(b) Conductor Insulation. Storage-battery leads shall be rubber-covered
or thermoplastic-covered.
640-10. Circuit Overcurrent Protection. Overcurrent protection shall be
provided as follows:
(a) Heater or Filament (Cathode). Circuits to the heater or filament
(cathode) of an electronic tube shall have overcurrent protection not
exceeding 15 amperes where supplied by lighting branch circuits or by
storage batteries exceeding 20 ampere-hour capacity.
(b) Plate (Anode-Positive). Circuits to the plate (anode-positive) and to
the screen grid of an electronic tube shall have overcurrent protection not
exceeding 1.0 ampere.
(c) Control Grid. Circuits to the control grid of an electronic tube shall
have overcurrent protection not exceeding 1.0 ampere where supplied by
lighting branch circuits or by storage batteries exceeding 20 ampere-hour
capacity.
(d) Location. Overcurrent devices shall be located as near as practicable to the source of power supply.