Regl. 5293, art. 620-41
In locations subject to excessive moisture or corrosive
Cite as Reglamento Núm. 5293, Art. 620-41
vapors or gases, supporting members of other materials shall be permitted.
Where steel supporting members are used, they shall run straight through
the center of the cable assembly and shall not be cabled with the copper
strands of any conductor.
In addition to conductors used for control and signaling circuits, Types
E, EO, ET, ETLB, ETP, and ETT elevator cables shall be permitted to
incorporate in the construction one or more No. 20 telephone conductor
pairs, one or more coaxial cables, and/or one or more optical fibers. The
No. 20 conductor pairs shall be permitted to be covered with suitable
shielding for telephone, audio, or higher frequency communication circuits; the coaxial cables consist of a center conductor, insulation, and
Table 400-4. Flexible Cords and Cables
(See Section 400-4)
70-308
Braid
Type
Size
No. of
Nominal
Trade Name
Insulation
on Each
Letter
AWG
Outer Covering
Use
Conductors
Insulation Thickness*
Conductor
AWG
Mils
Lamp Cord
C
18-10
2 or more
Ther-
18-16
30
Cotton
None
Pendant
Dry
Not
moset
or
Loca-
Hard
or
Portions.
Usage
Thermo-
14-10
45
table
plastic
Elevator
E
Three Cotton,
Elevator
Nonhazardous
Cable
See
Outer one
Lighting
Locations
Note
20-16
20
Cotton
Flameand
5.
Retardant &
Control
Moisture-
See
20-14
2 or
Ther-
Flexible
Resistant,
Note
More
moset
20-16
20
Nylon
See Note 3.
9.
Jacket
Three Cotton,
Nonhazardous
NATIONAL ELECTRICAL CODE
Outer one
Locations
Flame-
Retardant &
Moisture-
EO
Resistant.
Elevator
See
See Note 3.
Cable
Note
20-14
2 or
Ther-
20-16
20
Cotton
5.
More
moset
One Cotton
Hazardous
and a
Elevator
(Classified)
Neoprene
Lighting
Locations
Jacket
and
14
30
See Note 3.
Control
See Notes 1 through 9.
*See Note 8.
Table 400-4. (Continued)
ET
20-14
2 or More
Thermo-
20-16
20
Rayon
Three Cotton
Nonhazardous
See
plastic
or equivalent,
Locations
Note 5.
Outer one
Flame-
Retardant &
ETLB
14
30
None
Moisture-
See
Resist.
Note 5.
See Note 3.
Elevator
Cable
ETP
Thermo-
Rayon
Thermoplastic
Hazardous
See
plastic
(Classified)
Note 5.
Locations
ETT
Thermo-
None
One Cotton or
Hazardous
See
plastic
equivalent
(Classified)
Note 5.
and a Ther-
Locations
moplastic
Jacket
Portable
G
8-500
2-6 plus
Ther-
8-2
60
Oil-
Portable, Extra Hard Usage,
Power
kcmil
Grounding
moset
1-4/0
80
Resistant
and as Permitted in Sec-
Cable
Conduc-
250 kcmil-
95
Thermoset
tions 520-68(a) and 530-12.
tor(s)
500 kcmil
ARTICLE 400 FLEXIBLE CORDS AND CABLES
Heater Cord
HPD
18-12
2, 3, or 4
Thermoset
Thermoset
with
Cotton or
Portable
Dry
Not
Asbestos
None
Loca-
Hard
or All
18-16
15
Rayon
Heaters
tions
Usage
Thermoset
14-12
30
Parallel
HPN
18-12
2 or 3
Thermo-
18-16
45
None
Thermosetting
Portable
Damp
Not
Heater
See
setting
14
80
Loca-
Hard
Cord
Note 6.
12
95
tions
Usage
See Notes 1 through 9.
* See Note 8.
