6600 volt-amperes
1st 3000 volt-amperes at 100 percent
3000 volt-amperes
Remainder (6600 - 3000) at 35 percent
1260 volt-amperes
4260 volt-amperes
4260 volt-amperes
=17.75 amperes per leg
240 volts
Amperes per leg
A
B
Lighting and appliances
17.75