Regl. 5293, art. 620-7-645 dup2
ELECTRONIC COMPUTER/DATA
Cite as Reglamento Núm. 5293, Art. 620-7-645 dup2
PROCESSING EQUIPMENT
645-1. Scope. This article covers equipment, power-supply wiring,
equipment interconnecting wiring, and grounding of electronic computer/
data processing equipment and systems, including terminal units, in an
electronic computer/data processing room.
(FPN): For further information, see Protection of Electronic Computer/Data
Processing Equipment, NFPA 75-1992 (ANSI).
645-2. Special Requirements for Electronic Computer/Data Processing
Equipment Room. This article applies provided all the following conditions are met:
(1) Disconnecting means complying with Section 645-10 are provided.
(2) A separate heating/ventilating/air conditioning (HVAC) system is
provided that is dedicated for electronic computer/data processing equipment use and is separated from other areas of occupancy. Any HVAC
system that serves other occupancies may also serve the electronic
computer/data processing equipment room if fire/smoke dampers are provided at the point of penetration of the room boundary. Such dampers shall
operate on activation of smoke detectors and also by operation of the disconnecting means required by Section 645-10.
(FPN): For further information, see Protection of Electronic Computer/Data
Processing Equipment, NFPA 75-1992 (ANSI).
(3) Listed electronic computer/data processing equipment is installed.
(FPN): For further information, see Protection of Electronic Computer/Data
Processing Equipment, NFPA 75-1992 (ANSI), Section 5-1.1.
(4) Occupied only by those personnel needed for the maintenance and
functional operation of the installed electronic computer/data processing
equipment.
70-672
NATIONAL ELECTRICAL CODE
(FPN): The computer room is not to be used for the storage of combustibles
beyond that necessary for the day-to-day operation of the equipment. For further
information, see Protection of Electronic Computer/Data Processing Equipment,
NFPA 75-1992 (ANSI).
(5) The room is separated from other occupancies by fire-resistant-rated
walls, floors, and ceilings with protected openings.
(6) The building construction, rooms, or areas and occupancy comply
with the applicable building code.
645-5. Supply Circuits and Interconnecting Cables.
(a) Branch Circuit Conductors. The branch circuit conductors supplying one or more units of a data processing system shall have an ampacity
not less than 125 percent of the total connected load.
(b) Connecting Cables. The data processing system shall be permitted
to be connected to a branch circuit by any of the following means listed for
the purpose:
(1) Computer/data processing cable and attachment plug cap.
(2) Flexible cord and an attachment plug cap.
(3) Cord-set assembly. Where run on the surface of the floor, they
shall be protected against physical damage.
(c) Interconnecting Cables. Separate data processing units shall be permitted to be interconnected by means of cables and cable assemblies listed
for the purpose. Where run on the surface of the floor, they shall be protected against physical damage.
(d) Under Raised Floors. Power cables, communications cables, connecting cables, interconnecting cables, and receptacles associated with the
data processing equipment shall be permitted under a raised floor, provided:
(1) The raised floor is of suitable construction and the area under the
floor is accessible.
(FPN): See Protection of Electronic Computer/Data Processing Equipment,
NFPA 75-1992 (ANSI).
(2) The branch-circuit supply conductors to receptacles or field-wired
equipment are in rigid metal conduit, rigid nonmetallic conduit, intermediate metal conduit, electrical metallic tubing, metal wireway, surface metal
raceway with metal cover, flexible metal conduit, liquidtight flexible metal
or nonmetallic conduit, Type MI cable, Type MC cable, or Type AC cable.
These supply conductors shall be installed in accordance with the requirements of Section 300-11.
(3) Ventilation in the underfloor area is used for the data processing
equipment and data processing area only.
(4) Openings in raised floors for cables protect cables against abrasions
and minimize the entrance of debris beneath the floor.
(5) Cables, other than those covered in (2) above, shall be listed as
Type DP cable having adequate fire-resistance characteristics suitable for
use under raised floors of a computer room. This listing requirement shall
become effective July 1, 1994.