70-309
Table 400-4. (Continued)
Braid
Type
Size
No. of
Nominal
70-310
Trade Name
Insulation
on Each
Letter
AWG
Conductors
Outer Covering
Use
Insulation Thickness*
Conductor
AWG
Mils
Thermoset
18-16
15
Cotton
Portable
Extra
Jacketed
HS
14-12
(Thermoset/
and
or
Hard
Heater
Thermoset
HSJ
Asbestos)
Thermoset
Portable
Usage
Cord
with
Heaters
See
Asbestos
18-16
30
Note 7.
18-12
or
(All
Hard
All
Thermoset)
Damp
Usage
HSJO
2, 3, or 4
Ther-
None
Cotton
Locations
See
moset
14-12
30
and Oil-
Note 7.
(Thermoset/
Resistant
Asbestos)
Extra
Hard
HSO
14-12
14-12
45
Usage
(All
Thermoset)
Twisted Porta-
PD
18-10
2 or more
Thermoset
18-16
30
Cotton
Cotton or Rayon
Pendant
Dry
Not
ble Cord
or Ther-
14-10
45
or
Locations
Hard
NATIONAL ELECTRICAL CODE
moplastic
Portable
Usage
Hard Service
S
18-2
2 or more
Thermoset
18-16
30
None
Thermoset
Pendant
Damp
Extra
Cord
See
14-10
45
or
Locations
Hard
Note 4.
8-2
60
Portable
Usage
Flexible Stage
SC
8-250
1 or more
Thermoset
8-2
60
Thermoset**
Portable, Extra Hard Usage,
and Lighting
kcmil
1-4/0
80
and as permitted in Articles
Power Cable
250 kcmil
95
520 and 530
Flexible Stage
SCE
8-250
1 or more
Thermo-
8-2
60
Thermoplastic
Portable, Extra Hard Usage,
and Lighting
kcmil
plastic
1-4/0
80
Elastomer**
and as permitted in Articles
Power Cable
Elastomer
250 kcmil
95
520 and 530
Flexible Stage
SCT
8-250
1 or more
Thermo-
8-2
60
Thermoplastic**
Portable, Extra Hard Usage,
and Lighting
kcmil
plastic
1-4/0
80
and as permitted in Articles
Power Cable
250 kcmil
95
520 and 530
See Notes 1 through 9.
* See Note 8.
**The required outer covering on some single-conductor cables may be integral with the insulation.
Table 400-4. (Continued)
Hard
SE
18-2
2 or more
Thermo-
18-16
30
None
Thermoplastic
Pendant
Damp
Extra
Service
See
plastic
14-10
45
Elastomer
or
Locations
Hard
Cord
Note 4.
Elastomer
8-2
60
Portable
Usage
SEO
Oil-Resistant
See
Thermo-
Note 4.
plastic Elastomer
SEOO
Oil-Resistant
See
Thermo-
Note 4.
plastic
Elastomer
Junior Hard
SJ
Thermoset
Thermoset
Pendant
Damp
Hard
Service
or
Locations
Usage
Cord
SJE
Thermo-
None
Portable
Thermoplastic
plastic
Elastomer
Elastomer
8-12
30
SJEO
Oil-Resistant
Thermoplastic
ARTICLE 400 FLEXIBLE CORDS AND CABLES
Elastomer
SJEOO
Oil-Resistant
Thermoplastic
Elastomer
SJO
18-10
2,3,4,
Thermoset
Oil-Resistant
or 5
Thermoset
See Notes 1 through 9.
*See Note 8.
70-311
Table 400-4. (Continued)
Braid
70-312
Type
Size
No. of
Nominal
Trade Name
Insulation
on Each
Letter
AWG
Conductors
Outer Covering
Use
Insulation Thickness*
Conductor
AWG
Mils
Junior Hard
SJOO
18-10
2, 3, 4,
Oil-
8-12
30
None
Oil-Resistant
Pendant
Damp
Extra
Service Cord
or 5
Resistant
Thermoset
or
Loca-
Hard
Ther-
Portable
tions
Usage
moset
SJT
Thermo-
Thermoplastic
plastic or
10
45
Thermoset
SJTO
Thermoset
Oil-Resistant
or
Thermoplastic
Thermoplastic
SJTOO
Oil-
Oil-Resistant
Resistant
Thermoplastic
Thermo-
NATIONAL ELECTRICAL CODE
plastic or
Thermoset
Hard Service
so
Thermoset
18-16
30
Oil-Resistant
Pendant
Damp
Extra
Cord
See
Thermoset
or
Loca-
Hard
Note 4.
