Regl. 5293, art. 630-21
Resolución 2535: adopta el Código Eléctrico Nacional, versión 1993. (Sustituye el Anejo A del Reglamento 4435)
Cite as Reglamento Núm. 5293, Art. 630-21
85
85
90
140
Periodic Duty
Rolls, ore- and coal-handling
machines, etc.
85
90
95
140
Varying Duty
110
120
150
200
Any motor application shall be considered as continuous duty unless the nature of the
apparatus it drives is such that the motor will not operate continuously with load under any
condition of use.
(b) Separate Terminal Enclosure. The conductors between a stationary
motor rated 1 horsepower or less and the separate terminal enclosure permitted in Section 430-145(b) shall be permitted to be smaller than No. 14
but not smaller than No. 18, provided they have an ampacity as specified
in (a) above.
430-23. Wound-Rotor Secondary.
(a) Continuous Duty. For continuous duty, the conductors connecting
the secondary of a wound-rotor alternating-current motor to its controller
shall have an ampacity not less than 125 percent of the full-load secondary
current of the motor.
(b) Other than Continuous Duty. For other than continuous duty, these
conductors shall have an ampacity, in percent of full-load secondary current, not less than that specified in Table 430-22(a), Exception.
(c) Resistor Separate from Controller. Where the secondary resistor is
separate from the controller, the ampacity of the conductors between controller and resistor shall not be less than that shown in Table 430-23(c).
70-398
NATIONAL ELECTRICAL CODE
Table 430-23(c). Secondary Conductor
Ampacity of Conductor in
Percent of Full-Load
Resistor Duty Classification
Secondary Current
Light starting duty
35
Heavy starting duty
45
Extra-heavy starting duty
55
Light intermittent duty
65
Medium intermittent duty
75
Heavy intermittent duty
85
Continuous duty
110
430-24. Several Motors or a Motor(s) and Other Load(s). Conductors
supplying several motors, or a motor(s) and other load(s), shall have an
ampacity at least equal to the sum of the full-load current rating of all the
motors, plus 25 percent of the highest rated motor in the group, plus the
ampere rating of other loads determined in accordance with Article 220 and
other applicable sections.
Exception No. 1: Where one or more of the motors of the group are
used for short-time, intermittent, periodic, or varying duty, the ampere
rating of such motors to be used in the summation shall be determined in
accordance with Section 430-22(a), Exception No. 1. For the highest rated
motor, the greater of either the ampere rating from 430-22(a), Exception
No. 1 or the largest continuous duty motor full-load current multiplied by
1.25 shall be used in the summation.
Exception No. 2: The ampacity of conductors supplying motor-operated
fixed electric space heating equipment shall conform with Section 424-3(b).
Exception No. 3: Where the circuitry is interlocked so as to prevent
operation of selected motors or other loads at the same time, the conductor ampacity shall be permitted to be based on the summation of the currents of the motors and other loads to be operated at the same time that
results in the highest total current.
(FPN): See Chapter 9, Example No. 8.
430-25. Multimotor and Combination-Load Equipment. The ampacity of
the conductors supplying multimotor and combination-load equipment
shall be not less than the minimum circuit ampacity marked on the equipment in accordance with Section 430-7(d). Where the equipment is not
factory-wired and the individual nameplates are visible in accordance with
Section 430-7(d)(2), the conductor ampacity shall be determined in accordance with Section 430-24.
430-26. Feeder Demand Factor. Where reduced heating of the conductors results from motors operating on duty-cycle, intermittently, or from all
motors not operating at one time, the authority having jurisdiction shall be
permitted to grant permission for feeder conductors to have an ampacity
less than specified in Section 430-24, provided the conductors have sufficient ampacity for the maximum load determined in accordance with the
sizes and number of motors supplied and the character of their loads and
duties.
ARTICLE 430 - MOTOR CIRCUITS, CONTROLLERS
70-399
430-27. Capacitors with Motors. Where capacitors are installed in motor
circuits, conductors shall comply with Sections 460-8 and 460-9.
430-28. Feeder Taps. Feeder tap conductors shall have an ampacity not
less than that required by Part B, shall terminate in a branch-circuit protective device and, in addition, shall meet one of the following requirements: (1)
be enclosed by either an enclosed controller or by a raceway, be not more
than 10 feet (3.05 m) in length, and, for field installation, be protected by an
overcurrent device on the line side of the tap conductor, the rating or setting
of which shall not exceed 1000 percent of the tap conductor ampacity; or (2)
have an ampacity of at least one-third that of the feeder conductors, be protected from physical damage and be not more than 25 feet (7.62 m) in length;
or (3) have the same ampacity as the feeder conductors.
Exception: Feeder Taps Over 25 Feet (7.62 m) Long. In high-bay manufacturing buildings [over 35 feet (10.67 m) high at walls] conductors
tapped to a feeder shall be permitted to be not over 25 feet (7.62 m) long
horizontally and not over 100 feet (30.5) total length where all of the following conditions are met:
a. The ampacity of the tap conductors is not less than one-third that
of the feeder conductors.
b. The tap conductors terminate with a single circuit breaker or a
single set of fuses conforming with (1) Part D if the tap is a branch circuit
or (2) Part E if the tap is a feeder.
c. The tap conductors are suitably protected from physical damage
and are installed in raceways.
d. The tap conductors are continuous from end-to-end and contain
no splices.
e. The tap conductors shall be No. 6 copper or No. 4 aluminum or
I
larger.
f. The tap conductors shall not penetrate walls, floors, or ceilings.
g. The tap shall not be made less than 30 feet (9.14 m) from the floor.
