(d) Panelboards. A panelboard, not part of the service equipment, shall
have an equipment grounding conductor installed between its grounding
terminal and the grounding terminal of the service equipment. This conductor shall be sized in accordance with Table 250-95 but not smaller than
No. 12. It shall be an insulated conductor and shall be installed with the
feeder conductors in rigid metal conduit, intermediate metal conduit, or
rigid nonmetallic conduit. The equipment grounding conductor shall be
connected to an equipment grounding terminal of the panelboard.
Exception No. 1: The equipment grounding conductor between an existing remote panelboard and the service equipment shall not be required to
be in one of the conduits listed in paragraph (d) if the interconnection is by
means of a flexible metal conduit or an approved cable assembly with an
insulated or covered equipment grounding conductor.
Exception No. 2: Electrical metallic tubing shall be permitted to be used
to protect conductors where installed on or within the building.
(FPN): For permitted use of electrical metallic tubing, see Section 348-1.
(e) Cord-Connected Equipment. Where fixed or stationary equipment is
connected with a flexible cord to facilitate removal or disconnection for
maintenance, repair, or storage as provided in Section 680-7, the equipment grounding conductors shall be connected to a fixed metal part of the
70-706
NATIONAL ELECTRICAL CODE
assembly. The removable part shall be mounted on or bonded to the fixed
metal part.
(f) Other Equipment. Other electrical equipment shall be grounded in
accordance with Article 250 and connected by wiring methods of Chapter 3.
680-26. Electrically Operated Pool Covers.
(a) Motors and Controllers. The electric motors, controllers, and wiring
shall be located at least 5 feet (1.52 m) from the inside wall of the pool
unless separated from the pool by a wall, cover, or other permanent barrier. Electric motors installed below grade level shall be of the totally
enclosed type.
(FPN No. 1): For cabinets installed in damp and wet locations, see Section
373-2(a).
(FPN No. 2): For switches or circuit breakers installed in a wet location, see