Portable
tions
18-2
2 or more
Usage
SOO
Oil-
14-10
45
Oil-Resistant
See
Resistant
Thermoset
Note 4.
Thermoset
8-2
60
See Notes 1 through 9.
* See Note 8.
Table 400-4. (Continued)
All Thermoset
SP-1
18
18
30
None
Thermoset
Pendant
Damp
Not
Parallel
See
Thermoset
or
Locations
Hard
Cord
Note 6.
Portable
Usage
18-16
45
SP-2
18-16
2 or 3
See
Note 6.
SP-3
18-10
Thermoset
18-16
60
None
Thermoset
Refrigera-
Damp
Not
See
14
80
tors,
Locations
Hard
Note 6.
12
95
Room Air
Usage
10
110
Conditioners,
and as
permitted
in Section
422-8(d)
All Elastomer
SPE-1
18
Thermo-
18
30
None
Thermoplastic
Pendant
Damp
Not
(Thermo-
See
plastic
Elastomer
or
Locations
Hard
plastic)
Note 6.
Elastomer
Portable
Usage
Parallel
18-16
45
Cord
SPE-2
18-16
2 or 3
See
Note 6.
ARTICLE 400 FLEXIBLE CORDS AND CABLES
SPE-3
18-10
18-16
60
None
Thermoplastic
Refrigera-
Damp
Not
See
14
80
Elastomer
tors,
Locations
Hard
Note 6.
12
95
Room Air
Usage
10
110
Conditioners,
and as
permitted
in Section
422-8(d)
All Plastic
SPT-1
18
Thermo-
18
30
None
Thermoplastic
Pendant
Damp
Not
Parallel
See
plastic
or
Locations
Hard
Cord
Note 6.
Portable
Usage
70-313
See Notes 1 through 9.
* See Note 8.
Table 400-4. (Continued)
Nominal
Braid
70-314
Type
Size
No. of
Trade Name
Insulation
Insulation
on Each
Outer Covering
Use
Letter
AWG
Conductors
Thickness*
Conductor
AWG
Mils
All Plastic
SPT-2
18-16
2 or 3
Thermoplastic
18-16
45
None
Thermoplastic
Pendant or
Damp
Not
Parallel Cord
See
Portable
Locations
Hard
Note 6.
Usage
SPT-3
18-10
Thermoplastic
18-16
60
None
Thermoplastic
Refrigera-
Damp
Not
See
14
80
tors, Room
Locations
Hard
Note 6.
12
95
Air Condi-
Usage
10
110
tioners,
and as permitted in
Section
422-8(d)
Range,
SRD
10-4
3 or 4
Thermoset
None
Thermoset
Portable
Damp
Ranges,
Dryer
Locations
Dryers
Cable
10-4
45
SRDE
10-4
3 or 4
Thermoplastic
None
Thermoplastic
Portable
Damp
Ranges,
NATIONAL ELECTRICAL CODE
Elastomer
Elastomer
Locations
Dryers
SRDT
10-4
3 or 4
Thermoplastic
None
Thermoplastic
Portable
Damp
Ranges,
Locations
Dryers
Hard Service
ST
Thermo-
18-16
30
Thermoplastic
Pendant
Extra
Cord
See
plastic or
14-10
45
None
or
Damp
Hard
Note 4.
18-2
2 or more
Thermoset
8-2
60
Portable
Locations
Usage
STO
Oil-Resistant
See
Thermoplastic
Note 4.