430-29. Constant Voltage DC Motors - Power Resistors. Conductors
connecting the motor controller to separately mounted power accelerating
and dynamic braking resistors in the armature circuit shall have an ampacity not less than the value calculated from Table 430-29 using motor fullload current. If an armature shunt resistor is used, the power accelerating
resistor conductor ampacity shall be calculated using the total of motor
full-load current and armature shunt resistor current.
Armature shunt resistor conductors shall have an ampacity of not less
than that calculated from Table 430-29 using rated shunt resistor current as
full-load current.
C. Motor and Branch-Circuit Overload Protection
430-31. General. Part C specifies overload devices intended to protect
motors, motor-control apparatus, and motor branch-circuit conductors
against excessive heating due to motor overloads and failure to start.
70-400
NATIONAL ELECTRICAL CODE
Table 430-29. Conductor Rating Factors for Power Resistors
Time in Seconds
Ampacity of Conductor in Percent
On
Off
of Full-Load Current
5
75
35
10
70
45
15
75
55
15
45
65
15
30
75
15
15
85
Continuous Duty
110
Overload in electrical apparatus is an operating overcurrent that, when
it persists for a sufficient length of time, would cause damage or dangerous
overheating of the apparatus. It does not include short circuits or ground
faults.
These provisions shall not be interpreted as requiring overload protection where it might introduce additional or increased hazards, as in the
case of fire pumps.
(FPN): See Installation of Centrifugal Fire Pumps, NFPA 20-1990 (ANSI).
The provisions of Part C shall not apply to motor circuits rated over 600
volts, nominal. See Part J.
(FPN): See Chapter 9, Example No. 8.
430-32. Continuous-Duty Motors.
(a) More than 1 Horsepower. Each continuous-duty motor rated more
than 1 horsepower shall be protected against overload by one of the following means:
(1) A separate overload device that is responsive to motor current.
This device shall be selected to trip or rated at no more than the following
percent of the motor nameplate full-load current rating.
Motors with a marked service factor not less than 1.15
125%
Motors with a marked temperature rise not over 40° C
125%
All other motors
115%
Modification of this value shall be permitted as provided in Section
430-34.
For a multispeed motor, each winding connection shall be considered
separately.
Where a separate motor overload device is so connected that it does not
carry the total current designated on the motor nameplate, such as for
wye-delta starting, the proper percentage of nameplate current applying to
the selection or setting of the overload device shall be clearly designated
on the equipment, or the manufacturer's selection table shall take this into
account.
ARTICLE 430 - MOTOR CIRCUITS, CONTROLLERS
70-401
(2) A thermal protector integral with the motor, approved for use with
the motor it protects on the basis that it will prevent dangerous overheating of the motor due to overload and failure to start. The ultimate trip current of a thermally protected motor shall not exceed the following percentage of motor full-load current given in Tables 430-148, 430-149, and
430-150.
Motor full-load current not exceeding 9 amperes
170%
Motor full-load current 9.1 to and including 20 amperes
156%
Motor full-load current greater than 20 amperes
140%
If the motor current-interrupting device is separate from the motor and
its control circuit is operated by a protective device integral with the
motor, it shall be so arranged that the opening of the control circuit will
result in interruption of current to the motor.
(3) A protective device integral with a motor that will protect the
motor against damage due to failure to start shall be permitted if the motor
is part of an approved assembly that does not normally subject the motor
to overloads.
(4) For motors larger than 1500 horsepower, a protective device having embedded temperature detectors that cause current to the motor to be
interrupted when the motor attains a temperature rise greater than marked
on the nameplate in an ambient of 40°C.
(b) One Horsepower or Less, Nonautomatically Started.
(1) Each continuous-duty motor rated at 1 horsepower or less that is
not permanently installed, is nonautomatically started, and is within sight
from the controller location shall be permitted to be protected against overload by the branch-circuit short-circuit and ground-fault protective device.
This branch-circuit protective device shall not be larger than that specified
in Part D of Article 430.
Exception: Any such motor shall be permitted on a nominal 120-volt
branch circuit protected at not over 20 amperes.
(2) Any such motor that is not in sight from the controller location
shall be protected as specified in Section 430-32(c). Any motor rated at
1 horsepower or less that is permanently installed shall be protected in
accordance with Section 430-32(c).
(c) One Horsepower or Less, Automatically Started. Any motor of 1
horsepower or less that is started automatically shall be protected against
overload by one of the following means:
(1) A separate overload device that is responsive to motor current.
This device shall be selected to trip or rated at no more than the following
percentage of the motor nameplate full-load current rating.
Motors with a marked service factor not less than 1.15
125%
Motors with a marked temperature rise not over 40°C.
125%
All other motors
115%
70-402
NATIONAL ELECTRICAL CODE
For a multispeed motor, each winding connection shall be considered
separately. Modification of this value shall be permitted as provided in