STOO
Oil-Resistant
See
Thermo-
Note 4.
plastic or
Thermoset
See Notes 1 through 9.
* See Note 8.
Table 400-4. (Continued)
Vacuum
SV
18-17
2 or 3
Thermoset
18-17
15
None
Thermoset
Pendant
Damp
Not
Cleaner
See
or
Locations
Hard
Cord
Note 6.
Portable
Usage
SVE
Thermo-
Thermoplastic
See
plastic
Elastomer
Note 6.
Elastomer
Oil-Resistant
SVEO
Thermo-
See
plastic
Note 6.
Elastomer
SVEOO
Oil-Resistant
See
Thermo-
Note 6.
plastic
Elastomer
SVO
Thermoset
Oil-Resistant
Thermoset
SVOO
Oil-Resistant
Oil-Resistant
Thermoset
Thermoset
SVT
Thermoset
Thermoplastic
See
or Thermo-
Note 6.
plastic
ARTICLE 400 FLEXIBLE CORDS AND CABLES
SVTO
Thermoset
Oil-Resistant
See
or Thermo-
Thermo-
Note 6.
plastic
plastic
SVTOO
Oil-Resistant
Oil-Resistant
Thermo-
Thermoplastic or
plastic
Thermoset
Parallel
TPT
27
2
Thermo-
27
30
None
Thermoplastic
Attached
Damp
Not
Tinsel
See
plastic
to an
Locations
Hard
Cord
Note 2.
Appliance
Usage
70-315
See Notes 1 through 9.
* See Note 8.
Table 400-4. (Continued)
Nominal
Braid
70-316
Type
Size
No. of
Trade Name
Insulation
Insulation
on Each
Outer Covering
Use
Letter
AWG
Conductors
Thickness*
Conductor
AWG
Mils
TS
Attached
Not
See
to an
Hard
27
2
Thermoset
None
Thermoset
Note 2.
Appli-
Damp
Usage
Jacketed
ance
Locations
Tinsel
27
15
Cord
TST
Thermo-
Thermoplastic
Attached
Not
See
27
plastic
to an
Hard
2
None
Note 2.
Appli-
Damp
Usage
ance
Locations
Portable
W
8-500
1-6
Thermoset
8-2
60
Oil-Resistant
Portable, Extra Hard Usage, and
Power
kcmil
1-4/0 =
80
Thermoset
as Permitted in Sections 520-68
Cable
250 kcmil
95
and 530-12.
500 kcmil
See Notes 1 through 9.
* See Note 8.
NATIONAL ELECTRICAL CODE
ARTICLE 400 - FLEXIBLE CORDS AND CABLES
70-317
shield for use in video or other radio frequency communication circuits.
The optical fiber shall be suitably covered with flame-retardant thermoplastic. The insulation of the conductors shall be rubber or thermoplastic of thickness not less than specified for the other conductors of the
particular type of cable. Metallic shields shall have their own protective
covering. Where used, these components shall be permitted to be incorporated in any layer of the cable assembly but shall not run straight
through the center.
6. The third conductor in these cables shall be used for equipment
grounding purposes only.
7. The individual conductors of all cords, except those of heatresistant cords, shall have a thermoset or thermoplastic insulation, except
that the grounding conductor where used shall be in accordance with Section 400-23(b). Unvulcanized rubber compounds shall be permitted to be
used for all sizes of heater cord Types HSJ and HSJO, and for sizes No.
18 and 16 Type HPD.
8. Where the voltage between any two conductors exceeds 300, but
does not exceed 600, flexible cord of Nos. 10 and smaller shall have thermoset or thermoplastic insulation on the individual conductors at least
45 mils in thickness, unless Type S, SE, SEO, SEOO, SO, SOO, ST, STO,
or STOO cord is used.
9. Insulations and outer coverings that meet the requirements as flameretardant, limited-smoke, and are so listed, shall be permitted to be designated limited-smoke with the suffix /LS after the Code type designation.
400-5. Ampacities for Flexible Cords and Cables. Table 400-5(A) provides the allowable ampacities and Table 400-5(B) provides the ampacities
for flexible cords and cables with not more than three current-carrying
conductors. If the number of current-carrying conductors exceeds three,
the allowable ampacity or the ampacity of each conductor shall be reduced
from the 3-conductor rating as shown in the following table:
Percent of Value
Number of
in Tables 400-5(A)
Conductors
and 400-5(B)
4 through 6
80
7 through 9
70
10 through 20
50
21 through 30
45
31 through 40
40
41 and above
35
Ultimate Insulation Temperature. In no case shall conductors be associated together in uch a way with respect to the kind of circuit, the wiring
method used, or the number of conductors such that the limiting temperature of the conductors is exceeded.
70-318
NATIONAL ELECTRICAL CODE
A neutral conductor that carries only the unbalanced current from other
conductors of the same circuit need not be considered as a currentcarrying conductor.
In a 3-wire circuit consisting of two phase wires and the neutral of a
4-wire, 3-phase wye-connected system, a common conductor carries
approximately the same current as the other conductors and shall be considered a current-carrying conductor.
On a 4-wire, 3-phase wye circuit where the major portion of the load
consists of nonlinear loads such as electric-discharge lighting, electronic
computer/data processing, or similar equipment, there are harmonic currents present in the neutral conductor, and the neutral shall be considered
to be a current-carrying conductor.
An equipment grounding conductor shall not be considered a currentcarrying conductor.
Where a single conductor is used for both equipment grounding and to
carry unbalanced current from other conductors, as provided for in Section
250-60 for electric ranges and electric clothes dryers, it shall not be considered as a current-carrying conductor.
Exception: For other loading conditions, adjustment factors shall be
permitted to be calculated under Section 310-15(b).
(FPN): See Appendix B, Table B-310-11 for adjustment factors for more than
three current-carrying conductors in a raceway or cable with load diversity.
400-6. Markings.
(a) Standard Markings. Flexible cords and cables shall be marked by
means of a printed tag attached to the coil reel or carton. The tag shall
contain the information required in Section 310-11(a).
Types S, SC, SCE, SCT, SE, SEO, SEOO, SJ, SJE, SJEO, SJEOO,
SJO, SJT, SJTO, SJTOO, SO, SOO, ST, STO, and STOO flexible cords
and G and W flexible cables shall be durably marked on the surface at
intervals not exceeding 24 inches (610 mm) with the type designation, size,
and number of conductors.
(b) Optional Markings. Flexible cords and cable types listed in Table
400-4 shall be permitted to be surface marked to indicate special characteristics of the cable materials.
(FPN): Examples of these markings include, but are not limited to, "LS" for
limited-smoke and markings such as "sunlight-resistant."
400-7. Uses Permitted.
(a) Uses. Flexible cords and cables shall be used only for (1) pendants;
(2) wiring of fixtures; (3) connection of portable lamps or appliances; (4)
elevator cables; (5) wiring of cranes and hoists; (6) connection of stationary equipment to facilitate their frequent interchange; (7) prevention of the
transmission of noise or vibration; (8) appliances where the fastening
means and mechanical connections are specifically designed to permit
ready removal for maintenance and repair, and the appliance is intended or
identified for flexible cord connection; (9) data processing cables as permitted by Section 645-5; (10) connection of moving parts; or (11) temporary
wiring as permitted in Sections 305-4(b) and 305-4(c).
ARTICLE 400 - FLEXIBLE CORDS AND CABLES
70-319
Table 400-5(A). Allowable Ampacity for Flexible Cords and Cables
[Based on Ambient Temperature of 30°C (86°F). See Section 400-13 and Table 400-4.]
Size
Thermoset
Thermoset Types
Types
Type
C, E, EO, PD, S, SJ, SJO,
AFS,
TS
SJOO, so, soo, SP-1, SP-2,
AFSJ,
AWG
SP-3, SRD, SV, svo, SVOO
HPD,
HPN,
Thermo-
Thermoplastic
HS,
plastic
Types ET, ETLB, ETT, SE,
HSJ,
Types
SEO, SJE, SJEO, SJT, SJTO,
HSJO,
TPT,
SJTOO, SPE-1, SPE-2, SPE-3,
HSO
TST
SPT-1, SPT-2, SPT-3, ST, SRDE,
SRDT, STO. STOO, SVE, SVEO,
SVT, SVTO, SVTOO
At
Bt
27*
0.5
20
5**
7**
18
7
10
10
17
12
16
10
13
15
15
17'
14
15
18
20
12
20
25
30
10
25
30
35
8
35
40
6
45
55
4
60
70
2
80
95
* Tinsel cord.
Elevator cables only.
t The allowable currents under subheading A apply to 3-conductor cords and other multiconductor cords connected to utilization equipment so that only 3 conductors are currentcarrying. The allowable currents under subheading B apply to 2-conductor cords and other
multiconductor cords connected to utilization equpment so that only 2 conductors are
current-carrying.
(FPN): It is intended that this table be used in conjunction with applicable end-use product standards to ensure selection of the proper size and type.
(b) Attachment Plugs. Where used as permitted in subsections (a)(3),
(a)(6), and (a)(8) of this section, each flexible cord shall be equipped with
an attachment plug and shall be energized from a receptacle outlet.
Exception: As permitted in Section 364-8.
400-8. Uses Not Permitted. Unless specifically permitted in Section
400-7, flexible cords and cables shall not be used (1) as a substitute for the
I
fixed wiring of a structure; (2) where run through holes in walls, ceilings,
or floors; (3) where run through doorways, windows, or similar openings;
(4) where attached to building surfaces; (5) where concealed behind building walls, ceilings, or floors; or (6) where installed in raceways, except as
otherwise permitted in this Code.
70-320
NATIONAL ELECTRICAL CODE
Exception: Flexible cord and cable shall be permitted to have one connection to the building surface for a suitable tension take-up device.
Length of the cord or cable from the supply termination to the take-up
device shall be limited to 6 feet (1.83 m).
Table 400-5(B). Ampacity of Cable Types SC, SCE, SCT, G, and W.
[Based on Ambient Temperature of 30°C (86°F). See Table 400-4.]
Temperature Rating of Cable
Size
60°C (140°F)
75°C (167°F)
90°C (194°F)
AWG/
kcmil
D
E
F
D
E
F
D
E
F
8
60
55
48
70
65
57
80
74
65
6
80
72
63
95
88
77
105
99
87
4
105
96
84
125
115
101
140
130
114
3
120
113
99
145
135
118
165
152
133
2
140
128
112
170
152
133
190
174
152
1
165
150
131
195
178
156
220
202
177
1/0
195
173
151
230
207
181
260
234
205
2/0
225
199
174
265
238
208
300
271
237
3/0
260
230
201
310
275
241
350
313
274
4/0
300
265
232
360
317
277
405
361
316
250
340
296
259
405
354
310
455
402
352
300
375
330
289
445
395
346
505
449
393
350
420
363
318
505
435
381
570
495
433
400
455
392
343
545
469
410
615
535
468
500
515
448
392
620
537
470
700
613
536
The ampacities under subheading D are permitted for single-conductor Types SC, SCE,
SCT, and W cable only where the individual conductors are not installed in raceways and
are not in physical contact with each other except in lengths not to exceed 24 inches
(610 mm) where passing through the wall of an enclosure.
The ampacities under subheading E apply to 2-conductor cables and other multiconductor
cables connected to utilization equipment so that only 2 conductors are current-carrying.
The ampacities under subheading F apply to 3-conductor cables and other multiconductor
cables connected to utilization equipment so that only 3 conductors are current-carrying.
400-9. Splices. Flexible cord shall be used only in continuous lengths
without splice or tap when initially installed in applications permitted by